Load Bank Sample Software Report (DataView) - 1

Report Printing Time:2012-11-02 10:24:27 Company Name: Eagle Eye Power Solutions Testing Location: Lab Testing Target: Standard String S/N 0001 Testing Type Check Test Discharge String Type 48V Cell Model 2V Cells No. 24cells Set Discharge Current 99.9A Testing Time 7/23/2011 2:28:02 PM Actual Discharge Time 14:23:18 Cell Rated Capacity Ah Discharge Capacity 1436.9Ah Battery Manufacturer Company ABC Year Limit For Operation Department: Electrical Set Discharge Capacity 3600Ah Testing Personnel Electrical Reporter: Ryan Ending Cause Reach Cell Ending Volt Set Discharge Time 37:00:00 Set Total Ending Volt 42V Set Single Cell Ending volt: 1.75V Rated capacity of this cell stringAh Discharge Capacity1436.9Ah Discharge Rated Capacity 508834.1%

Open the catalog to page 1
Load Bank Sample Software Report (DataView) - 2

Report Printing Time:2012-11-02 10:24:27 First 10 Cells With Lowest Volt 5#:1.748V 12#:1.926V 16#:1.927V 11#:1.961V 20#:1.964V 2#:1.966V 22#:1.973V 4#:1.980V 3#:1.984V 23#:1.984V Suggestion: Above cells need longer time for checking cells condition, and 5# cell No. Through 14:23:18 Discharge cells discharge to reduce to below1.8V. You are suggested to activate these cells and have a evaluation for capacity. If they do not work, please change them.

Open the catalog to page 2

All Eagle Eye Power Solutions catalogs and technical brochures

  1. SC-1000

    2 Pages

  2. SC-1500

    2 Pages

  3. SC-2000

    2 Pages

  4. RM-48-2K

    2 Pages

  5. RM-48-3K

    2 Pages

  6. RM-48-KA

    1 Pages

  7. MIS-1000

    3 Pages

  8. ENC-2000

    1 Pages

  9. BTM-Series

    1 Pages

  10. BQMS

    2 Pages

Archived catalogs

  1. HGD-3000

    1 Pages

  2. DC Load Bank

    3 Pages

  3. LB-1000

    1 Pages

  4. SCR-SCRF

    1 Pages

  5. SG-100M

    1 Pages

  6. SG-1000

    1 Pages

  7. SG-Ultra Max

    1 Pages