video corpo

127

127

127

Product catalog summary
Description: The document details the specifications and features of the single pole thermal overcurrent circuit breaker model 127. It includes a push-to-reset, tease-free, trip-free, snap action mechanism. The breaker is available for plug-in, integral, track, or snap-in panel mounting. An optional -KF housing is available for high humidity conditions. It complies with the CBE standard EN 60934.
Typical Applications: The circuit breaker is suitable for use with motors, transformers, solenoids, battery chargers, and extra low voltage systems.
Ordering Information: The document provides a detailed guide on how to construct the part number based on various options such as mounting type, terminal design, manual release, special housing, and current ratings.
Approvals: The circuit breaker is approved under several standards including VDE (IEC/EN 60934), UL (UL 1077), CSA (C22.2 No 235), and CQC (GB 17701) for both AC and DC voltages.
Technical Data: Key specifications include a voltage rating of AC 250 V and DC 28 V (UL: DC 50 V), current ratings from 0.05 to 25 A, and a typical life of 5,000 operations at 2 x IN. The ambient temperature range is -20 to +60 °C. The breaker has a dielectric strength of AC 3,000 V and an insulation resistance greater than 100 MΩ. It features an interrupting capacity of up to 300 A depending on the current rating.
Environmental and Mechanical Specifications: The breaker is rated IP40 for the operating area and IP00 for the terminal area. It withstands vibration up to 8 g and shock up to 25 g. It is tested for corrosion resistance and humidity endurance.
Accessories: The document lists connector bus links and mounting sockets compatible with the circuit breaker, specifying maximum load capacities and wire cross-sectional areas.
Diagrams and Dimensions: Installation drawings and internal connection diagrams are provided, with dimensions primarily in millimeters. The document emphasizes that metric dimensions take precedence.
See more

Catalog excerpts

127-1

Thermal Overcurrent Circuit Breaker 127-... Description Single pole thermal circuit breaker with push-to-reset, tease-free, trip-free, snap action mechanism (R-type TO CBE to EN 60934; M-type when fitted with optional manual release feature). Available in versions for plug-in or integral mounting, track mounting, or with a frame for snap-in panel mounting. The optional -KF housing is particularly suited to high humidity and other damp conditions. Approved to CBE standard EN 60934 (IEC 60934). Typical applications Motors, transformers, solenoids, battery chargers, extra low voltage systems. Ordering information Technical data Type No. 127 Mounting options leave blank for integral/plug-in option T12 track mounting with screw terminals M4 Terminal design (for use with and without flange -F) P10 blade terminals A6.3-0.8 (QC .250) Manual release H manual release facility Special housing KF for tropical and high humidity conditions Current ratings 0.05...25 A 127 - F - P10 - H - .. - 10 A ordering example The exact part number required can be built up from the table of choices shown above. Ordering references for optional features should be omitted if not required. Standard current ratings and typical internal resistance values Current rating (A) For further details please see chapter: Technical Information Voltage rating AC 250 V; DC 28 V (UL: AC 250 V; DC 50 V) Current ratings 0.05...25 A Typical life 0.05...16 A 5,000 operations at 2 x IN, inductive 17...25 A 5,000 operations at 2 x IN, resistive Ambient temperature -20...+60 °C (-4...+140 °F) Insulation co-ordination rated impulse pollution (IEC 60664 and 60664 A) withstand voltage degree 2.5 kV 2 reinforced insulation in operating area Dielectric strength (IEC 60664 and 60664A) test voltage operating area AC 3,000 V Insulation resistance > 100 MΩ (DC 500 V) Interrupting capacity Icn 0.05...2.5 A 8 x IN 3...5 A 20 x IN 6...12 A 200 A 13...25 A 300 A Interrupting capacity IN UN (UL 1077) 0.05...20 A AC 250 V 2,000 A 0.05...25 A DC 50 V 2,500 A Degree of protection operating area IP40 (IEC 60529/DIN 40050) terminal area IP00 Vibration 8 g (57-500 Hz) ± 0.61 mm (10-57 Hz) to IEC 60068-2-6, test Fc, 10 frequency cycles/axis Shock 5 g (11 ms), to IEC 60068-2-27, test Ea 2 Corrosion 96 hours at 5 % salt mist, to IEC 60068-2-11, test Ka Humidity 240 hours at 95 % RH to IEC 60068-2-78, test Cab Mass 127-P10-..: approx. 20 g 127-T..-: approx. 35 g Rated voltage Current ratings

 Open the catalog to page 1
127-2

Thermal Overcurrent Circuit Breaker 127-... Dimensions Internal connection diagram Typical time/current characteristics at +23 °C/+73.4 °F 9.4 .370 11.5 .453 blade terminal DIN 46244-A6.3-0.8 (QC .250) Trip time in seconds The time/current characteristic curve depends on the ambient temperature prevailing. In order to eliminate nuisance tripping, please multiply the circuit breaker current ratings by the derating factor shown below. See also section Technical information. Derating factor operating area Installation drawings mounting area This is a metric design and millimeter dimensions take...

 Open the catalog to page 2
127-3

Thermal Overcurrent Circuit Breaker 127-... Accessories Mounting sockets 10F-P10 (up to 16 A max. load) 7 .276 wire corss sectional areas 2 x max. 2.5 mm2 (AWG14) stranded 2 x max. 4 mm2 (AWG12) solid Accessories for sockets (up to 20 A max. load) 2-way bus bar Y 301 166 02 4-way bus bar Y 301 166 01 Connector bus links -K10 X 210 589 01/2.5 mm2 (AWG 14), black (up to 20 A max. load) X 210 589 02/1.5 mm2 (AWG 16), brown (up to 13 A max. load) 50 pin lugs to DIN 46230 tinned copper Connector bus links -P10 X 210 588 01/1.5 mm2 (AWG 16), brown (up to 13 A max. load) X 210 588 02/2.5 mm2 (AWG 14),...

 Open the catalog to page 3