1. Catalogs
  2. DETAS
  3. Catalogue Surge protection Low voltage

Catalogue Surge protection Low voltage

Catalogue  Surge protection  Low voltage
1 / 40 PagesView full catalog

Catalogue Surge protection Low voltage

Product catalog summary
Introduction
SALTEK, a Czech company founded in 1995, specializes in surge protection devices (SPD) for low voltage, telecommunications, and photovoltaic systems. The company operates from Ústí nad Labem and Prague, emphasizing quality with certifications in ISO 9001, ISO 14001, and OHSAS 18001.
Product Specifications
SALTEK's SPDs are classified into three types per EN 61643-11 standards: Type 1 (Lightning current arresters), Type 2, and Type 3 (Surge arresters). These devices protect against overvoltage and electromagnetic disturbances.
Technical Standards and Compliance
Installation and design follow EU harmonized standards like EN 50310, IEC 60364, and EN 62305, covering protective bonding, lightning protection, and risk assessment.
Installation and Connection Guidelines
Effective protection requires proper installation, including positioning devices near input cables, minimizing conductor impedance and length, ensuring conductor cross-section is larger than PEN conductor diameter, and installing arresters before RCDs.
Product Features and Technical Data
SALTEK's SPDs feature replaceable modules, visual and remote fault signaling, and operate in a wide temperature range. Specifications include nominal and maximum voltage, discharge current, voltage protection level, response time, and degree of protection.
Specifications Overview
SPDs are designed for low-voltage networks, categorized as Type 1 and Type 2 (class B+C), suitable for various network configurations. Key specifications include nominal voltage (230 V AC), maximum operating voltage (up to 275 V AC/350 V DC), discharge currents, and protection levels.
Features
SPDs offer replaceable modules, no follow or leakage current, low residual voltage, and optional remote status signaling.
Compliance
Products meet IEC 61643-11 ed. 1.0 and EN 6163-11:2012 standards.
Ordering Information
Each model has a specific ordering number, with replacement modules available for maintenance.
Technical Data for Specific Models
SPD Type 2 and Type 3 are designed for different network configurations, with specifications for nominal voltage, discharge current, and protection levels. They are mounted on DIN rails and offer optional remote signaling.
Accessories
Replacement modules are available for maintenance without circuit disconnection.
Product Range
The range includes devices for low voltage systems, renewable energy, control lines, telecom lines, video/security, and Ethernet, each designed for specific surge protection needs.
Contact Information
Contact details for SALTEK's headquarters and sales office in the Czech Republic are provided for inquiries and support.
See more

Catalog excerpts

Catalogue  Surge protection  Low voltage-2

SALTEK, s.r.o. (limited liability company), is a Czech company specialising in the develop- ment and manufacture of surge protection devices (SPD). SALTEK offer a wide range of li- ghtning current arresters and surge arresters type 1 to 3, pursuant to EN 61643-11, as well as surge arresters for information technolo- _~ gy, measurement and control, telecommuni- I ^r*Ji? cations, also for the protection of photovol- I & - ' j> taic applications. ft¥ -^^i^^i^SS SALTEK has been in the business since 1995. n* Jfc^ lAl^lPl Currently, the company has 2 centres in the 'JJoT Czech Republic. Its headquarters,...

 Open the catalog to page 2
Catalogue  Surge protection  Low voltage-3

CATALOGUE SURGE PROTECTION LOW VOLTAGE Lightning current arresters based on spark-gap technology Terminal protection for DIN rail Powerful combined lightning and surge arrester modern technology – no follow current, no leakage current Economical lightning and surge arresters based on MOV technology Versatile standard product with excelent reliability Variety of voltages Enhanced MOV-GDT combination reducing leakage current with prolonged MOV lifetime, T3 tested Terminal protection The complete range of devices for low voltage power supply, signal, measurement, data and telecom lines also for...

 Open the catalog to page 3
Catalogue  Surge protection  Low voltage-4

Lightning and surge protection Lightning and surge protection 1. Introduction – Legislative The use of modern sophisticated equipment, consumer electronics and control systems places high demands on their electromagnetic compatibility. Modern electronic control systems provided with circuits with a very high integration level are becoming more and more sensitive to electromagnetic disturbance and overvoltage. The installation of surge protections according to effective legal standards will reduce the danger of their being damaged to a minimum. Technical designs are defined by standards harmonised...

 Open the catalog to page 4
Catalogue  Surge protection  Low voltage-5

I Lightning and surge protection 2. Connection of protections inTN,TT and IT systems Principle of connection of surge 3. Principles of positioning and wiring of surge arresters and lightning current arresters Surge arresters and lightning current arresters cannot be installed in the distribution system at random. You must be aware of the fact that protection should be placed at the closest proximity to the input feed cable in order to minimize the inductive loop area, see fig. 1. Fig. I - Examples of device positioning in the distribution system. overhead, PEN (PE) down overhead, PEN (PE) up...

