Product Overview: The Detectomat Fire Control Panel DETECT 3004PLUS S-HOUSING is a microprocessor-controlled panel designed for use with Loop 3000 fire detection system components. It is compliant with EN 54-2 A1 2006, EN 54-4 A1 2002, A2 2006, and VdS standards, suitable for VdE 0833 applications.
Key Features:
  • Large LCD display with 160 x 80 points resolution.
  • RS-232 interface for programming via DPT-Software.
  • Capacity for 2 modules, each connecting up to 126 Loop 3000 components.
  • Supports up to 128 programmable detector zones.
  • Event log memory for up to 500 messages.
  • Programmable for up to 504 connections.
  • Compliant with EN 61000-6-3 class B for emissions, suitable for sensitive areas.
  • Option for 2 conventional interface cards for 16 conventional zones.
  • Extinguishing interface for controlling systems per EN 12094.
  • Integrated interface for up to 63 additional network components.
Technical Specifications:
  • Supply Voltage: 230 V AC (-15% / +10%).
  • Emergency Supply: 2 x 12 V/12 Ah.
  • Power Supply: 24 V DC/72 W/3.5 A; 1 output 24 V DC/800 mA for external devices.
  • Quiescent Current: 250 mA.
  • Display: LC-display 160 x 80 pixel, backlit.
  • Interfaces: RS-232, Bitbus (RS-485 based), Fire brigade interface.
  • Protection Class: IP 30.
  • Operating Temperature: -5°C to +40°C.
  • Humidity: 5% to 95% (non-condensing).
  • Dimensions: 490 mm x 420 mm x 150 mm.
  • Weight: 12 kg without batteries.
  • Material: Sheet metal, light grey RAL 7035.
Compliance and Approvals:
  • Standards: EN 54-2: 1997 A1:2006; EN 54-4: 1997 A1:2002 A2:2006.
  • VdS-approval: G 203068.
  • System-approval: S 210001.
  • CE-CPD-Number: 0786-CPD-20817.
  • Further Approvals: EN 12094 for 1 area-extinguishing panels.
Additional Remarks: The product is supplied without loop modules and network components.
See more

Catalog excerpts

FIRE CONTROL PANEL DC3400 COMPACT-1

PRODUCT INFORMATION SHEET Actual status: 15.02.18 Microprocessor controlled fire control panel for the use with the Loop 3000 fire detection system components. Approved to EN 54-2 A1 2006, EN 54-4 A1 2002, A2 2006 and VdS for the use according to VdE 0833. • Large LCD, 160 x 80 points • RS-232 interface for easy programming via DPT-Software • Space for 2 modules to connect 126 Loop 3000 fire detection system components per module • Up to 128 programmable detector zones • Event log memory of up to 500 messages • Easy programming of up to 504 connections • In accordance to EN 61000-6-3 class B for emissions, so suitable for the use in sensitive areas • Option for 2 conventional interface cards for controlling up to 16 conventional zones • Extinguishing interface for controlling extinguishing and gas suppression systems in accordance to EN 12094 • Integrated interface for the connection of up to 63 additional network components • Integrated control of extinguishing systems via the standard extinguishing interface in accordance to VdS Technical Data Supply Voltage230 V AC (-15% / +10%) Emergency Supply2 x 12 V/12 Ah Power Supply 24 V DC/72 W/3,5 A; 1 output 24 V DC/800 mA for external devices Display Interfaces_ Protection class_ Ambient temperature Humidity_ Dimensions (H x B x T) Weight Material_ Standards VDS-approval_ System-approval CE-CPD-Number 3 inputs for collective evetnts_ LC-display 160 x 80 pixel. backlit RS-232, Bitbus (RS-485 based), Fire brigade interface IP 30_ 12 kg without batteries Sheet metal_ Further approvals_EN 12094 for 1 area-extinguishing panels_ Remarks Supply without loop modules, network components Detectomat GmbH An der Strusbek 5 22926 Ahrensburg, Germany detectomat.com Product changes, technical changes and mistakes reserved.

 Open the catalog to page 1
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.