Data sheet Solenoid valves for water shut off and leak detection Solenoid valve range for water leak detection in residential and industrial buildings: • Houses and apartments - Kitchen and bathrooms • Commercial buildings • Industrial buildings Solenoid valves used for shut-off water supply to prevent water damages from leaking systems. y Flow range for water in Kv: 0.7 - 40 m³ / h y Media temperature from 0 – 120 °C y Thread connections: From G 3/8 – G 2 y DN 6 – 50 y Water hammer damped y Built-in filter y Adjustable closing time available
Open the catalog to page 1Data sheet | Solenoid valves for water shut off and leak detection, Types EV220T, EV220W, EV220B, and EV228B EV220T Polymer valve body, NC y WRAS y RoHS Directive 2011/65/EU y - Low Voltage Directive 2014/35/EU - EN60730-1 - EN60730-2-8 (Notified body by Semko) - Pressure Equipment Directive 2014/68/EU y UL recognized Seal material Inlet Outlet G ¾ ext. G ¾ ext. EPDM G ¾ ext. G ¾ ext. EPDM See separate table for AS/AZ coils. ) It is recommended to install a filter in front of the valve. ) In water applications, exercise the valves at least once every 24 hours, meaning change the state of the...
Open the catalog to page 2Data sheet | Solenoid valves for water shut off and leak detection, Types EV220T, EV220W, EV220B, and EV228B Function, NC Coil voltage disconnected (Closed) When voltage is disconnected, the armature spring (2) presses the armature (3) down against the pilot orifice (4). Pressure builds up over the diaphragm (5) via the equalizing orifice (6). The diaphragm closes the main orifice (7) as soon as the pressure over the diaphragm equals the inlet pressure. The valve stays closed for as long as voltage remains disconnected. Description Coil Armature spring Armature Pilot orifice Diaphragm Equalizing...
Open the catalog to page 3Data sheet | Solenoid valves for water shut off and leak detection, Types EV220T, EV220W, EV220B, and EV228B Dimensions and weight ISO 228-1 connection Inlet Outlet G ¾ ext. G ¾ ext. G ¾ ext. G ¾ ext. Mounting angle Capacity diagram Example for water: Capacity for EV220T at a differential pressure of 3 bar: Approx. 7 m3 / h
Open the catalog to page 4Data sheet | Solenoid valves for water shut off and leak detection, Types EV220T, EV220W, EV220B, and EV228B EV220W Brass valve body, NC y WRAS y RoHS Directive 2011/65/EU y - Low Voltage Directive 2014/35/EU - EN60730-1 - EN60730-2-8 y UL recognized Seal material G 3/8 EPDM G 1/2 EPDM G 3/4 EPDM G1 EPDM See separate table for AC/AZ coils ) It is recommended to install a filter in front of the valve. ) In water applications, exercise the valves at least once every 24 hours, meaning change the state of the valve. The valve exercise will minimize the risk of the valve sticking due to calcium carbonate,...
Open the catalog to page 5Data sheet | Solenoid valves for water shut off and leak detection, Types EV220T, EV220W, EV220B, and EV228B Function, NC Coil voltage disconnected (Closed) When voltage is disconnected, the armature spring (2) presses the armature (3) down against the pilot orifice (4). Pressure builds up over the diaphragm (5) via the equalizing orifice (6). The diaphragm closes the main orifice (7) as soon as the pressure over the diaphragm equals the inlet pressure. The valve stays closed for as long as voltage remains disconnected. Description Coil Armature spring Armature Pilot orifice Diaphragm Equalizing...
Open the catalog to page 6Data sheet | Solenoid valves for water shut off and leak detection, Types EV220T, EV220W, EV220B, and EV228B Mounting angle Capacity diagram Example for water: Capacity for EV220W at a differential pressure of 3 bar: Approx. 7 m3 / h
Open the catalog to page 7Data sheet | Solenoid valves for water shut off and leak detection, Types EV220T, EV220W, EV220B, and EV228B y Enclosure: Up to IP65 / NEMA 4 AS/AZ, Compact UL recognised, clip-on coils y Used with EV220T and EV220W y For UL recognised valves y In accordance with: - RoHS Directive 2011/65/EU - Low Voltage Directive 2014/35/EU - EN60730-1 - EN60730-2-8 y UL recognized Supply voltage Technical data Design Insulation of coil windings Connection Enclosure, IEC 529 Plug type In accordance with UL 429 Class H according to IEC 85 Spade connector in accordance with DIN 43650 form A IP00 with DIN spade...
Open the catalog to page 8Data sheet | Solenoid valves for water shut off and leak detection, Types EV220T, EV220W, EV220B, and EV228B EV220B 6 - EV220B 12 Brass valve body, NO y WRAS y ACS y PZH y In accordance with: - Low Voltage Directive 2014/35/EU - EN60730-1 - EN60730-2-8 - Pressure Equipment Directive 2014/68/EU y UL recognized Seal material EPDM EPDM Kv Media Max working Differential value temperature pressure pressure [m³/h] [°C] [Bar] [Bar] 0.7 0 – 100 20 0.1 – 10 2.1 0 – 100 10 0.3 – 10 ) It is recommended to install a filter in front of the valve. ) In water applications, exercise the valves at least once...
Open the catalog to page 9Data sheet | Solenoid valves for water shut off and leak detection, Types EV220T, EV220W, EV220B, and EV228B EV220B 6 - EV220B 12 DZR Brass valve body, NO y WRAS y In accordance with: - Low Voltage Directive 2014/35/EU - EN60730-1 - EN60730-2-8 - Pressure Equipment Directive 2014/68/EU y UL recognized Seal material EPDM EPDM Kv Media Max working Differential value temperature pressure pressure [m³/h] [°C] [Bar] [Bar] 0.7 0 – 100 20 0.1 – 10 2.1 0 – 100 10 0.3 – 10 ) It is recommended to install a filter in front of the valve. ) In water applications, exercise the valves at least once every 24...
Open the catalog to page 10Data sheet | Solenoid valves for water shut off and leak detection, Types EV220T, EV220W, EV220B, and EV228B Function, NO Coil voltage disconnected (open): When the voltage to the coil (8) is disconnected, the pilot orifice (6) is open. As the pilot orifice is larger than the equalizing orifice (4), the pressure across the diaphragm (7) drops and therefore it is lifted clear of the main orifice (5). The valve will be open for as long as the minimum differential pressure across the valve is maintained, and for as long as the voltage to the coil is disconnected. Description Armature Opening spring...
Open the catalog to page 1121 Pages
11 Pages
17 Pages
6 Pages
8 Pages
7 Pages
14 Pages
12 Pages
22 Pages
40 Pages
48 Pages
22 Pages
60 Pages
28 Pages
12 Pages
4 Pages
2 Pages
4 Pages
68 Pages
2 Pages
2 Pages
44 Pages
10 Pages
12 Pages
12 Pages
12 Pages
2 Pages
2 Pages
5 Pages
46 Pages
171 Pages