3 PHASES POWER FACTOR CORRECTION CAPACITORS TECHNICAL SPECIFICATIONS

3 PHASES POWER FACTOR CORRECTION CAPACITORS TECHNICAL SPECIFICATIONS

3 PHASES POWER FACTOR CORRECTION CAPACITORS TECHNICAL SPECIFICATIONS

Product catalog summary
Technical Specifications:
  • General Features: Cylindrical aluminum case, low losses, self-healing polypropylene film, high dielectric strength, 100,000 hours lifetime, environmentally friendly (no PCBs, Pb-free).
  • Application: Power factor correction, harmonic filtering.
  • Construction: Metallized polypropylene film dielectric, overpressure disconnection system, internal discharge resistors, cylindrical aluminum can, polypropylene resin fill material (UL 94V2), universal screw connection, M12 bolt fixing system.
  • Technical Standards: IEC60831-1, NOM-003-SCFI-2014.
  • Electrical Specifications: Working voltage ranges from 220-690 VAC, frequency 50/60 Hz, power tolerance -5% to +10%, operating temperature -25 to +55°C, dielectric losses <0.2 W/kvar, total losses <0.5 W/kvar, maximum overvoltage 1.1UN, maximum overcurrent 1.35IN, internal triangle connection, connection terminals max torque 5 Nm, fixed bolt max torque 9 Nm, connection cable max diameter 6.5 mm (AWG 2 max).
  • Permissible Voltage Levels: Continuous at 1.00 UN, 8 hours at 1.10 UN, 30 minutes at 1.15 UN, 5 minutes at 1.20 UN, 1 minute at 1.30 UN.
Product Codes and Characteristics:
  • Various codes with specific capacitance, power (kVAr), current (A), and size (mm) for different voltage levels (220V, 230V, 240V, 380V, 400V, 415V, 440V, 460V, 480V, 525V).
Overpressure Disconnection System:
  • Mechanical fuse on cover, verified with IEC 60831-2, no additional folds needed.
Installation Recommendations:
  • Install rejection reactors if voltage harmonics >5% or current harmonics >20% (IEEE 519).
  • Use contactors with pre-insertion resistors to avoid in-rush current.
  • Ensure dry installation site, use cold ventilation if in a cabinet, maintain 60 mm distance between capacitors, use cables for 1.5 times nominal current, verify capacitor discharge before handling, avoid hot spots, use isolated cables for arrays, adjust nut to max torque 9 Nm.
Warranty: 18 months.
Final Disposition: Capacitor waste is considered dangerous and must be solidified, stabilized, or encapsulated by a licensed company.
Revision History:
  • Multiple revisions from 2015 to 2018, including updates to certifications, specifications, sizes, and images.
See more

Catalog excerpts

3 PHASES POWER FACTOR CORRECTION CAPACITORS TECHNICAL SPECIFICATIONS-1

3 PHASES POWER FACTOR CORRECTION CAPACITORS TECHNICAL SPECIFICATIONS General Features: • Cylindrical Aluminum case • Low losses • Self-healing Polypropylene film. • High level of dielectric strength. • Life time: 100.000 hours • Friendly to the environment - No PCB's - Pb free Application: Power factor correction, Harmonic Filtering Construction: • Dielectric: Metallized Polypropylene film. • Overpressure disconnection system • Internal Discharge Resistors. • Cylindrical Aluminum can • Fill Material: Polypropylene resin, classification UL 94V2. • Connection: Universal screw • Fixing system: M12 bolt, nut and washer APPROVAL: TECHNICAL MANAGER 08/10/2018

 Open the catalog to page 1
3 PHASES POWER FACTOR CORRECTION CAPACITORS TECHNICAL SPECIFICATIONS-2

APPROVAL: TECHNICAL MANAGER 08/10/2018

 Open the catalog to page 2
3 PHASES POWER FACTOR CORRECTION CAPACITORS TECHNICAL SPECIFICATIONS-3

APPROVAL: TECHNICAL MANAGER 08/10/2018

 Open the catalog to page 3
3 PHASES POWER FACTOR CORRECTION CAPACITORS TECHNICAL SPECIFICATIONS-4

Overpressure disconnection system: • Mechanical fuse on cover, when a overpressure occurs the cover change its shape and disconnect the capacitor • Verified with IEC 60831-2 • The Can do not need additional folds APPROVAL: TECHNICAL MANAGER 08/10/2018

 Open the catalog to page 4
3 PHASES POWER FACTOR CORRECTION CAPACITORS TECHNICAL SPECIFICATIONS-5

Installation recommendations In order to do an appropriate installation of Capacitor's Banks you should follow below recommendations: • The Capacitor could amplify harmonic current if they are not specified appropriately. If the system has voltage harmonics higher than 5% or current harmonics higher than 20%, must install rejection reactors (IEEE 519) • In order to avoid In-rush current is recommended to install contactor with pre insertion resistors • The installation site has to keep dry • If capacitors are installed in a cabinet must install cold ventilation • Maintain at least 60 mm of distance...

 Open the catalog to page 5
3 PHASES POWER FACTOR CORRECTION CAPACITORS TECHNICAL SPECIFICATIONS-6

APPROVAL: TECHNICAL MANAGER 08/10/2018