CEAG Products Main Catalogue Part 2: Chapter 3 Cable glands www.crouse-hinds.de EATON

Open the catalog to page 1
Cable glands - 3

Cable glands www.crouse-hinds.de EATON

Open the catalog to page 3
Cable glands - 4

Conform with latest standards Cable glands with metric screw-in threads are now standard and had replace the PG cable glands that were formally used. The CEAG plastic cable glands are in accordance with EN 60079-0: 2012 and can be used in Ex-e/Ex-i housings in hazardous areas of the Zones 1, 21,2 and 22. Optional and not used cable glands must be closed with certified blanking plugs. The blanking plugs allow for a flexible and cost effective utilization of the explosion-protected appliances. Changes and upgrades can be then easily carried out at a later date. The outstanding feature of...

Open the catalog to page 4
Cable glands - 5

Ex-cable plastic glands Technical data Marking accd. to 2014/34/EU EC-Type Examination Certificate lECEx Certificate of Conformity Marking accd. to IECEx Permissible ambient temperature M20 M25 - M63 Degree of protection accd. to EN 60529 Enclosure material Ex e cable glands © II 2 G Ex eb IIC Gb / © II 2 D Ex tb IIIC Db PTB 14 ATEX 1015 X IECEx PTB 14.0027X Ex eb IIC Gb / Ex eb IIC Gb -20 °C up to +70 °C (see ordering details) -40 °C up to +70 °C (see ordering details) -55 °C up to +70 °C (see ordering details) IP66 / IP68: 1 m water depth for 0.5 h Polyamide Ex-e screw plug Marking accd....

Open the catalog to page 5
Cable glands - 6

Ex-e/i cable plastic glands Ordering details Thread Cable 0 mm A/F L E seal. 1+2+3 seal. 1+2 seal. 1 mm mm mm Weight OU Order No. Order No. Ex-e cable gland with short thread accd. to EN 50262 -black M12 x 1.5 --- 5 - 7 15 19.3 8 0.003 20 GHG 960 1955 R0001 --- Ex-e cable gland with long thread -black M12 x 1.5 --- 5 - 7 15 19.3 12 0.003 20 GHG 960 1955 R0021 --- Ex-i cable gland with short thread -blue M12 x 1.5 --- 5 - 7 15 19.3 8 0.003 20 GHG 960 1955 R0101 --- Ex-i cable...

Open the catalog to page 6
Cable glands - 7

Ex-plastic screw plug / blanking plugs Ordering details Thread Cable0 mm A/F L E Weight OU Order No. Order No. Multiple cable glands -black M25 x 1.5 2 x 4.5 - 7 29 29.5 8 0.019 20 GHG 960 1955 R0054 --- Enlargement cable glands (reduced thread diameter) M16/M20 7 - 9 9.5 - 13 24 25.0 12 0.010 20 GHG 960 1956 R0002 Blanking plug for cable glands M12 M16 M20 M25 M32 M40 M50 M63 11 M63 with additional sealing 21 Cable dimensions and ambient temperatures see operating instruction Cable glands with PG-thread are...

Open the catalog to page 7
Cable glands - 8

Ex-plastic reducer rings Thread 1 Thread 2 A/F L E LI Weight OU Order No. Cable glands with PG-thread are available on request. The order No. will show 1 pcs. Please note that only order units (OU) can be ordered. Blanking plug

Open the catalog to page 8
Cable glands - 9

Ex-trumpet-shaped cable glands Marking accd. to 2014/34/EU EC-Type Examination Certificate lEC-Ex Certificate of Conformity Marking accd. to IECEx Permissible ambient temperature Degree of protection accd. to EN 60529 Enclosure material Ex-e Trumpet shaped cable gland © II 2 G Ex e II / © II 2 D Ex tD A21 IP66 PTB 00 ATEX 3121 IECEx BKI 08.0007 Ex e II / Ex tD A21 IP66 T85°C -40 °C up to +85 °C IP66 Polyamide Ordering details Thread A/C L E 0 Cable A/F Weight OU Order No. Ordering details Trumpet shaped cable gland M20 x 1.5 47 64 15 8 -...

Open the catalog to page 9
Cable glands - 10

Ex-drainage plug 3 Breathing & drainage plug Ex-e Breathing and drainage plug Marking accd. to 2014/34/EU D II 2 G Ex e II EC-Type Examination Certificate SIRA 99 ATEX 3050 U IECEx Certificate of Conformity IECEx SIR 08.0024X Marking accd. to IECEx Ex e IIC Gb / Ex eb IIC Gb / Ex tb IIIC Db IP66 Permissible ambient temperature -50 °C to +85 °C Degree of protection accd. to EN 60529 IP66 Enclosure material Polyamide Ordering details Type Thread A/F L E Weight OU Order No. The order No. will show 1 pcs. Please note that only order units (OU) can be...

Open the catalog to page 10
Cable glands - 11

Accessories for Ex-cable glands Accessories Type A/F Thickness Ordering details lock nut for cable glands M12 x 1.5 17 5 Ordering details gasket for glands M12 x 1.5 18 1.2 0.44 10 CAP 221 249 Size SW Ordering details special spanner for fastening of cable glands The order No. will show 1 pcs. Please note that only order units (OU) can be ordered.

Open the catalog to page 11
Cable glands - 12

Designed according to the latest standards For introducing cables or leads into metal housings, explosion-protected housing or, if reinforced cables have to be introduced, metal cable glands are used. Metal glands are designed for use in areas of Zone 1, 2, 21 and Zone 22 at no risk of explosion and for cables with and without reinforcement. Depending on the area of use, these cable entries are certified with the type of protection Ex-d or Ex-e pursuant to the latest standard EN 60079-1 or EN 60079-7 For all applications For special applications, the cable glands are available...

Open the catalog to page 12
Cable glands - 13

Technical data Ex e cable glands metal ADE ... EC-Type Examination Certificate IECEx Certificate of Conformity Marking accd. to IECEx Permissible ambient temperature Degree of protection accd. to EN 60529 Enclosure material Nickel-plated brass (CuZn gal. Ni), stainless steel, bronze, natural brass option www.crouse-hinds.de EATON

Open the catalog to page 13
Cable glands - 14

Order No. stainless steel Ordering details iso Type Cable 0 ABEL outside mm mm mm mm mm Cable gland type ADE 1F2 for unarmoured cable with ISO thread M12 x 1.5 4 4.5 - 8 17 17 15 25 Please use sealing washers (see page 2.3.28). For cable gland kits with washer and lock nut please add ”K1” et the end of the order No. Example: CAP 806 404 V1 K1 contains a ADE 1F2 M12 x 1.5 type 4 + 1 x MsNi lock nut M12 + 1 x green fibre gasket for M12 Dimension drawing

Open the catalog to page 14
Cable glands - 15

Ordering details NPT Type Cable 0 ABEL Order No. Order No. outside mm mm mm mm CuZn gal. Ni stainless steel mm Cable gland type ADE 1F2 for unarmoured cable with NPT thread 1/2“ 3 2.75 - 5.5 24 15 22.2 24 CAP 808 664 V1 CAP 808 669 V1 Please use sealing washers (see page 2.3.28). For cable gland kits with washer and lock nut please add “K1” et the end of the order No. Example: CAP 808 604 V1 K1 contains a ADE 1F2 1/2'' type 6 + 1 x MsNi lock nut 1/2'' + 1 x green fibre gasket for 1/2'' Dimension drawing