video corpo

PAX P, DP
6Pages

{{requestButtons}}

Catalog excerpts

PAX P, DP - 1

- 1-channel model PAX P and 2-channel model PAXDP - 5 digits, 14 mm high LEDs, annunciators - Input signal 4...20 mA and 0...10 VDC - 20 measurements/s (PAX P) - 5,3 bis 105,3 measurements/s, selectable (PAX DP) - 2, resp. 3 programmable user inputs - Protection class IP65 - Working temperature 0 to 50 °C, - Easy programming directly, or via PC - Plug-in output-cards: analog, USB, Relay (thresholds), Transistor, RS232, Profibus - Summation, min-/max value display - 16 point scaling - two galvanically isolated input channels (PAX DP)

Open the catalog to page 1
PAX P, DP - 2

TECHNICAL DATA Display 5 digits, 14 mm high, red LEDs Panel cut-out MAX, MIN, TOT (sum), SP1, SP2, SP3, SP4 (the respective output SP is active) A, B, C (respective programmable display of the channel), SP1, SP2, SP3, SP4 (the respective output is active) Programmable user inputs 3 (PAX P), 2 (PAX DP), logic state: jumper selectable for sink/source logic 10 (-1 to 13), accuracy (18-28 °C): 0.03% of reading, display resolution 1 mV 20 (-26 to 26), accuracy (18-28 °C): 0.03% of reading, display resolution 1 µA 20 (-2 to 26), accuracy (18-28 °C): 0.03% of reading, display resolution 1 µA 10...

Open the catalog to page 2
PAX P, DP - 3

Display readout legends optional custom units overlay Setpoint alarm annunciators Panel cut-out Connections PADDP

Open the catalog to page 3
PAX P, DP - 4

The display can be fitted with up to three optional plug-in cards. The details for each plug-in card can be reviewed in the specification section below. Only one card from each function type can be installed at one time. The plug-in cards can be installed initially or at a later date. Analog Output Card (retransmitted linear DC output): PAXCDL10: - Types: 0 to 20 mA, 4 to 20 mA, or 0 to 10 VDC. - Isolation to sensor + user input commons: 500 Vrms for 1 min., working range 50V, not isolated from all other commons. - Accuracy: 0.17 % of FS (10 to 28 degree Celsius), 0.4% (0 to 50 degree...

Open the catalog to page 4
PAX P, DP - 5

PROGRAMMING Directly by the displays keys DISPLAY MODE: The meter normally operates in the Display Mode. In this mode, the meter displays can be viewed consecutively by pressing the DSP key. The annunciators to the left of the display indicate which display is currently shown; Max Value (MAX), Min Value (MIN), or Totalizer Value (TOT). Each of these displays can be locked from view through programming. (See Module 3) The Input Display Value is shown with no annunciator. PROGRAMMING MODE: Two programming modes are available: Full Programming Mode permits all parameters to be viewed and...

Open the catalog to page 5
PAX P, DP - 6

PAXP000B Voltage supply: 85 to 250 VAC Voltage supply: 85 to 250 VAC PAXDP00B Voltage supply: 85 to 250 VAC Plug-in cards Software PAXCDC20 Serial communication card RS232, terminal ProLOG on request PAXCDC50 Interface card PROFIBUS-DP PAXCDL10 Analog output card PAXCDS10 Dual relay, Form-C, normally open & closed PAXCDS20 Quad relay, Form-A, normally open only PAXCDS30 Quad sinking NPN open collector PAXCDS40 Quad sourcing PNP open collector PAXCDC2C Serial communication card RS232, 9 pole SUB-D connector Miscellaneous Housings PAXLBK10 Units...