1-34-020 / D2x: Aluminium hazardous location The D2xC1X05 features a high output, 116dB(A) alarm horn sounder combined with a 5 Joule Xenon strobe warning light / beacon. Globally approved, the robust Type 4/4X, IP66 enclosure ensures suitability for all haz loc fire alarm and general signalling applications. The corrosion proof, marine grade aluminium die cast enclosure is chromated and powder coated providing resilience in the harshest of hazardous location environments. One device, globally certified: ATEX, IECExZone 2 & 22; NEC/CEC CI D2 and CII D2; NEC CI Zone 2 and Zone 22; CEC Zone 2 & 22 and CII D2. UL & cUL approved 24Vdc version for fire alarm use. • 5 Joule Xenon beacon with 116dB(A) alarm horn • 64 alarm tones, 4 remotely selectable alarm stages/channels • Field replaceable lens colour filters • Dual cable entries • Supplied with haz loc rated stopping plugs/adaptors • IECEx cert: IECEx ULD 14.0004X • ATEX cert: DEM KO 14 ATEX 4786493904X Class I Div 2 ABCD T2B Ta -40°C to +70°C Class I Div 2 ABCD T2C Ta -40°C to +55°C Class I Div 2 ABCD T2D Ta -40°C to +40°C Class II Div 2 FG T5 Ta -40°C to +50°C Class III Div 1&2 Ta -40°C to +50°C Class I Zone 2 AEx ec IIC T2 Gc Ta -40°C to +50°C Zone 22 AEx tc IIIC T120°C Dc Ta -40°C to +50°C Class I Zone 2 Ex ec IIC T2B Gc X Ta -40°C to +50°C Class I Zone 2 Ex ec IIC T2C Gc X Ta -40°C to +45°C Zone 22 Ex tc IIIC T120°C Dc Ta -40°C to +50°C • IECEx & ATEX: See product manual for full voltage specific coding. warning signals
Open the catalog to page 1Part Codes Alarm Horn Sounder: Part Code: Identifier: Description: Product type: D2xC1X05 Haz Loc alarm horn sounder & Xenon strobe warning light / beacon Cable Entry Type: A [e] B Stopping plug/ N adaptor material: S [m]_ Nominal output: 112dB(A) @ 1m +/- 3dB - Tone 2 [103dB(A) @ 10ft/3m] No. of tones: 64 (UKOOA / PFEER compliant) Volume control: Adjustable -12dB(A) [Tone 2] Stage switching: DC units - Positive or Negative line. AC units - common supply line Peak Candela: 500,000 cd - calculated from energy (J) Effective Intensity 250 cd - calculated from energy (J) cd: Peak Candela: 33,410...
Open the catalog to page 2Current Consumption Product Version: Nominal Voltage: Voltage Range: Current Consumption: Alarm Horn Sounder: 313mA [at nominal voltage] 181mA [at nominal voltage] 89mA 52mA Xenon Strobe Beacon: DC024 24V dc 275mA [at nominal voltage] 145mA [at nominal voltage] 80mA 30mA Combined Horn & Strobe: DC024 24V dc 513mA [at nominal voltage] 311mA [at nominal voltage] 174mA 63mA
Open the catalog to page 3Tone table S 1 Description T 1 1000 Continuous - PFEER Toxic Gas T 2 1200/500 @ 1Hz Sweeping - DIN / PFEER P.T.A.P. T 14 1000/2000 @ 1Hz - Singapore T 15 300 Continuous T 16 440 Continuous T 17 470 Continuous T 18 500 Continuous - IMO code 2 (Low) T 19 554 Continuous T 20 660 Continuous T 21 800 Continuous - IMO code 2 (High) T 22 1200 Continuous T 23 2000 Continuous T 24 2400 Continuous No liability is accepted tor any consequence of the use of this document The technical specification of this unit is subject to change without notice due to our policy of continual product development All dimensions...
Open the catalog to page 42 Pages
2 Pages
2 Pages
1 Page
1 Page
1 Page
1 Page
48 Pages
2 Pages
20 Pages
43 Pages