Overview: The Insulation Monitor LK 5894 from the VARIMETER IMD family by DOLD is designed for monitoring insulation in non-earthed AC, AC/DC, and DC power supplies (IT systems). It enhances plant availability and supports preventive maintenance by detecting faults during operation, thus preventing costly standstills.
Specifications: The LK 5894 can handle system leakage capacitances up to 1000 µF and is applicable in non-earthed DC/AC and mixed networks with nominal voltages from 0 V to 690 V. It supports maximum voltages up to DC 1000 V and AC 760 V without additional devices. The device features latching rotary switches for easy adjustment, measuring circuit monitoring for broken wire detection, and an LED chain indicating current insulation resistance.
Advantages: Key benefits include preventive fire and plant protection, early fault detection, no need for additional ballast, fast error localization, and reliable monitoring even in voltage-free networks. The device is suitable for universal application across various network types.
Technical Features: The LK 5894 complies with IEC/EN 61557-8 standards, detects symmetrical and asymmetrical insulation faults, and includes two changeover contacts. It offers adjustable prewarning and alarm thresholds, selectable open or closed circuit principles for output relay, and a simple setting structure using a screwdriver. The device also supports automated and manual self-tests.
Applications: The insulation monitor is applicable in DC/AC and mixed IT networks, UPS systems, networks with frequency converters, battery networks, photovoltaic systems, and hybrid or battery-operated cars.
Additional Information: For systems with leakage capacities up to 3000 µF or requiring a second measuring circle or analogue output, further customization may be necessary.
See more

Catalog excerpts

Flyer insulation monitor LK 5894-1

VARIMETER IMD Insulation Monitor LK 5894 With the new Insulation Monitor LK 5894 from the VARIMETER IMD family, DOLD offers a convincing solution for insulation monitoring of non-earthed AC, AC/DC, and DC power supplies (IT systems). The LK 5894 increases the availability of plants and is used for preventive maintenance and repair. Faults are detected even during operation and costly plant standstills are prevented. The insulation monitor was specially designed for use in modern power supplies that often include rectifiers, converters, thyristor controllers or directly connected DC components. EMC interference suppression measures with its leakage capacitances against earth play an important role in this matter. DOLD's insulation monitor meets the criteria. Besides a faster fault localisation by selective earth fault detection and optimised measuring times, the insulation monitor can deal with system leakage capacitances of up to 1000 µF. It is also universally applicable in non-earthed DC/AC and mixed networks from 0 V to 690 V nominal voltage. The maximum voltage can be up to DC 1000 V and AC 760 V without additional adaption device. The device can be adjusted quickly and easily with its latching rotary switches. The measuring circuit monitoring for broken wire detection and the LED chain for indication of the current insulation resistance are further convincing features of the LK 5894. Advantages and customer benefit Preventive fire and plant protection Early insulation fault detection during operation No additional ballast needed Fast error localisation via selective earth fault detection to L+ and L Suitable for universal application in non-earthed DC/AC and mixed networks Suitable for system leakage capacitances up to 1000 μF Simple adjustment via latching rotary switches Reliable monitoring, also in voltage-free network Measuring circuit monitoring of wire breakage

 Open the catalog to page 1
Flyer insulation monitor LK 5894-2

Insulation Monitor LK 5894 Technical features Insulation monitoring in accordance with IEC/EN 61557-8 Detection of symmetrical and asymmetrical insulation faults 2 changeover contacts Max. voltage up to DC 1000 V and AC 760 V Adjustment range prewarning threshold: 20 kΩ ... 2 MΩ Adjustment range alarm threshold: 1 kΩ ... 250 kΩ Open circuit or closed circuit principle selectable for output relay Adjustment of maximum system leakage capacitance for reduction of response time Simple, clearly structured setting of the device with screw driver LED chain for indication of the current insulation resistance...

 Open the catalog to page 2

All DOLD catalogs and technical brochures

  1. SAFEMASTER

    13  Pages

  2. SAFEMASTER

    5  Pages

  3. VARIMETER PRO

    5  Pages

  4. VARIMETER

    7  Pages

  5. SAFEMASTER W

    9  Pages

  6. DOLD

    3  Pages

  7. Safety technique

    626  Pages

  8. News 2018.01

    3  Pages

  9. News 2017.01

    5  Pages

  10. News 2017.02

    3  Pages

  11. News 2016

    3  Pages

  12. Highlights

    7  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.