VLT 2800
34Pages

{{requestButtons}}

Catalog excerpts

VLT 2800 - 1

Electrical installation, control terminals 24 General technical data 25 Technical data, mains supply 1 x 220 - 240 V/3 x 200-240V 30 Technical data, mains supply 3 x 380 - 480 V 31 Supplied with the unit 33 MD.27.A2.02 - VLT® is a registered Danfoss trademark

Open the catalog to page 1
VLT 2800 - 2

MD.27.A2.02 - VLT® is a registered Danfoss trademark

Open the catalog to page 2
VLT 2800 - 3

Order form This section makes it easier for you to specify and order a VLT 2800. Choice of frequency converter The frequency converter must be chosen on the basis of the present motor current at maximum loading of the unit. The frequency converter's rated output current IINV. must be equal to or greater than the required motor current. Mains voltage VLT 2800 is available for two mains voltage ranges: 200-240 V and 380-480 V. Select whether the frequency converter is connected to a mains voltage of: - 1 x 220 - 240 V single-phase AC voltage - 3 x 200 - 240 V three-phase AC voltage - 3 x 380...

Open the catalog to page 3
VLT 2800 - 4

3 x 380 - 480 Volt mains voltage Type 2805 2807 2811 2815 2822 2830 2840 2855 2875 2880 2881 2882 Typical shaft output PINV. [kW] 0.55 0.75 1.1 1.5 2.2 3.0 4.0 5.5 7.5 11 15 18.5 [HP] 0.75 1.0 1.5 2.0 3.0 4.0 5.0 7.5 10.0 15 20 25 Max. constant output current IINV. Max. constant output power at 400 V SINV. [A] [kVA] 1.7 1.1 2.1 1.7 3.0 2.0 3.7 2.6 5.2 3.6 7.0 4.8 9.1 6.3 12.0 8.3 16.0 11.1 24 16.6 32 22.2 37.5 26.0 Enclosure Harmonic filter All VLT 2800 units are supplied with IP 20 enclosure as standard. This enclosure level is ideal for panel mounting in areas where a high degree of...

Open the catalog to page 4
VLT 2800 - 5

Control unit The frequency converter is always supplied with an integral control unit. All displays are in the form of a six-digit LED display capable of showing one item of operating data continuously during normal operation. As a supplement to the display, there are three indicator lamps for voltage (ON), warning (WARNING) and alarm (ALARM). Most of the frequency converter's parameter Setups can be changed immediately via the integral control panel. An LCP 2 control panel to be connected via a plug to the front of the frequency converter is available as an option. The LCP 2 control panel...

Open the catalog to page 5
VLT 2800 - 6

Motor coils By fitting the motor coil module between the frequency converter and the motor it is possible to use up to 200 metres of unscreened/unarmoured motor cable or 100 metres of screened/armoured motor cable. The motor coil module has an enclosure of IP 20 and can be installed side-by-side. NB! To have long motor cables and still comply with EN55011-1A, motor coil and EMC filter for long motor cables are needed. NB! To comply with EN55011-1A the EMC filter for long motor cables can only be fitted to a VLT 2800 with integral 1A filter (R1 option). See also the section EMC Emission....

Open the catalog to page 6
VLT 2800 - 7

RFI 1B filter All frequency converters will cause electromagnetic noise in the mains supply when they are operating. An RFI (Radio Frequency Interference) filter will reduce the electromagnetic noise in the mains supply. Without an RFI filter there is a risk that a frequency converter will disrupt other electrical components that are connected to the mains and might thus cause operating disruption. Technical data for VLT 2803–2875 RFI 1B filter Max. cable length (screened/armoured) 200-240 V Max. cable length (screened/armoured) 380-480 V Enclosure Max. rated current Max. Voltage Max....

Open the catalog to page 7
VLT 2800 - 8

RFI 1B/LC filter The RFI 1B/LC filter contains both an RFI module that complies with EN 55011-1B and an LC filter that reduces the acoustic noise. LC filter Installation of thermistor (PTC) The RFI 1B/LC filter has an integral thermistor (PTC), which is activated if an overtemperature arises. The frequency converter can be programmed to stop the motor and activatee an alarm via a relay output or a digital output if the thermistor is activated. When a motor is controlled by a frequency converter, at times you will be able to hear the acoustic noise from the motor. The noise, which is caused...

