1. Catalogs
  2. detectomat GmbH
  3. PRIMARY PULSED POWER SUPPLY, 2 A
video corpo

PRIMARY PULSED POWER SUPPLY, 2 A

PRIMARY PULSED POWER SUPPLY, 2 A

Product catalog summary
Product Overview: The Primary Pulsed Power Supply, model 2 A 2402STE, is a universal mains adapter designed for emergency power supply in the detect 3000 range. It is compliant with EN 54-4 A1 2002, A2 2006, and VdS standards, suitable for fire alarm and detection systems.
Key Features:
  • Continuous active battery monitoring ensures maximum battery life.
  • Deep discharge protection disconnects the battery at 21 V to prevent damage.
  • Battery charging is activated only when a battery is correctly connected.
  • LED indicators: Green for mains presence, Red for output, battery, charger faults, and mains failure.
  • Includes two solid-state relay output contacts.
Technical Specifications:
  • Battery Capacity: 2 x 17 Ah
  • Input Voltage: 110 V to 230 V AC, 50 Hz to 60 Hz
  • Output Voltage: 27.6 V DC nominal
  • Output Current: Max 2.0 A
  • Protection Class: IP 31
  • Operating Temperature: -5°C to +40°C
  • Storage Temperature: -20°C to +80°C
  • Humidity: Max 95% (non-condensing)
  • Dimensions: 420 mm x 400 mm x 80 mm
  • Weight: 6.2 kg (without batteries)
  • Material: Sheet metal
  • Color: White
Compliance and Approvals:
  • Standards: EN 54-4:1997+A1:2002+A2:2006
  • VdS Approval: G 209142
  • CE-CPD Number: 0786-CPD-20787
  • Further Approvals: CNOBP: 1773 / 2013
See more

Catalog excerpts

PRIMARY PULSED POWER SUPPLY, 2 A-1

PRODUCT INFORMATION SHEET Actual status: 15.02.18 PRIMARY PULSED POWER SUPPLY, 2 A VdS-approval G 209142 Universal primary pulsed mains adapter for the use as an emergency power supply unit for the detect 3000 range. Approved according to EN 54-4 A1 2002, A2 2006 and VdS for the use according to VdE 0833 • Recommended for fire alarm and detection system and other safety systems • Well-appointed indication the technical condition • Maximum battery life is assured through continuous active battery monitoring • Deep discharge protection disconnects battery from load when battery voltage falls to 21 V • Battery charging circuit is energised only when a battery is correctly connected • Mains indicator LED (green) showing mains present • Fault indicator LED (Red) flashes on detection of output fault, battery fault, charger fault and mains failure • With 2 solid state relay output contacts • Mains indicator LED (green) showing mains present • Fault indicator LED (Red) flashes on detection of output fault, battery fault, charger fault and mains failure • With 2 solid state relay output contacts Technical Data Battery capacity Input Voltage Output voltage Output current Protection class Ambient temperature Storage temperature Sheet metal Further approvals Detectomat GmbH An der Strusbek 5 22926 Ahrensburg, Germany Product changes, technical changes

 Open the catalog to page 1
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.