DPT-R8 Series

DPT-R8 Series

DPT-R8 Series

Product catalog summary
Overview
The DPT-R8 series are advanced differential pressure transmitters designed for building automation in the HVAC/R industry. They measure static and differential pressure with field-selectable units, range, and output options.

Measurement Ranges
- DPT250-R8: ±25 to 250 Pa
- DPT2500-R8: ±100 to 2500 Pa
- DPT7000-R8: 1000 to 7000 Pa

Model Variants
Models are available with options such as display, autozero (AZ) function, and span point calibration.

Key Features
- Field adjustable, multi-range capability
- Proportional output options: 0–10 V and 4–20 mA
- Autozero function for automatic zero point calibration
- Backlit display and span point calibration

Applications
Commonly used in HVAC/R systems for valve and damper control and pressure monitoring in cleanrooms.

Specifications
- Accuracy: ±1.5% + 1 Pa
- Overpressure: Proof pressure 25 kPa, Burst pressure 30 kPa
- Response time: 4.0 s or 0.8 s
- Operating temperature: -10 to 50 °C
- Humidity: 0 to 95% rH, non-condensing
- Dimensions: 90.0 x 95.0 x 36.0 mm
- Weight: 150 g
- Protection standard: IP54

Electrical Specifications
- Voltage input: 24 VAC or VDC, ±10%
- Output: 0–10V or 4–20 mA
- Power consumption: <1.2 W

Conformance
Meets CE marking requirements, EMC Directive 2004/108/EY, and RoHS Directive 2002/95/EY.

AZ-Calibration
The AZ-calibration function automatically adjusts the transmitter zero at regular intervals, reducing maintenance needs and ensuring long-term accuracy.
See more

Catalog excerpts

DPT-R8 Series-1

DIFFERENTIAL PRESSURE TRANSMITTERS DPT-R8 Series Field adjustable, multi-range differential pressure transmitters for air DPT-R8 series differential pressure transmitters are engineered for building automation in the HVAC/R industry. The most technologically advanced transmitters on the market, measuring static and differential pressure, with field selectable units, range and output, all in a single device. DPT-R8 series devices include: including: Pa, kPa, mbar, inchWC, mmWC, psi. bi-directional, selectable via jumper, (see Model Summary). • Proportional output options including: voltage (0–10 V) and current (4–20 mA). DPT-R8 series device options offer: • AZ (autozero) function for automatic zero point calibration, eliminating the need for periodic manual autozeroing to ensure long term accuracy • Backlit display • Field adjustable span point calibration The versatility of the DPT-R8 series differential pressure transmitters ensures that the right product for your application is available. SIMILAR PRODUCTS • DPT-2W series differential pressure transmitters with DPT-R8 series devices are commonly used in HVAC/R systems for: • DPT-MOD series differential pressure transmitters • DPI series electronic differential pressure switches • PS series mechanical differential pressure switches • valve and damper control • pressure monitoring in cleanrooms MODEL SUMMARY Measurement ranges (Pa) Multi-range differential pressure transmitter - with display - with AZ & span point calibration - with AZ, display and span point cal

 Open the catalog to page 1
DPT-R8 Series-2

DIFFERENTIAL PRESSURE TRANSMITTERS DPT-R8 Series SPECIFICATIONS Performance Accuracy (from applied pressure): ±1,5 % + 1 Pa (including: general accuracy, temperature drift, linear ity, hysteresis, long term stability, and repetition error) Thermal effects: Temperature compensated across the full spectrum of capability. Overpressure: Proof pressure: 25 kPa Burst pressure: 30 kPa Zero point calibration: Automatic autozero or manual pushbutton Response time: 4.0 s or 0.8 s, selectable via jumper Dimensions: Case: 90.0 x 95.0 x 36.0 mm Weight: 150 g Mounting: 2 each 4.3 mm screw holes, one slotted...

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.