Dowei Electric Earthing Transformer DKS

Dowei Electric Earthing Transformer DKS

Dowei Electric Earthing Transformer DKS

Product catalog summary
General Description:
  • The document outlines specifications for earthing transformers, specifically Zig Zag transformers, which are used to create a neutral point in a network and limit line-to-earth current during system earth faults.
  • Compliance with standards such as IEC 60076-6, ANSI/IEEE Std C57.12, and NEMA is highlighted, along with certifications like ISO 9001, KEMA, CESI, CE, TUV, UL, and ASTA.
  • The transformers are designed for seismic conditions and high altitudes, with structural design adhering to ASTM A325, ANSI/AISC 360, and AWS D1.1.
  • They use mineral or vegetable oil (FR3) and are free of PCBs.
Typical Specifications:
  • 35kV Earthing Transformer:
    • Rated Voltage: 30-36 kV with a tapping range of ±5% or ±2x2.5%.
    • Vector Group: ZN / Zig-Zag.
    • Zero Phase Impedance ranges from 22.9 to 95.3 Ω.
    • Rated Short-time Neutral Current varies from 200 to 1100 A with durations of 10 to 30 seconds.
  • 10kV Earthing Transformer:
    • Rated Voltage: 6-11 kV with a tapping range of ±5% or ±2x2.5%.
    • Vector Group: ZN / Zig-Zag.
    • Zero Phase Impedance ranges from 10 to 190.5 Ω.
    • Rated Short-time Neutral Current varies from 100 to 1050 A with durations of 10 to 30 seconds.
See more

Catalog excerpts

Dowei Electric Earthing Transformer DKS-1

Power Transmission & Distribution One stop equipments solution Earthing Transformer

 Open the catalog to page 1
Dowei Electric Earthing Transformer DKS-2

General Description: • IEC 60076-6, ANSI/IEEE Std C57.12, NEMA • ISO 9001, KEMA, CESI, CE, TUV, UL, ASTA • Mineral Oil / Vegetable Oil (FR3), Free PCB • Seismic design, ETGI-1.020, IEEE Std 693, NCh2369 • Structural design, ASTM A325, ANSI/AISC 360, AWS D1.1 • High altitude correction per IEC 60076 & IEEE C57.12, ~ 5000m • Earthing transformer creates a neutral point for a network • Limit the line to earth current under system earth fault condition • Z connection provides linear and specified zero sequence impedance Rated Voltage (kV) Tapping range Vector Group Zero Phase Rated Short-time Duration...

 Open the catalog to page 2