Catalog excerpts
Compact Genset Controller Data sheet
Open the catalog to page 1Generator control and protection Engine monitoring and protection Generator and mains breaker control The Compact Genset Controller, CGC 400, is a microprocessor-based control unit containing all necessary functions for protection and control of a diesel engine. Furthermore, it contains a three-phase AC voltage measuring circuit. The unit is equipped with an LCD display presenting all values and alarms. CGC 400 is a compact flexible unit designed for the following applications: 1. Automatic engine start/stop 2. Engine protection 3. Breaker control 4. Generator protection 5. Automatic Mains...
Open the catalog to page 3Display folios
Open the catalog to page 4Terminal overview CGC 400 unit rear view
Open the catalog to page 5Mains voltage Generator voltage Generator current Binary inputs Multi-functional inputs Power supply Emer. stop INFO Terminals 28-32, 56-57 and 58-59 are not available in CGC 412. Input/output table Input/output table Type Digital input, configurable Relay output, configurable Multi-inputs, can be configured to either Pt100/1000, 4 to 20 mA, RMI* or binary input *RMI is short for resistance measurement input. INFO For further information about terminals, please refer to the "Installation Instructions".
Open the catalog to page 6Technical specification Technical specifications 8.0 Vdc to 35.0 Vdc, continuous power supply. Reverse protection -35 Vdc continuously Dropout cranking Able to survive 0 V for 50 ms, providing supply was at least 10 V before drop-out and supply recovers to 8 V. This is achieved without the need for internal batteries. Power consumption Protection response time (Delay set to min.) generator: Reverse power < 400 ms Power/overload < 400 ms Over-current < 400 ms Over-/under-voltage < 400 ms Over-/under-frequency < 400 ms Accuracy on AC voltage measurement Class 1.0 to IEC/EN 60688 Class 2.0 on...
Open the catalog to page 73 A @ 35 Vdc, voltage free output 8 A @ 250 Vac/30 Vdc, voltage free output 8 A @ 250 Vac/30 Vdc, voltage free output 8 A @ 250 Vac/30 Vdc, voltage free output Service port Standard USB-B plug (standard USB A/B cable needed) 5 A/1 A (rated). Max. consumption: 0.3 VA/phase Working conditions Storage condition Protective level All plastic materials are self-extinguishing to UL94 (V1) Plug connections Tightening torque AC voltage/current inputs: 3.5 mm2 (13 AWG) multi-stranded Other: 1.5 mm2 (16 AWG) multi-stranded 0.5 Nm (5-7 lb-in) CE/EMC marking Load dump ISO 7637-2 (24V DC system - test...
Open the catalog to page 8Order specification and disclaimer Order specifications Variants Mandatory information Additional accessories to the standard variant Example: Mandatory information Item no. Additional accessories to the standard variant
Open the catalog to page 9Mandatory information Item no. Example: Mandatory information Item no. DEIF A/S reserves the right to change any of the contents of this document without prior notice. The English version of this document always contains the most recent and up-to-date information about the product. DEIF does not take responsibility for the accuracy of translations, and translations might not be updated at the same time as the English document. If there is a discrepancy, the English version prevails.
Open the catalog to page 10All DEIF catalogs and technical brochures
-
TRI-2
9 Pages
-
EQ96-sw4, EQ96-sw7, VDQ96-sw
4 Pages
-
AGC-4 Mk II
4 Pages
-
IMD 100
12 Pages
-
KBU
9 Pages
-
ASR
77 Pages
-
DCP2
4 Pages
-
DBC-1
15 Pages
-
Battery chargers TOP
3 Pages
-
AGC-4
30 Pages
-
Alarm panel – type AL8-2
8 Pages
-
Shunt resistors
2 Pages
-
ENGINE & GEN-SET CONTROLS
2 Pages
-
G59 protection relay package
3 Pages