D-ZL

D-ZL

Product catalog summary
Overview: The document provides technical specifications and applications for DURAG GmbH's ignition lances, designed for use with high energy ignition devices in industrial burners. These lances are suitable for igniting gas or liquid fuels, even in hazardous areas.
Features:
  • Customizable installation with various component combinations.
  • Ignition tips are replaceable and available in normal or high temperature-proof models.
  • Special ignition tips for high-pressure or heavy fuel oil (HFO) ignition.
  • Lance lengths up to 15 meters, with high voltage cables extending up to 50 meters without performance loss.
  • Compatible with D-VE 500 retraction units.
Applications: Suitable for use in chemical industries, refineries, cement plants, waste incinerators, power plants, steam generators, and Claus plants.
Certifications: The ignition lances are certified under ATEX/IECEx and EAC standards.
Technical Specifications:
  • Ignition Lance Length: Minimum 0.7 m, maximum 15 m (grid dimension: 100 mm).
  • Weight: 1.6 kg/m at a diameter of 22 mm.
  • Operational Life of Ignition Tip: 10⁶ sparks.
  • Max Temperature: Normal temperature up to 600 °C, briefly 800 °C; high temperature up to 1000 °C.
  • High Voltage Cable Length: Minimum 3 m, maximum 50 m (grid dimension: 5 m).
  • Weight of High Voltage Cable: 0.5 kg + 0.5 kg/m.
  • Ex Protection: II 2G Ex d IIC T6, T5, T4 Gb; II 2D Ex tb IIIC T80, 95, 130 °C Db IP65.
  • Permissible Ambient Temperature: -40 °C to +80 °C.
See more

Catalog excerpts

D-ZL-1

DURAG Ignition lances For the connection to the high energy ignition devices of the D-HG 400 and D-HG 500 series in order to ignite gas or liquid fuels in industrial burners of any capacity -also in hazardous areas Features • Flexible customization for specific installation conditions by various combination of components • Easily replaceable ignition tips - available as normal or high temperature-proof models • Special igntion tips for the ignition of HFO or at high pressure • Ignition lance lenghts up to 15 meter • Up to 50 m distance can be overcome by using robust high voltage cables - without any loss of performance! • Compatible with retractions units D-VE 500 Applications • Chemical industry • Refineries • Cement plants • Waste incinerators • Power plants • Steam generators • Claus plants Certifications • ATEX/lECEx • EAC Length ignition lance LZL D-ZL 521- seperated ignition lance for D-HG ...-60/ -61/ -62 ©DURAG GROUP 08/2016 • Subject to change without notice DURAG GmbH Kollaustrasse 105 • 22453 Hamburg • Germany [«— LHV—►! Lanz / Length ignition lance LZL

 Open the catalog to page 1

All DURAG GROUP catalogs and technical brochures

  1. D-LX 201

    6  Pages

  2. D-LX 110

    6  Pages

  3. D-EMS 2020

    6  Pages

  4. D-LX 200

    4  Pages

  5. D-LX 201/721

    6  Pages

  6. D-LX 100

    1  Page

  7. D-HG 500

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.