video corpo

Pressure switch RT

Pressure switch RT
1 / 17 PagesView full catalog

Pressure switch RT

Product catalog summary
Overview: The RT series pressure switches by Danfoss are designed for industrial and marine applications, including safety pressure switches for steam boiler plants. They feature a pressure-controlled, single-pole changeover switch with high accuracy, repeatability, and a long operational lifetime. The series includes standard pressure switches, differential pressure switches, and those with adjustable neutral zones.
Specifications: The RT pressure switches are CE marked according to EN 60947-4/-5 and PED 2014/68/EU for certain models. They are approved by various international maritime and safety organizations, including DNV GL, Lloyds Register, and Bureau Veritas. The switches operate within a wide range of pressures and temperatures, with specific models designed for ammonia and steam applications.
Features: Key features include a simple design, high accuracy, and availability with major marine approvals. The switches are rated SIL 2 according to IEC 61508, ensuring safety integrity. They are equipped with gold-plated contacts for installations with few switching cycles or low signal currents and voltages.
Technical Data: The switches cover a range of pressures from -1 to 36 bar, with mechanical differentials and adjustable neutral zones. They are constructed from materials like stainless steel, brass, and deep-drawn steel, ensuring durability and compatibility with various media.
Functionality: The switches provide alarms for both rising and falling pressures, with options for manual or automatic reset. Fail-safe designs ensure that in case of a defect, the system defaults to a safe state, preventing media leakage.
Applications: Examples include controlling cooling water pumps, steam boiler burners, and lubricating oil pressure systems. The switches are adaptable for various configurations, including liquid level control in tanks.
RT 113 Pressure Switch Overview: This document provides technical specifications and installation guidelines for the RT 113 pressure switch, designed for controlling liquid levels in open tanks and managing pressure differentials in various applications.
RT 113 Specifications: The RT 113 pressure switch is suitable for air-absorbing liquids where direct connection is not feasible. It includes a shut-off valve for draining impurities and a filling connector for fresh water. Installation options include using an air bell or connecting to the side of the tank with the switch above the liquid level. Pressure switches are equipped with an adjustable neutral zone for floating control, allowing for precise management of pressure variations.
Installation Procedures: For air bell installations, the bell should be placed 20-40 mm below the lowest liquid level for control purposes, and 100 mm below the maximum level for indication purposes. Horizontal and vertical tube lengths must be calculated to ensure reliable control, with reference to provided diagrams. Pressure switches must be installed with the low-pressure connection upwards to ensure proper function.
Control and Monitoring: The RT pressure switches can be used for controlling and monitoring pressure differentials, with settings adjusted via a setting knob and range scale. Units with changeover switches (SPDT) and adjustable neutral zones are available, allowing for precise control of differential pressures.
Examples and Applications: Examples include controlling pump operations in pressure boosting plants and maintaining constant differential pressure in heating systems. Specific models like RT 260A and RT 262AL are recommended based on application requirements.
Spare Parts and Accessories: A variety of spare parts and accessories are available, including different types of switches, connectors, and damping coils. Special versions with tamper-proof caps and manual reset options are also offered.
Installation Considerations: Pressure connections should be handled with care to avoid damage, and specific installation positions are recommended to minimize the impact of vibrations. For steam plants, a water-filled loop is recommended to protect the pressure element from high temperatures.
Pressure Switch Connection: The pressure switch should be connected to minimize the impact of pulsations on the pressure element. A damping coil can be used to achieve this. For strongly pulsating media, diaphragm pressure switches such as types KPS 43, KPS 45, and KPS 47 are recommended.
Installation: Key components include the setting knob, range scale, and differential setting disc. Proper installation involves setting the range using the setting knob while reading the scale. For pressure switches with a seal cap, tools are required for adjustments.
Setting: The range is adjusted using the setting knob and scale. For units with a fixed differential, the cut-in and cut-out pressures are predetermined. For adjustable differentials, the front cover must be removed to set the differential disc according to the diaphragm.
Selection of Differential: A suitable differential pressure is crucial for proper plant function. A small differential may cause short running periods and hunting, while a large differential can lead to significant pressure oscillations. Differential scale values serve as a guide.
See more

Catalog excerpts

Pressure switch RT-1

Data sheet Pressure switch RT RT Pressure switches incorporate a pressure controlled, single-pole change over swich where the contact position depends on the pressure in the connection port and the set value. The RT series consists of pressure switches, differential pressure switches and pressure switches for neutral zone regulation, all for general use within the industrial and marine segments. The series also covers safety pressure switches dedicated for steam boiler plants. For installations in which operation is particularly critical from safety and economic points of view, the use of fail-safe pressure switches is recommended. The use of gold-plated contacts is also recommended in such installations, provided operation involves only a few switching cycles or signal currents and voltages. • Simple design • High accuracy • High repeatability • Long operation life time • Available with all major marine approvals • Safety Integrity Level: SIL 2 according to IEC 61508

