Catalog excerpts

condensing boilers and cascade systems-3

ECODENSE condensing boilers provide high-efficiency energy generation with their “Premix Technology" and “Condensing Technology". Providing an advantage in boiler room plannings and conversions with its compact structure in terms of area of use, ECODENSE condensing boilers, when used as CASCADE, meet high-capacity energy requirements with line-up operation and also expand the life-cycle by ensuring equal aging in boilers.

 Open the catalog to page 3
condensing boilers and cascade systems-4

CONDENSING TECHNOLOGY At the end of the combustion process, a large proportion of heat is released outside along with flue gases. The condensing technology does not allow releasing of this heat; provides higher energy saving. In the heat exchanger, the heat of water is drawn and sent to the heating system. When compared with a conventional combustion system, more than 100% of energy in the fuel used can be converted into heat. CASCADE SYSTEM In these systems, multiple devices that are connected to each other engage/disengage as needed. In the cascade systems, all devices operate as modulating...

 Open the catalog to page 4
condensing boilers and cascade systems-5

CONTROL PANEL FEATURES 1 - Selectable system control language from the languages defined in languages options. 2 - You can control the system using weekly time program and set the system to turn on/off 3 times a day. The system operates in comfort mode during programmed periods and in economy mode at other times for economic use. 3 - Controller can be used to add vacation mode for the heating circuit. During vacation period, the heating circuit operates according to the freezing temperature or economy temperature for energy efficiency. 4 - You may control the heating circuit by parameters presented...

 Open the catalog to page 5
condensing boilers and cascade systems-6

LUT-S SERIES IUHLL HUNG CONDENSING BOILER SPECIFICATIONS • High efficiency with Premix condensing technology and micro-flame metal fiber coated steel burner, • 3 different capacity option: 45 kW, 55kW and 65 kW- in WT-S series stainless steel heat exchanger condensing boilers and up to1040 kW in CASCADE systems, • Low energy consumption with integrated modulated primary circulation pump, • When used as CASCADE, the panel on the boiler allows controlling 16 boilers + 1 outdoor sensor + 1 mixing valve, • Provides energy saving through 5:1 modulating operation, • Allows simple control with illuminated...

 Open the catalog to page 6
condensing boilers and cascade systems-8

"ECODENSE" economic and enviromentally friendly solutions to individual and central heating systems -Compact design, -High energy efficiency, -Low polluting emissions, -Operation in lower sound level

 Open the catalog to page 8
condensing boilers and cascade systems-9

OR WIDE RRNGE OF CAPACITIES

 Open the catalog to page 9
condensing boilers and cascade systems-10

LUT SERIES LUHLL HUNG CONDENSING BOILER • High efficiency with Premix condensing technology and micro-flame metal fiber coated steel burner, • 6 different capacity option between 65 kW-150 kW in WT series aluminum spiral heat exchanger condensing boilers and up to 2400 kW in CASCADE systems • When used as CASCADE, the panel on the boiler allows controlling 16 boilers + 1 outdoor sensor + 1 mixing valve, • Provides energy saving through 5:1 modulating operation, • Allows simple control with illuminated LCD panel which provides ease of use; and error codes and boiler information can be displayed...

 Open the catalog to page 10
condensing boilers and cascade systems-12

FLOOR TVPE CONDENSING BOILER SPECIFICATIONS • Homogenous heat distribution with Premix condensing technology and micro-flame metal fiber coated steel burner, • Aluminum silicate alloy cast casing exchanger that provides high operating efficiency with high heat transfer, • A wide option of capacity up to 200 kW- 550 kW in individual boilers and up to 8800 kW in CASCADE systems, • Provides energy saving through 5:1 modulating operation, • Allows cascade connection up to total 16 boilers, including 1 master and 15 slave boilers, • Allows simple control with illuminated LCD panel which provides ease...

 Open the catalog to page 12
condensing boilers and cascade systems-14

ROOFTOP SERIES CONDENSING BOILER ECODENSE Roof Top condensing boilers offer solution in hot water production for rooftop outdoor installation in many applications such as shopping centers, office buildings, hospitals and hotels. ECODENSE condensing boilers, when used as CASCADE, meet high-capacity energy requirements with line-up operation and also expand the life-cycle by ensuring equal aging in boilers. SPECIFICATIONS • High efficiency with premix condensing technology and micro-flame metal fiber coated steel burner, • Provides energy saving through 5:1 modulating operation, • 10 different...

 Open the catalog to page 14
condensing boilers and cascade systems-15

BOILER SAFETY • When outdoor temperature goes below +4 °C, the boiler automatically protects itself and prevents from freezing. • The boiler protects itself, when the temperature of flue gas exceeds the set value during operation, • The boiler protects itself during unexpected high temperatures with combustion space safety thermostat. • Primer hydraulic circuit circulating pump, • Inlet and return collectors in size according to installed total • Check valve in inlet line and safety valve in return line of the • Ball valves in both inlet and return lines of the boilers, • Balance container with...

 Open the catalog to page 15
condensing boilers and cascade systems-16

OPTIONAL ACCESSORIES Circulation Pump: High efficiency circulation pump provides energy saving. Checkvalve: It must be installed on the installation according to the check valve circuit diagram with the appropriate connection diameter. 6 bar safety valve:A spring-loaded safety valve must be fitted on the installation in accordance with the circuit diagram of the valve without other restriction. r QAC Outside Sensor: Operable at the range of -50°C to 70°C. Allows connection at maximum 120 meters using cable with 1.5 mm2 section. +1/-1 Kelvin tolerance. QAD36 Strap-On Temperature Sensor: Operable...

 Open the catalog to page 16
condensing boilers and cascade systems-17

Webserver You can connect to the web server device from anywhere in the world to monitor and control your system. • Remote access to your facility, and monitoring operating values, • Adjustment of system hour, minute and year details, • Language selection setting, • Time program setting (Heating circuit, boiler, external time program) • Vacation mode setting for heating circuits (controlling the heating circuit as per the anti-freeze protection mode in buildings for prolonged non-use) • Changing temperature values of heating circuits, • Setting boiler operating temperature and changing the boiler’s...

 Open the catalog to page 17
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.