RTD Temperature Monitor DG 3602 / DG 3632-1

RTD Temperature Monitor DG 3602 / DG 3632Limit Monitoring withPt, Ni, KTY and NTC Sensors The Temperature Monitors DG 3602 and DG 3632 are used for temperature control with RTD sensors in 2-wire connection. The sensor signal will be compared with the set limit values. In case of overshooting or undershooting, the output relays react according to the set configuration. Two relay outputs (synchronous switching) can be configured as MIN or MAX alarm in open-circuit or closed-circuit operation with the analog control electronics. All setting elements are located behind the openable front cover and can also be operated when the unit is mounted. The switching points and the switching hysteresis can be adjusted with potentiometers. The monitoring states are indicated by yellow LEDs. The relay changeover contacts switch high power loads up to 6 A. Input, power supply and the outputs are safely galvanically isolated from each other. The Protective Separation and the 24 V DC power supply make the DG 3602 and DG 3632 universally applicable for all measurement and industrial applications, as well as for building automation. Measuring range and operating mode switchable, switch point and hysteresis adjustable with potentiometer Easy monitoring and switching point adjustment 2 fully isolated changeover contacts Protection against erroneous measurements due to parasitic voltages or ground loops Protects service personnel and downstream devices against impermissibly high voltage No microprocessor, no integrated software 12.5 mm slim housing for a simple and space saving DIN rail mounting Defects occurring within 5 years from delivery date shall be remedied free of charge at our plant DRAGO Signal Converter - Isolation Amplifiers - www.drago-automation.de

 Open the catalog to page 1
RTD Temperature Monitor DG 3602 / DG 3632-2

Input ranges (switchable) Monitoring sensors Sensor current Sensor connection Switch point setting Hysteresis setting Contact type Switching capability AC max. Switching capability DC max. Recommended minimum load Status indication Response time General Data Switch error Temperature coefficient1 Test voltage Working voltage (Basic Insulation)2) Protection against electrical shock2) Power supply Ambient temperature Ni 100, Ni 120, Ni500, Ni 1000, Further high impedance RTD 2-wire sensor connection, manual compensation of line resistances required 0 to 110 % with 12-turn potentiometer 0 to 6 %...

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.