 Open the catalog to page 1
Pressure switch RT-2

Note: in addition we refer to the certificates, the copies of which can be ordered from Danfoss All RT are: • CE marked in accordance with EN 60947-4/-5 for sale in Europe. • Further, the RT 19, RT 30, RT 35, RT 112 W, RT 33, RT 31 and RT 32 series is CE marked in accordance with PED 2014/68/EU, category IV, safety equipment. Standard pressure switches Pressure switches for steam plant approved by Vd TUV Pressure switches with adjustable neutral zone Differential pressure switches

 Open the catalog to page 2
Pressure switch RT-3

Technical data and code nos. When ordering, please state type and code The type designation number. for the letters below means: A: Unit suitable for ammonia L: Unit with neutral zone Pressure switches RT 113 for manual setting; cover with windows RT 116 for tamper proof; cap and blank cover 4 Supplied with 06 / 010 mm weld nipple. 2) With seal cap. Pressure switches with adjustable neutral zone RT 262 A Differential pressure switch Preferred versions Regulation range 1) Supplied with 06 / 010 mm weld nipple. Differential pressure switches 1) Supplied with 06 / 010 mm nipple. / 2) Non-snap action...

 Open the catalog to page 3
Pressure switch RT-4

Technical data and ordering The designation letters mean: A: Units suitable for ammonia. B: Safety units with external resetW: Units for control purposes. S: Safety units with internal reset Pressure switches for steam plant, PED approved acc. to EN 12953-9 and EN 12922-11

 Open the catalog to page 4
Pressure switch RT-5

Materials in contact with the medium

 Open the catalog to page 5
Pressure switch RT-6

Data sheet | Pressure switch, RT Function Scale setting Mechanical differential Fig. 4. Contact function, setting for rising pressure. a. RT 19, RT 30 and pressure switches with max. reset I.Alarm for rising pressure given at the set range value. When the pressure exceeds the set range value, contacts 1-4 make and contact 1-2 brake. The contacts changeover to their initial position when the pressure falls to the range value minus the differential (see fig. 4). II. Alarm for falling pressure given at the set range value minus the differential. Scale setting Mechanical differential Units with max....

 Open the catalog to page 6
Pressure switch RT-7

Data sheet | Pressure switch, RT Function (continuation) Example I An extra cooling water pump must start if the cooling water pressure falls below 6 bar, and must stop when the pressure exceeds 7 bar. Choose an RT 116 with a range of 1 - 10 bar and an adjustable differential of 0.2 - 1.3 bar. The start pressure of 6 bar must be set on the range scale. The differential must be set as the difference between the stop pressure (7 bar) and the start pressure (6 bar) = 1 bar. According to fig. 3, the differential setting disc must be set on 8. Example 2 The burner on a steam boiler must cut out when...

 Open the catalog to page 7
Pressure switch RT-8

Data sheet | Pressure switch, RT Pressure switches for liquid level control RT 113 The RT 113 pressure switch can be used to control the liquid level in open tanks. Fig. 6 shows in principle, four different types of installation. 1. With air bell (see “Accessories”) For control purpose, the air bell should be installed 20 – 40 mm below the lowest liquid level. In addition, the tube between the RT 113 and the air bell must be absolutely airtight. If only an indication is required, the bell can be placed 100 mm below the max. level. The RT 113 must be set at 0 cm wg and the differential disc on...

 Open the catalog to page 8
Pressure switch RT-9

Data sheet | Pressure switch, RT Application RT-L pressure switches are fitted with a switch with an adjustable neutral zone. This enables the units to be used for floating control. The terminology involved is explained below. Floating control A form of discontinuous control where the correcting element (e.g. valve, damper, or similar) moves towards one extreme position at a rate independent of the magnitude of the error when the error exceeds a definit positive value, and towards the opposite extreme position when the error exceeds a definite negative value. Hunting Periodic variations of the...

 Open the catalog to page 9
Pressure switch RT-10

NZ = NATURALZONE / DEADZONE psig 3 2 10 Range setting Inlet pressure Differential (mechanical differential) corresponds to the least neutral zone setting. Example Together with a VLT® static frequency converter, RT 200L neutral zone pressure switches can be used for the infinite control of a pump in, for example, a pressure boosting plant. In this case, the pump must be up and downregulated at 32 m and 25 m wg. The RT 200L must be set using the setting knob (5) fig. 8 page 9 at 3.5 bar (35 m wg) minus the fixed differential of 0.2 bar. The neutral zone, 35 - 32 = 3 m wg, corresponding to 0.3...

 Open the catalog to page 10
Pressure switch RT-11

Data sheet | Pressure switch, RT Application Control and monitoring of pressure differentials A differential pressure switch is a pressure controlled switch that cuts in and cuts out the current dependent on the pressure differential between the counteracting bellows elements and the set scale value. This unit is also available with an adjustable neutral zone (like the RT-L which is described on page 9. The setting disc (5) becomes accessible when the front cover is removed. The differential pressure is set by turning the disc with a screwdriver while reading the scale (9). For differential pressure...

 Open the catalog to page 11

Archived catalogs

  1. Type EV210A

    10  Pages

  2. Supermarkets

    28  Pages

  3. Optyma™

    60  Pages

  4. Danfoss Link™

    14  Pages

  5. Wind Power

    8  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.