Catalog excerpts
Sectionalizing Cabinets Catalog Data CA901002EN Effective March 2024 Supersedes October 2022 COOPER POWERSERIES 600 A, 15, 25, and 28 kV class Cleer SecTER cabinet General Eaton's Cooper Power™ series versatile single-and three-phase 600 A Cleer™ SecTER™ cabinets are designed as cable sectionalizing centers. They can be used wherever underground cable must be sectionalized or connected. Functions include sectionalizing cable, switching cable, isolating cable and feeder taps. Each Cleer SecTER cabinet comes complete with one of Eaton's Cooper Power series exclusive 600 A, 15, 25, or 28 kV Class Cleer loadbreak connectors installed per phase. The aesthetic low profile design provides unobtrusive installations for sectionalizing, tapping or terminating underground cable. The top hinged diagonally cut removable cover and cabinet are designed for easy one man opening. Recessed door and low sill provides improved access to interior terminations. A door stop prevents the door from accidentally closing. TGIC powder coating exceeds ANSI® coating requirements. Standard Munsell Green 7GY3.29/1.5 twelve gauge mild steel designs with standard stainless steel hardware are available. For highly corrosive environments, stainless steel or aluminum are also available. Continuous seam welding ensures a sturdy smooth cabinet. A welded-on ground nut is also provided for each phase. Optional features • Cleer 600 A loadbreak connectors installed • Available in ANSI® 70 gray • 3/8-inch copper ground rod installed • Mild steel base extensions • Fiberglass ground sleeves Powering Business Worldwide
Open the catalog to page 1Catalog Data CA901002EN Effective March 2024 600 A, 15, 25, and 28 kV class Cleer SecTER cabinet 600 A, 15, 25, and 28 kV Cleer loadbreak connector system The Cleer loadbreak connector system is a 600 A loadbreak device available in ratings for operation on 15, 25, or 28 kV class systems. It is used to provide a visible break and visible ground on 600 A network and distribution systems without having to remove 600 A terminations and move heavy cable. The Cleer loadbreak connector system Is fully shielded, submersible and meets the applicable requirements of IEEE Std 386™-2006—“Separable...
Open the catalog to page 2600 A, 15, 25, and 28 kV class Cleer SecTER cabinet Catalog Data CA901002EN Effective March 2024 15 kV ratings, characteristics Production tests Tests are conducted in accordance with IEEE Std 386-2006. • AC 60 Hz 1 minute withstand • 34 kV • Minimum partial discharge extinction voltage • 11 kV (3-pc sensitivity) Tests are conducted in accordance with Eaton requirements. • Physical inspection • Periodic dissection • Periodic fluoroscopic analysis Table 1. Current ratings and characteristics 600 A loadbreak interface Continuous current Loadbreak switching Fault closure 4-hour overload...
Open the catalog to page 3Effective March 2024 Cleer SecTER cabinet 25 kV ratings, characteristics Production tests Tests are conducted in accordance with IEEE Std 386-2006. • AC 60 Hz 1 minute withstand • 40 kV • Minimum partial discharge extinction voltage • 19 kV (3-pc sensitivity) Tests are conducted in accordance with Eaton requirements. • Physical inspection • Periodic dissection • Periodic fluoroscopic analysis Table 3. Current ratings and characteristics Description Amperes 600 A loadbreak interface Continuous current Loadbreak switching Fault closure 4-hour overload current Short-time current 600 A rms Five...
Open the catalog to page 4600 A, 15, 25, and 28 kV class Cleer SecTER cabinet Catalog Data CA901002EN Effective March 2024 28 kV ratings, characteristics Production tests Tests are conducted in accordance with IEEE Std 386-2006. • AC 60 Hz 1 minute withstand • 45 kV • Minimum partial discharge extinction voltage • 21.1 kV (3-pc sensitivity) Tests are conducted in accordance with Eaton requirements. • Physical inspection • Periodic dissection • Periodic fluoroscopic analysis Table 5. Current ratings and characteristics Description Amperes 600 A loadbreak interface Continuous current Loadbreak switching Fault closure...
