DL2000ID

Product catalog summary
Overview: The DL2000ID is a high precision fluxgate AC/DC current transducer designed for galvanically isolated measurement up to 3000 A. It features a 1500:1 primary/secondary current ratio, a 68 mm aperture, and a total accuracy of 7 ppm. Suitable applications include electric vehicle test benches, power measurement, and medical scanners.
Specifications: The transducer operates with a nominal primary AC current of 2000 Arms and a DC current range of -3000 to 3000 A. It has a linearity error of less than 1 ppm and an offset current of 6 ppm. The device supports a bandwidth of 300 kHz and a response time of 1 µs to 90% of step current. It requires a power supply voltage of ±14.25 to ±15.75 V and operates within a temperature range of -40 to 65 °C.
Isolation and Safety: The DL2000ID complies with IEC 61010-1 standards, offering reinforced insulation with a clearance and creepage distance of 22 mm. It can withstand transient voltages up to 12500 V for CAT III applications. The device is designed for indoor use with an ingress protection rating of IP20.
Environmental and Mechanical Characteristics: The transducer is designed for use at altitudes up to 2000 m and in environments with a pollution degree of 2. It has a mass of 5.7 kg and uses a D-sub-9 connector for connections.
Usage Instructions: The device should be powered by a DSSIU-4-1U or DSSIU-6-1U power supply. It is important to connect all cables before powering up the device and to ensure no uninsulated wires touch the metal enclosure to avoid electrical shock.
Advanced Sensor Protection Circuits (ASPC): These circuits protect the transducer from fault conditions, allowing it to handle DC and AC primary currents up to 100% of nominal value without damage.
Product Variations: The DL2000ID is available with additional calibration windings in two versions: DL2000ID-CB100 and DL2000ID-CD100, each with specific connection interfaces.
Figures and Diagrams: The document includes figures illustrating linearity error, frequency characteristics, and connection pinouts, providing visual guidance for setup and operation.
Declaration of Conformity: The document is a Declaration of Conformity from Danisense A/S, located in Taastrup, Denmark. It asserts that the product complies with specific European Community (EC) Directives and harmonized standards.
EC Directives: The product conforms to Directive 2014/30/EU and Directive 2014/35/EU, which pertain to electromagnetic compatibility and low voltage, respectively.
Harmonized Standards: The applied standards include EN 61010-1 (Third Edition):2010, EN 61010-1:2010/A1:2019, EN 61010-2-030:2021/A11:2021, and EN 61326-1:2013. These standards relate to safety requirements for electrical equipment for measurement, control, and laboratory use.
RoHS Compliance: All Danisense products are manufactured in compliance with the RoHS directive 2011/65/EU, which restricts the use of certain hazardous substances in electrical and electronic equipment. The directive was amended by directive 2015/863 to expand the list of restricted substances.
Additional Compliance: Danisense adheres to the provisions in EN 63000:2018, which provides technical documentation for the assessment of electrical and electronic products with respect to the restriction of hazardous substances.
Signature: The declaration is signed by Henrik Elbæk on March 15, 2022, in Taastrup, Denmark.
See more

Catalog excerpts

DL2000ID-1

Features • 2000 A rms nominal current • 1500:1 primary/secondary current ratio • Current output through D-sub-9 connector • Option for additional calibration windings Description High precision DC current transducer (DCCT) measuring up to 3000 A currents and continuously measuring 3000 A currents with a linearity error less than 1 ppm. Based on the ultra stable Danisense closed loop flux gate technology, the DL2000ID has very low offset and ultra low drift. It provides high resolution for precise monitoring, reliable and consistent performance, and a rugged design for durability. For calibration of currents up to ±50 A the DL2000ID-CB100 and DL2000ID-CD100 versions are available with additional calibration windings with 100 turns. Applications • Electric vehicle (EV) test bench • Power measurement and power analysis • Particle accelerators • MRI devices and medical scanners • Battery testing and evaluation systems • Current calibration purposes • Stable power supplies • Precision current sensing All information subject to change without notice

 Open the catalog to page 1
DL2000ID-2

2023-12-19 All information subject to change without notice www.danisense.com

 Open the catalog to page 2
DL2000ID-3

Linearity error Linearity error is defined as the deviation from a straight line. The straight line is a linear regression trend line based on the least squares method of the measurement points from 0 to positive max current and another trendline is calculated from 0 to negative max current. The difference between each measured point and the linear trend line is the linearity error. The linearity error eL can be expressed as (1), where Ireading is the measurement result and Ifitted is the regression value. Reading is the actual value measured at a given time. Full scale is the rated nominal value...

