Catalog excerpts
REVENUE GRADE INSTRUMENTS FOR SUPERIOR ENERGY MEASUREMENT Data Centers Tenant Submetering Bi-Directional Metering Real-Time Power Monitoring in Commercial, Retail, and Industrial environments MAXIMUM FLEXIBILITY FOR MONITORING The PowerScout 24 HD is a versatile, multi-channel instrument. The flexible design allows it to be configured for monitoring multiple electrical circuits. Designed specifically for applications where 12 channels are not enough, but 48 channels are overkill, the just-right PowerScout 24 HD can be supplied with any of DENT’s internally-shunted, 333 mV output split-core or RōCoil CTs. Monitor any combination of up to 8 three-phase or 24 single-phase electrical devices with a single meter. With data updates every 1 second and ANSI C12.202010 Class 0.2 revenue grade accuracy (depending on CT), the PowerScout 24 HD is well-suited for data center monitoring, tenant submetering, and for accountability metering in commercial, retail, and industrial facilities. 24 channels: Multi-circuit submeter monitors voltage, current, power, energy, and many other electrical parameters on any combination of single and/or threephase systems Two independent voltage inputs allow the PowerScout HD meter to be used on two systems simultaneously Line-Powered: 90-600V Phase-to-Phase Power Supply Revenue grade. ANSI C12.20-2010 Class 0.2 Available with UL 94-V0 enclosure or as a circuit board on a mounting plate that helps facilitate easy, safe installation Safest installation ever: TouchSāf™ HighVoltage Cover offers additional level of protection The PowerScout HD uses both BACnet or Modbus protocol and features 2 digital pulse input ports. All models feature both serial and Ethernet. Floating Point: IEEE-754 data format allows for bidirectional monitoring and eliminates scaling factors Mix-and-match a full range of Split Core or RōCoil™ Rogowski-style CTs, including several revenue-grade options Display shows real-time information about the meter configuration and metered data PhaseChek™ confirms proper CT orientation UL Listed (enclosure version) or UL Recognized (plate and circuit board only version) INDUSTRY-STANDARD MODBUS OR BACNET The PowerScout 24 HD supports both Modbus (based on SunSpec IEEE754) and BACnet communications protocols. Communications interface can be accomplished through standard serial RS-485 or Ethernet using either Modbus, BACnet MS/TP, Modbus TCP, or BACnet IP protocols. Additionally, the PowerScout 24 HD features two pulse inputs. EASY INSTALLATION Every PowerScout is line powered and designed to operate on any voltage from 90-600VAC. The PowerScout 24 HD is equipped with two independent voltage inputs, allowing for the monitoring of customer-derived voltage networks. Modbus & BACnet protocols are field-selectable and any combination of split-core or flexible RōCoil CTs can be used. Configure the meter prior to installation using the ViewPoint HD software utility and a direct USB connection or by using the built-in web server. Eliminate expensive trips back into the field: patented* PhaseChek™ ensures proper CT-to-phase installation the first time. *U.S. Patent and Tradema
Open the catalog to page 1POWERSCOUT ™ 24 HD KE Y HARDWARE /S O FT WA R E FE AT UR E S EASY DEPLOYMENT Setting the PowerScout HD up for a new deployment has never been easier thanks to two features: Network Scan Using ViewPoint HD Software, you can now quickly scan the local area network and find all the PowerScout HD meters installed on the network. The results page shows each meter’s system description and even allows for some basic meter setup directly from the scan window. Use ViewPoint HD to give each meter a “friendly” name, such as “3rd Floor Utility Rm,” to identify the right meter even faster....
Open the catalog to page 210. Navigation Buttons 11. Voltage Input 1 12. Voltage Input 2 13. Mounting Plate (Optional) 14. TouchSāf™ High Voltage Cover (IP30) 15. 1” EMT Conduit Connection (x6) 16. ABS Plastic Enclosure Detailed information about the PowerScout HD meter hardware and ViewPoint HD Software can be found in the Operator’s
Open the catalog to page 3POWERSCOUT ™ 24 HD SPECIFICATIONS TECHNICAL SERVICE TYPE Single Phase, Split Phase, Three Phase-Four Wire (WYE), Three Phase-Three Wire (Delta) WIRE CONNECTIONS 12-28 AWG 600 VAC, Voltage connection must be #14 AWG or larger & 600 VAC rated From L1 Phase to L2 Phase. 90-600VAC RMS CAT III 50/60Hz, 500mA AC Max. Use of 12 volt auxiliary output requires 100 VAC minimum input voltage. Panel Mount/Enclosure TOUCHSĀF™ HIGH VOLTAGE COVER IP30. Available with PS24 Enclosure & Plate Models 0.5A Fuse 200kA interrupt capacity OPERATING TEMPERATURE* Unregulated 12VDC output, 200 mA, self-resetting...
Open the catalog to page 4All DENT INSTRUMENTS catalogs and technical brochures
-
PowerScout 3 HD
3 Pages
-
1000A Clamp
1 Pages
-
RoCoil
1 Pages
-
RoCoil mV
1 Pages
-
RoCoil TCA-5
1 Pages
-
RoCoil vs RoCoil mV
1 Pages
-
72" RoCoil
1 Pages
-
150A EZ Clamp
1 Pages
-
100A Midi Hinged CT
1 Pages
-
600/1000A Large
1 Pages
-
50/100A Small Data Sheet
1 Pages
-
SMARTlogger Data Sheet
2 Pages
-
PowerScout 3037/24 Datasheet
2 Pages
-
ELITEpro XC Datasheet
8 Pages