RoCoil

RoCoil

Product catalog summary
Overview: The DENT RōCoil™ Current Transformers are designed for accurate, non-intrusive measurement of AC current, pulsed DC, or distorted waveforms, particularly where conventional rigid core CTs are unsuitable. They can measure AC current over a wide dynamic range from 20 Hz to 5 kHz.
Specifications:
  • Available in four lengths: 40 cm (16”), 60 cm (24”), 90 cm (35”), and 120 cm (47”).
  • Window sizes range from 11.5 cm (4.5”) to 37 cm (14.6”).
  • Output signal is 131 mVAC/1000A at 60 Hz and 109.2 mV/1000A at 50 Hz.
  • Current range is 5 - 5000A AC with typical accuracy of less than 0.6%.
Electrical Characteristics:
  • Output signal: 131 mV/1000A at 60 Hz, 109.2 mV/1000A at 50 Hz.
  • Wire colors: White for positive, Brown for negative, Bare wire for shield.
  • Phasing arrow points towards load with a phase shift of less than 0.2° at 50/60 Hz.
  • Frequency range: 20 Hz to 5 kHz.
  • Linearity: ± 0.2%.
  • Temperature sensitivity: 0.07% per °C.
Mechanical and Safety Features:
  • Coil materials are made of blue thermoplastic rubber, flame retardant UL 94 V-0 rated.
  • Working temperature ranges from -20 °C to +70 °C (-4° to +158 °F).
  • Working voltage is 1000 Vrms maximum with dielectric strength of 7400 VAC around the coil.
  • Certifications include conformity to UL STD 61010-1 and CAN/CSA STD C22.2 No. 61010.
Performance and Testing:
  • All accuracies are specified at 20°C (±2°C) with the RōCoil™ centered on the conductor.
  • CT testing was performed with a 16” RōCoil, with the conductor filling 90% of the RōCoil window.
  • RōCoil CTs are UL Rated to 100KA AC and have been verified to meet the C57.13-2008 Class 1.2 Standard.
See more

Catalog excerpts

RoCoil-1

The DENT R6Coil™Current Transformers have been designed for accurate non-intrusive measurement of AC current, pulsed DC or distorted waveforms where conventional rigid core CTs are unsuitable. This type of sensor may be used to measure AC current over a wide dynamic range and from 20 Hz to 5 kHz. Note: Some applications may require use of integrator/amplifier. See also R6Coil mV™. Accuracy (typical) < 0.6%** All accuracies specified at 20°C (±2°C) with RoCoil™ centered on conductor. Output Signal Wire Colors 131 mV/1000A @ 60 Hz 109.2 mV/1000A @ 50 Hz White = (+) positive Brown = (-) negative Bare wire = shield Phasing Phase Shift Frequency Range Useful Current Range Linearity Temperature Sensitivity Arrow Points Towards Load < 0.2° at 50/60 Hz 20 Hz to 5 kHz* 5 - 5000A AC* E Transformer Coil Diameter F Wire Lead Total Length Ratio Error MECHANICAL Coil Materials Coupling Materials Shielding Blue thermoplastic rubber, flame retardant UL 94 V-0 rated PA6 UL 94 V-0 rated Working Temp CT Primary Current (Amps) 1.0 0.5 0.0 -0.5 -1.0 Phase Error RoCoil™ PART NUMBERS SAFETY Working Voltage 1000 Vrms maximum Dielectric Strength 7400 VAC around coil Certifications f £ BUT Conforms to UL STD 61010-1 ClHUS Certified to CAN/CSA STD C22.2 E186827 No. 61010 CT testing performed with 16"RoCoil. Conductor used filled 90% of RoCoil window. *Depending on meter compatibility. ROCoil CTs UL Rated to 100KA AC. ELITEpro SP/XC (v .212 or newer firmware) and PowerScout™ 3 and 24 (v. 3.16 or newer firmware) rated for 5-5000A. Meters with earlier firmware versions rated from 50-5000A AC. PowerScout™ 18 rated for 50-3500A. **Installed using best practices with conductor centered in the CT window and ensure any external conductors are a minimum distance of > 2X the diameter of the ROCoil. Accuracy below 20A rated at 1.5% +/- 0.5A when used with DENT ELITEpro/PowerScout meters. ROCoil have been 100% verified to meet the C57.13-2008 Class 1.2 Standard. © DENT Instruments, Inc. rev 102113 All specifications subject to change without notice. CONTACT US DENT Instruments, Inc. Energy & Power Measurement Solutions An ISO 9001:2008 Certified Company 925 SW Emkay Drive Bend, Oregon 97702 USA 541.388.4774 | 800.388.0770 www.DENTinstruments.com