 Open the catalog to page 3
DL2000ID-4

Primary DC and peak current (A) Figure 2: Maximum measurement resistor RM vs. ambient temperatures Primary current (Arms) Figure 3: Maximum continuous primary current vs. frequency Figure 4: Frequency characteristics All information subject to change without notice

 Open the catalog to page 4
DL2000ID-5

A When using REINFORCED insulated wire, all wiring must be insulated for the highest voltage used. When using BASIC insulated or uninsulated wire, follow the specified voltages in the table below: All information subject to change without notice www.danisense.com

 Open the catalog to page 5
DL2000ID-6

External devices: External devices connected to current transducers must comply with the standards IEC61010-1 and IEC62368-1 and be energy-limited circuitry The transducer should only be cleaned with a damp cloth. No detergent or chemicals should be used. When multiple primary turns are used or high primary currents are applied the temperature around the transducer will increase, please monitor to ensure that the maximum ratings are not exceeded. It is recommended to have minimum 1 November 2012 mm2 Dato: per15.ampere in the primary bus bar. Intended use The DL2000ID is designed to measure current...

 Open the catalog to page 6
DL2000ID-7

Do not disassemble the unit. If the green status LED is not operating with all cables connected and the system powered up, disconnect power and contact Danisense for further instruction. If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. Positive current direction Positive current direc Figure 5: Dimensions of transducer. 0.3 mm Tolerance All information subject to change without notice

 Open the catalog to page 7
DL2000ID-8

Pin out description: DL2000ID Out+ NC Status+ Vs+ Figure 6: D-sub-9 connection pinout Dato: 15. November 2012 Measurement output negative terminal Status signal negative terminal 0 V connection for supply voltage Negative supply voltage Measurement output positive terminal Status signal positive terminal Positive supply voltage Positive current direction Is identified by an arrow on the back side isolation plastic insert. NOTICE OF PROPRIETARY RIGHTS THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION. IT MAY NOT BE REPRODUCED OR TRANSFERRED TO DOCUMENTS OR DISCLOSED TO OTHERS OR USED FOR MANUFACTURING...

 Open the catalog to page 8
DL2000ID-9

DL2000ID Product variations The DL2000ID can be ordered with additional calibration windings in two versions: DL2000ID-CB100 and DL2000ID-CD100. The difference betweens these is how the calibration windings are interfaced. The maximum ratings for calibration winding are: 500 mA Calibration winding resistance: Ampere turns (100 turns x 500 mA): Maximum continuous calibration winding current: The DL2000ID-CB100 has 100 turns of calibration winding which connects to the front mounted BNC connector (Only mounted on the DL2000ID-CB100 version) according to Fig. 9. The D-sub-9 connection is the same...

 Open the catalog to page 9
DL2000ID-10

Declaration of Conformity Danisense A/S Malervej 10 DK-2630 Taastrup Dato: 15. November 2012 Declares that under our sole responsibility that this product is in conformity with the provisions of the following EC Directives, including all amendments, and with national legislation implementing these directives: Directive 2014/30/EU Directive 2014/35/EU And that the following harmonized standards have been applied EEN 61010-1 (Third Edition):2010, EN 61010-1:2010/A1:2019 EN 61010-2-030:2021/A11:2021 EN 61326-1:2013 All DANISENSE products are manufactured in accordance with RoHS directive 2011/65/EU....

 Open the catalog to page 10

All Danisense catalogs and technical brochures

  1. DS600ID

    9  Pages

  2. DS400ID

    9  Pages

  3. DS300ID

    9  Pages

  4. DS200ID

    9  Pages

  5. DT200ID

    8  Pages

  6. DT100ID

    8  Pages

  7. DT50ID

    8  Pages

  8. DQ640ID-B

    7  Pages

  9. DQ600ID-P1300

    7  Pages

  10. DQ600ID

    9  Pages

  11. DQ500ID

    7  Pages

  12. RCM Smart

    10  Pages

  13. RCM Standard

    9  Pages

  14. DSSIU-1

    5  Pages

  15. DSUB2-20

    1  Page

  16. DSSIU-6-1U-V

    8  Pages

  17. DSSIU-4-1U

    6  Pages

  18. DS50ID

    9  Pages

  19. DL2000UB-10V

    9  Pages

  20. DL2000UB-1V

    9  Pages

  21. DS300UB-1V

    8  Pages

  22. DS300UB-10V

    8  Pages

  23. DN1000ID

    9  Pages

  24. DW500UB-2V

    9  Pages

  25. DM1200ID

    8  Pages

  26. DSSIU-6-1U

    7  Pages

  27. DR10000IM

    9  Pages

  28. DR5000IM

    9  Pages

  29. DP50IP-B

    4  Pages

  30. VOM1333-10

    1  Page

  31. DS400UB-10V

    6  Pages

  32. DC200IF

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.