ELITEpro XC Datasheet
8Pages

{{requestButtons}}

Catalog excerpts

ELITEpro XC Datasheet - 1

For single or 3-phase systems using 80-600V phase-to-phase (AC or DC) services when line powered or 0-600V (AC or DC) when externally powered. Measures up to four channels of energy metrics with currents ranging from 0-6,000 amps. Analog Inputs record analog data with configurable input ranges for voltage (0-10 VDC) or current loop (0-20 or 4-20 mA) transducers. Analog inputs are used for process or environmental correlation studies with power. Line-powered - no need for batteries or external power source. User-selectable recording intervals as short as every 1 second. 16 MB non-volatile memory standard for months of recording time. Better than 1% accuracy (<0.2% typical). Fast USB connection and standard Ethernet port. ELITEpro XC may be configured with optional Bluetooth® wireless technology. Optional Wi-Fi interface allows for remote data collection over wireless networks. Check real-time values using a Wi-Fi-enabled laptop, tablet, or smartphone via a web browser. Simple yet powerful Windows-based ELOG™ software package for setup, data retrieval, and analysis. Easy data exporting to almost any analysis program. Easy to setup and installs in minutes. Patented PhaseChek™ LED indicators ensure correct CT orientation at installation. Rugged and compact—easily fits inside breaker panels and switch gear. Measurement and Verification (M&V) Studies Electrical Load Profiling Energy Audits New Technology Assessment Studies

Open the catalog to page 1
ELITEpro XC Datasheet - 2

FOCUSED ON ENERGY MEASUREMENT DENT Instruments designs and manufactures data loggers and energy recorders for today’s energy professionals. Our products are often the first step in developing strong energy strategies, for maintaining peak operations, and for lowering operating costs. Our company has built a reputation for providing instruments of the highest quality whose robust design, small size and remote data acquisition make them the loggers of choice for companies large and small. Since the company’s emergence in 1988, we have performed energy measurement studies for a wide range of...

Open the catalog to page 2
ELITEpro XC Datasheet - 3

LINE POWERED WITH REDUCED IMPACT ON THE ENVIRONMENT EXCLUSIVE CT PHASE ERROR CORRECTION The ELITEpro XC is powered directly from the phases of the service being measured. It incorporates a broadband power supply which operates on virtually any 80-600V phase-tophase service. You will not have to worry about constantly changing or recharging batteries, nor finding an external power source at the job site. And you will avoid the negative environmental impact of disposing of batteries containing rare earth materials that are difficult to recycle or reclaim. All CTs exhibit both a ratio error...

Open the catalog to page 3
ELITEpro XC Datasheet - 4

EASY SETUP, INSTALLATION, AND DATA RETRIEVAL Using the ELITEpro XC on your next project is as easy as 1, 2, 3. INSTALL ELOG AND SEND A SETUP TABLE TO THE ELITEPRO XC The ELITEpro XC is configured using ELOG software. A Setup Table is the file that programs the logger for an upcoming project. Set parameters such as sampling rate and type of service then send the file to the logger. The ELITEpro XC is now ready for deployment. A simple one-page Setup Table guides you through the ELITEpro XC’s flexible metering options. CONNECT THE ELITEPRO XC TO THE PANEL YOU NEED TO MEASURE DOWNLOAD THE DATA...

Open the catalog to page 4
ELITEpro XC Datasheet - 5

CO M M U N I C ATIO N O PTIO N S CONNECT TO THE ELITEPRO XC FOUR WAYS STANDARD USB AND ETHERNET CONNECTIONS Every ELITEpro XC includes a USB and Ethernet (RJ-45) port. Connect directly to the ELITEpro XC via the included A-to-B USB cable. Or, have the ELITEpro XC on your local area network for convenient remote data download. Supports 10/100 MB Ethernet over Cat 5 or better and can be configured for DHCP or static IP. Schedule automatic data downloads from the logger using AutoPoll software (included with ELOG). Reconfigure the ELITEpro XC for a new project without leaving your workstation....

Open the catalog to page 5
ELITEpro XC Datasheet - 6

SMALL SPLIT CORE SCS-0050, -0100

Open the catalog to page 6
ELITEpro XC Datasheet - 7

The ELITEpro XC can be equipped with a wide selection of current transformers, which can be interchanged depending on your project needs. Choose from compact and economical Split-Core CTs, convenient Clamp-On style CTs, or the versatile Rogowski Flex CTs. All CTs are shunted and each type offers its own particular advantages depending on your application. LARGE SPLIT CORE SCL-0600, -1000 'Depending on meter compatibility. ELITEpro SP (v.212 or newer firmware) rated for 5-5000A. 5000V around the case 600V rated leads 5200 VAC, 50/60 Hz between primary, secondary and the outer case of the...

Open the catalog to page 7
ELITEpro XC Datasheet - 8

Several voltage clips options are available to meet your project needs: Croc Clips, Fused Crocs, Colored Leads, or Shark Clips. VOLTAGE LEAD COLORS (choose one) U = US/NORTH AMERICAN* ADDITIONAL COMMUNICATION OPTIONS (choose one) N = NONE (ETHERNET & USB ONLY) B = BLUETOOTH® WIRELESS TECHNOLOGY WI = WI-FI WITH INTERNAL ANTENNA WE = WI-FI WITH EXTERNAL 3 DBI ANTENNA * For DC applications, please see manual for full specifications and application details. t ELITEpro XC loggers that are equipped with a Wi-Fi package contain an internal antenna. An external antenna is...

Open the catalog to page 8

All DENT INSTRUMENTS catalogs and technical brochures

  1. 1000A Clamp

    1 Pages

  2. RoCoil

    1 Pages

  3. RoCoil mV

    1 Pages

  4. RoCoil TCA-5

    1 Pages

  5. 72" RoCoil

    1 Pages