Open the catalog to page 5600 A, 15, 25, and 28 kV class Cleer SecTER cabinet Ordering information 1. Select size of SecTER cabinet from Table 7 based on junctions required. Refer to figures referenced to confirm SecTER cabinet configuration meets requirements. 2. Build SecTER catalog number from Table 8 based on size selected from Table 7 and options required. 3. Fiberglass ground sleeves are ordered separately. If ground sleeve is required, select catalog number from Table 11 on page 11. 4. Mild steel base extensions are ordered separately. If base extension is required, select catalog number from Table 12 on page...
Open the catalog to page 6600 A, 15, 25, and 28 kV class Cleer SecTER cabinet Note: Dimensions are for reference only. Figure 2. SEC13023F0000M0G SecTER cabinet shown 66.00 Note: Dimensions are for reference only. Figure 3. SEC36623FCL15M0G SecTER cabinet shown with 15 kV, 600 A Cleer loadbreak installed
Open the catalog to page 7Effective March 2024 Cleer SecTER cabinet Note: Dimensions are for reference only. Figure 4. SEC38423F0000M0G SecTER cabinet shown Note: Dimensions are for reference only.
Open the catalog to page 8600 A, 15, 25, and 28 kV class Cleer SecTER cabinet Catalog Data CA901002EN Effective March 2024 Cleer multi-point junction assemblies Eaton designs Cooper Power series Cleer junction assemblies for vault or apparatus applications, which can be used for looping, tapping, switching and sectionalizing. They are fully shielded, submersible and are designed and manufactured in accordance with the IEEE Std 386-2016—“Separable Insulated Connector Systems. ” These junctions provide assemblies of multiple 2 to 6 mixed interface, 15 kV or 25 kV junctions linked by the Cleer C-connector to create...
Open the catalog to page 9600 A, 15, 25, and 28 kV class Cleer SecTER cabinet Ordering information 1. Select size of SecTER cabinet from Table 9 based on junctions required. Refer to figures referenced to confirm SecTER cabinet configuration meets requirements. 4. Mild steel base extensions are ordered separately. If base extension is required, select catalog number from Table 12 on page 12. 2. Build SecTER catalog number from Table 10 based on size selected from Table 1 and options required. Note: Width and depth dimensions of ground sleeves or base extensions must be matched to width of SecTER cabinet selected. 3....
Open the catalog to page 10All Eaton Count Control Products catalogs and technical brochures
-
COOPER POWER SERIES
20 Pages
-
Electrical enclosures
544 Pages
-
Climate Control Products
34 Pages
-
Eaton pilot devices
2 Pages
-
C22 Pilot Devices
4 Pages
-
Marina Power & RV Park Equipment
48 Pages
-
NEMA Contactors and Starters
154 Pages
-
IEC Contactors and Starters
259 Pages
-
Control Relays and Timers
204 Pages
-
Motor Protection and Monitoring
144 Pages
-
PowerXL DE1 Catalog
6 Pages
-
Expulsion Fuses
72 Pages
-
Pushbuttons and Indicating Lights
361 Pages
-
Power Pedestals
90 Pages
-
Loadcenters and Circuit Breakers
100 Pages
-
Series GJ
8 Pages
-
Series CD-CE-CF
10 Pages
-
Series GH
8 Pages
-
SAF Drives
1 Pages
-
SmartWire-DT
2 Pages
-
Cutler-Hammer
12 Pages
-
BladeUPS (12-60 kW)
12 Pages
-
9PX (5-11 kVA)
4 Pages
-
5S (500-1500 VA)
2 Pages
-
5P Tower (750-3000 VA)
2 Pages
-
5P Rackmount (500-3000 VA)
2 Pages
-
3S (350-750 VA)
2 Pages
-
Alternate Enclosures
4 Pages
-
Manual Motor Control
10 Pages
-
Multi-Pak Group Control
13 Pages
-
HVAC Control
10 Pages
-
Pump Panels
29 Pages
-
Reduced Voltage Starters
83 Pages
-
Lighting Contactors
16 Pages
-
NEMA Contactors and Starters
80 Pages
-
Volume 04 - Circuit Protection
684 Pages
-
Molded Case Circuit Breakers
432 Pages
-
Metering Products
151 Pages
-
Solutions Energy Savings
8 Pages
-
Counters, Timers and Tachometers
145 Pages
Archived catalogs
-
IEC Contactors and Starters
251 Pages