QS2_SERIES

QS2_SERIES

Product catalog summary
Overview: This document provides technical specifications and operational guidelines for a three-phase electromechanical control panel designed for two motor pumps. It includes details on power supply, inputs, controls, signals, protection, alarms, and operating conditions.
Technical Specifications:
  • Power Supply: 3 ~ 50/60Hz 400V ± 10%
  • Main Features: Main disconnecting switch with door lock, transformer for auxiliary circuits, contactor for each motor, adjustable timer changeover Star Delta Star (0.1 ÷ 600s), exchanger, and protection degree IP 55.
Inputs:
  • Six extra low voltage inputs for emergency stop, functional start and stop, maximum level alarm, and engine block due to temperature sensor tripping.
Controls and Signals:
  • Selector for MANUAL-AUTOMATIC-OFF for each engine.
  • Five indicator lights for power supply presence, motor pump operation, and motor protection tripping.
Protection and Alarms:
  • Thermal relay sensitive to phase loss, motor protection fuses, auxiliary circuit fuses, and alarm output for overload protection or maximum level reached.
Operating Conditions:
  • Ambient temperature range: -5 / +40°C
  • Relative humidity: 50% at 40°C
Model Specifications:
  • Various models are listed with specifications including power (HP/kW), nominal current, protection range, dimensions, and weight.
Notes:
  • Ensure motor ampere absorption is within the control panel's operating current values.
  • Housing is made of metal for all sizes.
See more

Catalog excerpts

QS2_SERIES-1

QS2 SERIES CONTROL PANELS FOR 2 THREE PHASE STARTING MOTOR PUMPS STAR DELTA START WITH THERMAL PROTECTION Three phase electromechanical control panel for two motor pumps. TECHNICAL DATA • Power supply 3 ~ 50/60Hz 400V ± 10% • Main disconnecting switch with door lock • Transformer for power supply of auxiliary circuits • Contactor for each motor • Timer changeover Star Delta Star adjustable (0,1 ÷ 600s) for each motor • Exchanger • Protection degree IP 55 INPUTS • No. 6 extra low voltage inputs for: - Emergency stop SL / SP STOP (e.g, oat switches for protection from dry operation), active in both AUTOMATIC and MANUAL modes - Functional start and stop SL / SP 1 and 2 (e.g.: control oat switches) - Maximum level alarm SL / SP MAX - Engine block due to temperature sensor tripping PROTECTION AND ALARMS • Thermal relay sensitive to the lack of phase internally resettable for each motor • Motor protection fuses for each motor • Protection fuses on the auxiliary circuits • Alarm output 24Vac active in case of overload protection tripping or maximum level reached • Engine block due to temperature sensor tripping OPERATING CONDITIONS • Ambient temperature -5 / +40°C • Relative humidity 50% with maximum temperature 40°C NOTES • The power value is indicative in order for you to choose the correct control panel, make sure that the motor ampere absorption is included between the two operating current values of the control panel. The values for the current of use in the table are referred for each motor • Housing made of metal (M) for all sizes. ELECTRICAL SPECIFICATION Model Three-phase 400V +10-15% - 50Hz QTSE 20/12A-T-AR * QTSE 20/16A-T-AR * QTSE 20/23A-T-AR * QTSE 20/28A-T-AR * QTSE 20/36A -T-AR * QTSE 20/39A-T-AR * QTSE 20/50A-T-AR * QTSE 20/60A-T-AR * QTSE 20/78A-T-AR * QTSE 20/100A-T-AR * QTSE 20/130A-T-AR * QTSE 20/195A-T-AR * * Star/Delta start ** 58% of nominal current Your Life, our Quality. Worldwide. The contents of this publication must not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice. CONTROLS AND SIGNALS • Selector MANUAL-AUTOMATIC-OFF for each engine • No. 5 indicator lights for the signaling of: - Presence of power supply - Motor pump 1 or 2 running - Motor protection tripping 1 or 2

 Open the catalog to page 1

All EBARA PUMPS EUROPE catalogs and technical brochures

  1. DW - DW VOX

    15  Pages

  2. DS-DVS

    3  Pages

  3. DML-DMLV

    5  Pages

  4. D-TANK

    2  Pages

  5. CVM

    10  Pages

  6. CDX-CDXL

    3  Pages

  7. 4BHS

    5  Pages

  8. 2CDX Surface

    5  Pages

  9. Q series

    1  Page

  10. e- poWer

    1  Page

  11. DFFRP

    1  Page

  12. 1epbh

    2  Pages

  13. 2 G P 2 C D X

    3  Pages

  14. idroGo

    4  Pages

  15. SF6

    18  Pages

  16. PRA-PRN

    4  Pages

  17. Q_SERIES

    1  Page

  18. QA60C_SERIES

    1  Page

  19. QM1_SERIES

    1  Page

  20. QM2_SERIES

    1  Page

  21. QME1_SERIES

    1  Page

  22. QME2_SERIES

    1  Page

  23. QS1_SERIES

    1  Page

  24. QS3_SERIES

    1  Page

  25. QT1_SERIES

    1  Page

  26. QT2_SERIES

    1  Page

  27. QT3_SERIES

    1  Page

  28. RIGHT

    3  Pages

  29. SANIRELEV

    5  Pages

  30. SB3

    3  Pages

  31. SP SERIES

    1  Page

  32. SWS-SWT

    3  Pages

  33. WINNER 4N

    14  Pages

  34. pressCoMfort

    1  Page

  35. 1GP P

    1  Page

  36. 1GP H

    2  Pages

  37. 6BHE(L)

    26  Pages

  38. 3TP

    4  Pages

  39. DL-DL W/C

    22  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.