Open the catalog to page 8
VLT 2800 - 9

RFI 1B/LC filter NB! To comply with EN 55011-1B the RFI 1B filter module must be fitted to a VLT 2800 with integral 1A RFI filter. Technical data for VLT 2803–2875 RFI 1B/LC filter Max. cable length (screened/armoured) 380-480 V Enclosure Max. rated current Max. voltage Max. voltage to earth Min. distance between VLT and RFI 1B/LC filter Min. distance above and below RFI 1B/LC filter Mounting Dimensions 195N3100 4.0 A H x W x D (mm) Dimensions 195N3101 9.1 A H x W x D (mm) Weight 195N3100 4.0 A Weight 195N3101 9.1 A MD.27.A2.02 - VLT ® is a registered Danfoss trademark NB! The 1B/LC filter...

Open the catalog to page 9
VLT 2800 - 10

Ordering numbers for VLT 2800 200-240 V 0,37 kW Unit RFI R1 R1 R1 R1 R1 R1 ST SB ST SB ST SB ST SB ST SB ST SB 0,55 kW Unit RFI R1 R1 R1 R1 R1 R1 ST SB ST SB ST SB ST SB ST SB ST SB 0,75 kW Unit RFI R1 R1 R1 R1 R1 R1 10 ST SB ST SB ST SB ST SB ST SB ST SB VLT 2803 1 x 220-240 V / 3 x 200-240 V Profibus DeviceNet Ordering no. DP1) 3 MBits/s 195N0001 195N0002 195N0003 195N0004 195N0005 ✓ 195N0006 ✓ 195N0007 ✓ 195N0008 ✓ 195N0009 ✓ 195N0010 ✓ 195N0011 ✓ 195N0012 ✓ VLT 2805 1 x 220-240 V / 3 x 200-240 V Profibus DeviceNet Ordering no. DP1) 3 MBits/s 195N0013 195N0014 195N0015 195N0016 195N0017...

Open the catalog to page 10
VLT 2800 - 11

3,7 kW Unit RFI - ST ST ST 3,7 kW Unit RFI R1 R1 R1 R1 R1 R1 ST SB ST SB ST SB ST SB ST SB ST SB VLT 2840 PD2 1 x 220-240 V / 3 x 200-240 V Ordering no. Profibus DP1) DeviceNet 3 MBits/s 178F5170 178F5171 ✓ 178F5172 ✓ VLT 2840 3 x 200-240 V Profibus DP1) DeviceNet 3 MBits/s ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ Ordering no. 195N0073 195N0074 195N0075 195N0076 195N0077 195N0078 195N0079 195N0080 195N0081 195N0082 195N0083 195N0084 ST: Standard unit. SB: Standard unit with integral brake. R1: With RFI filter that complies with EN 55011-1A. NB! For VLT 2803-2815 with an R1 filter it is only possible to connect...

Open the catalog to page 11
VLT 2800 - 12

Ordering numbers for VLT 2800 380-480V 0,55 kW VLT 2805 3 x 380-480 V Unit Profibus DP1) DeviceNet RFI 3 MBit/s ST SB R1 ST R1 SB ST ✓ SB ✓ R1 ST ✓ R1 SB ✓ ST ✓ SB ✓ R1 ST ✓ R1 SB ✓ 0,75 kW Unit RFI R1 R1 R1 R1 R1 R1 ST SB ST SB ST SB ST SB ST SB ST SB 1,1 kW Unit RFI R1 R1 R1 R1 R1 R1 ST SB ST SB ST SB ST SB ST SB ST SB 1,5 kW Unit RFI R1 R1 R1 R1 R1 R1 12 ST SB ST SB ST SB ST SB ST SB ST SB VLT 2807 3 x 380-480 V Profibus DP1) DeviceNet 3 MBit/s ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ VLT 2811 3 x 380-480 V Profibus DP1) DeviceNet 3 MBit/s ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ VLT 2815 3 x 380-480 V Profibus DP1) DeviceNet 3 MBit/s ✓...

Open the catalog to page 12

All Danfoss VLT Drives catalogs and technical brochures

  1. VACON® 100

    32 Pages

  2. TP5001 Range

    92 Pages

  3. Danfoss Drives

    12 Pages

  4. VLT®

    20 Pages