General Description:
The document outlines the specifications and standards for Dead Tank Circuit Breakers manufactured by Ningbo Dowei Electric Co., Ltd. These circuit breakers comply with international standards such as IEC 62271, ANSI C37 series, and are certified by ISO 9001, KEMA, CESI, CE, TUV, UL, and ASTA. They are designed to withstand seismic activities and adhere to structural standards like ASTM A325 and ANSI/AISC 360. The breakers are suitable for high altitudes up to 5000 meters and offer reliable and flexible solutions for high current switching.
Typical Specification: The document provides detailed specifications for SF6 Gas Dead Tank Circuit Breakers ranging from 40.5kV to 363kV. Key parameters include:
- Rated Voltage: 40.5 to 363 kV
- Rated Frequency: 50/60 Hz
- Rated Continuous Current: 3150 to 4000 A
- Rated Short Circuit Breaking Current: 31.5/40 to 50 kA
- Rated Short Circuit Making Current: 80/100 to 125 kA
- Rated Peak Withstand Current: 80/100 to 125 kA
- Short Line Fault Breaking Current: 36/30 to 45/37.5 kA
- Out of Phase Breaking Current: 10 to 12.5 kA
- Rated Power-Frequency Withstand Voltage: 95 to 510 kV
- Lightning Impulse Withstand (BIL): 185 to 1175 kV
- Type of Mechanism: Spring or Hydraulic
- Mechanical Endurance: ≥5000 operations
- Rated Operating Sequence: O-0.3s-CO-180s-CO
- Close Time: ≤100 ms
- Open Time: ≤30 ms
- Breaking Time: ≤60 ms
- Three Phase Operation: 3p or 1p
- Rated SF6 Gas Pressure: 0.5 to 0.6 Mpa
- Weight: 1550 to 100000 kg
See more