Battery charger/Power supply 4921210105H Easy installation - DIN-rail mounting Automatic recovery from overload conditions Switch mode power technology Application The DCP2 can be applied as battery charger or stabilized network component as a universal DC voltage supply. As battery charger parallel operation with other DC consumers is possible. For 10A, 20A and 40A types: OUTPUT VOLTAGE DCP2 as battery charger As battery charger the DCP2 is applied to charge and to maintain the full-charge condition of closed or gastight 24V (12V) Pb batteries. In parallel operation with a battery and other consumers the nominal power for the consumers is given until interruption from the battery, e.g. for the reason of recharging/maintenance. Automatic Restart (hicc-up mode) DCP2 as network component (power supply) As stabilized network component the DCP2 supplies connected consumers with a stabilized DC voltage. Protection The DCP2 is protected against continuous short circuit as well as continuous no-load operation. Further characteristics of the DCP2 are the high efficiency and the high voltage stabilization. For 5A types: OUTPUT VOLTAGE Principle/operation Application as stabilized net unit (supply) The DCP2 supplies a constant output voltage, according to setting, in the range of 23.5-27.5V DC respectively 11.8-13.8V DC (stabilized network component). The output voltage is held constant as long as the load does not exceed the nominal current. A load exceeding the current limitation will automatically reduce the output voltage (see the curves in the next column). Typical current limit for each type is specified under Technical specifications, section Output current. Automatic Restart (hicc-up mode)
Open the catalog to page 1Type DCP2 Application as battery charger When charging of a discharged battery is initiated, a high charging current will flow, which is limited and controlled by the DCP2. Voltage will immediately jump to approx. 2.1V per cell (12.6V for 12V types and 25.2V for 24V types). Normally it is recommended from manufacturers of Pb batteries to obtain 2.25V per cell at temperatures up to 30°C, before the battery is fully charged and trickling can start. For a 12V Pb battery this gives a trickle charging voltage of 13.5V (2.25 x 6 cells) and 27V (2.25 x 12 cells) for 24V batteries. According to information...
Open the catalog to page 2Type DCP2 Technical specifications General data: Duty ratio: Continuous duty is allowed Cooling: Short circuit: Protected against continuous short circuit DCP2-2420, -2440: Three poles, C-fuse or motor circuit breaker Switch - external (setting 3A) No-load operation: Output voltage: DCP2-12XX: 12V DC (adjustable 11.8…13.8V DC) Factory setting 13.4V DC ±1% DCP2-24XX: 24V DC (adjustable 23.5…27.5V DC) Factory setting 26.8V DC ±1% Protected against continuous no-load operation Wall mounted, input terminals placed at the top and output terminals at the bottom Output current: DCP2-XX05: 5A (typical...
Open the catalog to page 3Type DCP2 Technical specifications, cont. Hold-up time: DCP2-XX05 >80 ms at Uin = 230V AC DCP2-XX10 and -2410/115V >15 ms at Uin = 230V AC DCP2-2420 >15 ms at Uin = 230V AC DCP2-2420 >5 ms at Uin = 400V AC DCP2-2440 >5 ms at Uin = 400V AC The determined time, during which a power supply/charger’s output remains within a specified voltage range after its input ceases DCP2-2440: Primary max. 2.5 mm² Secondary 10.0 mm² Indication: Green LED – operating indication Housing: Materials: All plastic parts are self-extinguishing to UL94 (V0) DCP2-2440 is encapsulated in a metal housing Dimensions: WxHxD...
Open the catalog to page 49 Pages
4 Pages
10 Pages
4 Pages
12 Pages
9 Pages
77 Pages
15 Pages
3 Pages
30 Pages
8 Pages
2 Pages
2 Pages
3 Pages