Product catalog summary
Company Information: Eagle Eye Power Solutions conducted a battery discharge test at their lab. The test was a standard check test discharge on a 48V string with 24 cells, each 2V, manufactured by Company ABC.
Test Specifications: The set discharge current was 99.9A, and the test began on 7/23/2011 at 2:28:02 PM. The actual discharge time recorded was 14:23:18. The set discharge capacity was 3600Ah, while the actual discharge capacity achieved was 1436.9Ah.
Test Results: The test ended when the cell voltage reached the set ending voltage of 1.75V per cell, with a total ending voltage of 42V. The discharge rated capacity was noted as 508834.1%.
Cell Performance: The first 10 cells with the lowest voltage were identified, with cell 5# having the lowest at 1.748V. It is suggested that these cells need further evaluation and possible activation or replacement if they do not improve.
Discharge Process Data: The report includes detailed voltage readings for each cell at various time intervals during the discharge process. The total voltage decreased from 49.53V to 47.04V over the course of the test.
Recommendations: Cells with voltages dropping below 1.8V, particularly cell 5#, should be activated and evaluated for capacity. If they do not perform adequately, replacement is recommended.
See more

Catalog excerpts

Load Bank Sample Software Report (DataView)-1

Report Printing Time:2012-11-02 10:24:27 Company Name: Eagle Eye Power Solutions Testing Location: Lab Testing Target: Standard String S/N 0001 Testing Type Check Test Discharge String Type 48V Cell Model 2V Cells No. 24cells Set Discharge Current 99.9A Testing Time 7/23/2011 2:28:02 PM Actual Discharge Time 14:23:18 Cell Rated Capacity Ah Discharge Capacity 1436.9Ah Battery Manufacturer Company ABC Year Limit For Operation Department: Electrical Set Discharge Capacity 3600Ah Testing Personnel Electrical Reporter: Ryan Ending Cause Reach Cell Ending Volt Set Discharge Time 37:00:00 Set Total Ending Volt 42V Set Single Cell Ending volt: 1.75V Rated capacity of this cell stringAh Discharge Capacity1436.9Ah Discharge Rated Capacity 508834.1%

 Open the catalog to page 1
Load Bank Sample Software Report (DataView)-2

Report Printing Time:2012-11-02 10:24:27 First 10 Cells With Lowest Volt 5#:1.748V 12#:1.926V 16#:1.927V 11#:1.961V 20#:1.964V 2#:1.966V 22#:1.973V 4#:1.980V 3#:1.984V 23#:1.984V Suggestion: Above cells need longer time for checking cells condition, and 5# cell No. Through 14:23:18 Discharge cells discharge to reduce to below1.8V. You are suggested to activate these cells and have a evaluation for capacity. If they do not work, please change them.

 Open the catalog to page 2

All Eagle Eye Power Solutions catalogs and technical brochures

  1. SC-1000

    2  Pages

  2. SC-1500

    2  Pages

  3. SC-2000

    2  Pages

  4. RM-48-2K

    2  Pages

  5. RM-48-3K

    2  Pages

  6. RM-48-KA

    1  Page

  7. MIS-1000

    3  Pages

  8. ENC-2000

    1  Page

  9. BTM-Series

    1  Page

  10. BQMS

    2  Pages

Archived catalogs

  1. SG-Ultra Max

    1  Page

  2. SG-1000

    1  Page

  3. SG-100M

    1  Page

  4. SCR-SCRF

    1  Page

  5. LB-1000

    1  Page

  6. DC Load Bank

    3  Pages

  7. HGD-3000

    1  Page

  8. DC SLB-Series

    3  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.