 Open the catalog to page 5
Catalogue  Surge protection  Low voltage-6

Lightning Current Arresters FLP-SG50 V FLP-SG50 VS SPD type 1 – lightning current arrester Encapsulated high-performance spark gap with replaceable module, visual fault signalling To be installed in low-voltage distributions at the boundary of LPZ 0A and LPZ 1 zones to prevent overvoltage effects induced during direct or indirect lightning strikes in the most demanding applications in the heavy and chemicals industry, power stations, etc. Remote status signalling (S). Dimension drawing Basic circuit diagram connection of signalization terminal Technical data Nominal voltage Maximum operating...

 Open the catalog to page 6
Catalogue  Surge protection  Low voltage-7

Lightning Current Arresters FLP-A50N VS SPD type 1 – lightning current arrester N-PE module, replaceable module To be installed in low-voltage distributions at the boundary of LPZ 0A–LPZ 1 zones and higher to prevent overvoltage effects induced during direct or indirect lightning strikes for the connection of SPD type 1 in the mode 1+1. Basic circuit diagram Dimension drawing Technical data Nominal voltage Maximum operating voltage Nominal discharge current (8/20 μs) Maximum discharge current (8/20 μs) Lightning impulse current (10/350 μs) Voltage protection level Response time Ability to independently...

 Open the catalog to page 7
Catalogue  Surge protection  Low voltage-8

Lightning Current Arresters FLP-A100N VS SPD type 1 – lightning current arrester N-PE module, replaceable module To be installed in low-voltage distributions at the boundary of LPZ 0A and LPZ 1 zones to prevent overvoltage effects induced during direct or indirect lightning strikes for the connection of SPD type 1 in the mode 3+1. Basic circuit diagram Dimension drawing Technical data Nominal voltage Un Maximum operating voltage Uc Nominal discharge current (8/20 μs)/pole In Maximum discharge current (8/20 μs) Imax Lighting impulse current (10/350 μs)/pole Iimp Voltage protection level Up Response...

 Open the catalog to page 8
Catalogue  Surge protection  Low voltage-9

Lightning Current Arresters FLP-B+C MAXI V FLP-B+C MAXI VS SPD type 1 and type 2 versatile single-pole arrester Surge protective devices (SPD) type 1 and type 2 (class B+C) serve for protection of low-voltage (230/400 V AC) networks and connected appliances against surge voltages due to direct or indirect lightning strikes in the concept of zone lightning protection at the boundary of the LPZ 0 and LPZ 1 (or higher) zones. Replaceable module offers a combination of heavy duty gas discharge tube (GDT) rated at 25 kA (10/350 μsec pulse) with high energy varistors block. This proven technology guarantee...

 Open the catalog to page 9
Catalogue  Surge protection  Low voltage-10

Lightning Current Arresters FLP-B+C MAXI V/1+1 FLP-B+C MAXI VS/1+1 SPD type 1 and type 2 2-pole (1+NPE) arrester for single phase TT (TNS) networks Total Iimp = 50kA (10/350) Surge protective devices (SPD) type 1 and type 2 (class B+C) serve for protection of low-voltage (230/400 V AC) networks and connected appliances against surge voltages due to direct or indirect lightning strikes in the concept of zone lightning protection at the boundary of the LPZ 0 and LPZ 1 (or higher) zones. Replaceable module offers a combination of heavy duty gas discharge tube (GDT) rated at 25 kA (10/350 μsec pulse)...

 Open the catalog to page 10
Catalogue  Surge protection  Low voltage-11

Lightning Current Arresters FLP-B+C MAXI V/2 FLP-B+C MAXI VS/2 SPD type 1 and type 2 2-pole arrester for single phase TNS networks Total Iimp= 50kA (10/350) Surge protective devices (SPD) type 1 and type 2 (class B+C) serve for protection of low-voltage (230/400 V AC) networks and connected appliances against surge voltages due to direct or indirect lightning strikes in the concept of zone lightning protection at the boundary of the LPZ 0 and LPZ 1 (or higher) zones. Replaceable module offers a combination of heavy duty gas discharge tube (GDT) rated at 25 kA (10/350 μsec pulse) with high energy...

 Open the catalog to page 11

All DETAS catalogs and technical brochures

Archived catalogs

  1. MSCD series

    2  Pages

  2. MDCD series

    2  Pages

  3. TDC series

    1  Page

  4. TDCL series

    1  Page

  5. TSCD series

    2  Pages

  6. GSA SWD0.2

    32  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.