DSCL24 (Single Channel) Jumper Configurable - DIN or Panel Mount
3Pages

{{requestButtons}}

Catalog excerpts

DSCL24 (Single Channel) Jumper Configurable - DIN or Panel Mount - 1

Industrial Loop Isolators and Transmitters DSCL24 (Single Channel) Jumper Configurable - DIN or Panel Mount Description Each single channel DSCL24 module provides up to 36 different configurations of process current or voltage inputs and outputs. A unique snap-in tool allows quick extraction of the module’s circuit board to permit the user to reposition four (4) jumpers and reconfigure each module’s I/O. The factory default setting provides 4-20mA input and output current. Each module provides full 3-way isolation with 2300Vrms CMV input to output and 3700Vrms CMV power supply to I/O protection. Two module versions are offered that accept universal power supply of either 24 to 60VDC or AC and 85 to 230VDC or AC with the alternating current usage accepting 45 to 400Hz power. Features • Uses Universal Power Supply of 24 to 60V or 85 to 230V AC/DC • Configuration Jumpers Allows up to 36 I/O Settings • Three-Way Isolation for 2300Vrms Protection • Prevents Ground-Loop Problems • Prevents the Transfer of Interference Voltages and Currents • High Accuracy Over Full Span • No Recalibration or Maintenance Required • Narrow DIN Package, Mounts up to 27 Devices into a 19” Rack Space • DIN Rail or Panel Mountable • CE Compliant Figure 1: DSCL24 Block Diagram ©1995-2011 Dataforth Corporation, All Rights Reserved ISO9001:2008-Registered QMS

Open the catalog to page 1
DSCL24 (Single Channel) Jumper Configurable - DIN or Panel Mount - 2

Industrial Loop Isolators and Transmitters Specifications Typical at TA=+25°C and 24VDC or 230VAC ±10% supply voltage Input Range Input Limit (Iin) Input Limit (Vin) CMV Input to Output CMV Power Supply to I/O Accuracy (at 250Ω Load) Input Resistance Linearity Stability Input Overshoot Output Range(1) Output Limit (Iout) Output Limit (Vout) Limit Upper Range Bandwidth, –3dB CMR (50Hz or 60Hz) NMR Response Time Load Resistance Range Output Noise Ordering Information Model DSCL24-01 DSCL24-02 Table 1: Select Output Voltage or Current Power Supply Voltage Tolerance Power consumption...

Open the catalog to page 2
DSCL24 (Single Channel) Jumper Configurable - DIN or Panel Mount - 3

Connection Guide Jumpers B1 to B6 (table 2) are used for selecting the standard configurable ranges. Providing that the 'Span' and 'Zero' potentiometers are not adjusted, changing the range has no effect on the modules' accuracy. The 'Span' and 'Zero' allow ±10% mount accepts type rails; Dataforth Multiple modules next to each other without affecting Clamp type screw transparent cover transparent cover

Open the catalog to page 3