Data Sheet Solenoid valve Type EV310B Direct-operated 3/2-way solenoid valves for universal use EV310B covers a wide range of direct-operated 3/2-way solenoid valves for universal use. EV310B is a real robust valve program with high performance and can be used in all kind of tough working conditions. Clip-on coils can not be used on EV310B. Features • For water, oil, compressed air and similar neutral media • Screw on coil • Ambient temperature: Up to 40 °C • Coil enclosure (cable plug): Up to IP67 • Viscosity: Up to 50 cSt
Open the catalog to page 1Solenoid valve, type EV310B 1 Portfolio overview Table 1: Portfolio overview Features Body material Sealing material Kv [m3/h] Differential pressure range [bar] © Danfoss | Climate Solutions | 2021.06
Open the catalog to page 2Solenoid valve, type EV310B 2 Functions 2.1 Function, NC Coil voltage disconnected (closed): When the voltage to the coil is disconnected, the armature with the valve plates is pressed down by the closing spring and closes the connection between P and A. At the same time, the connection between ports A and R is opened. The connection between P and A will be closed for as long as the voltage to the coil is disconnected. Coil voltage connected (open): When voltage is applied, the armature with the valve plates is lifted and closes the connection between A and R. At the same time, the connection...
Open the catalog to page 3Solenoid valve, type EV310B The connection between P and A will be closed for as long as there is voltage to the coil. 1 2 Armature Opening spring Valve plate Application port (stamped: 2) Relief port (stamped: 3) 2.3 Function, NC FL MAN Coil voltage disconnected (open): When the voltage to the coil is disconnected, the armature, with the valve plates, is pressed down by the closing spring and closes the connection between P and A. At the same time, the connection between ports A and R is opened. The connection between P and A will be closed for as long as the voltage to the coil is disconnected....
Open the catalog to page 4Solenoid valve, type EV310B 1 2 Closing spring Valve plate Pressure port (stamped: 1) Application port (stamped: 2) © Danfoss | Climate Solutions | 2021.06
Open the catalog to page 5Solenoid valve, type EV310B 3 Applications It is recommended to use a filter in front of the valve. Recommended filter 50 mesh (297 microns). Figure 1: Filter In water applications, exercise the valves at least once every 24 hours, meaning change the state of the valve. The valve exercise will minimize the risk of the valve sticking due to calcium carbonate, zinc or iron oxide build-up. Figure 2: Exercise: Valve on/off To minimize scaling, and corrosion attack it is recommended that the water passing the valve have the following values: • Hardness 6 - 18 °dH to avoid scaling (chalk / lime stone...
Open the catalog to page 6Solenoid valve, type EV310B 4 Product specification 4.1 Technical data Table 2: Technical data Media For water, oil, compressed air and similar neutral media Min. Opening differential pressure [bar] Max. Opening differential pressure [bar] Differential pressure range Table 3: Differential pressure range Connection ISO228/1 Orifice size Time to open/close Table 4: Time to open/close Main type EV310B NC/NO/NC MAN/NO MAN/NC FL MAN Materials Table 5: Materials Components Valve body Stainless steel Armature tube Stainless steel Armature stop Stainless steel Stainless steel Seal material © Danfoss...
Open the catalog to page 7Solenoid valve, type EV310B 4.2 Dimension and weight Figure 3: Dimension and weight NC / NO / NC MAN / NO MAN Weight without coil 0.220 kg Figure 4: Dimension and weight NC FL MAN Weight without coil : 0.185 kg Pressure port Application port Relief port © Danfoss | Climate Solutions | 2021.06
Open the catalog to page 8Solenoid valve, type EV310B 4.3 Mounting Figure 5: Mounting angle © Danfoss | Climate Solutions | 2021.06
Open the catalog to page 9Solenoid valve, type EV310B 5 Ordering 5.1 Parts program Table 6: Brass, valve body NC, NO, NC MAN, NO MAN, NC FL MAN Orifice 5.2 Accessories Coil Table 7: Below coil can be used with EV310B Coil Power consumption IP00 with spade connector IP20 with protective cap, IP67 with cable plug Cable plug Figure 6: Cable plug Table 8: Cable plug Cable plug size © Danfoss | Climate Solutions | 2021.06
Open the catalog to page 10Solenoid valve, type EV310B Universal electronic multi-timer, type ET20M Figure 7: ET20M Suitable for coil types Code number Spare parts kit Table 9: Actuator kit, NC and NO Actuator kit Type EV310B 2 1. Armature with mounted spring 2. O-ring © Danfoss | Climate Solutions | 2021.06
Open the catalog to page 116 Online support Danfoss offers a wide range of support along with our products, including digital product information, software, mobile apps, and expert guidance. See the possibilities below. The Danfoss Product Store The Danfoss Product Store is your one-stop shop for everything product related—no matter where you are in the world or what area of the cooling industry you work in. Get quick access to essential information like product specs, code numbers, technical documentation, certifications, accessories, and more. Start browsing at store.danfoss.com. Find technical documentation Find the...
Open the catalog to page 1221 Pages
11 Pages
17 Pages
6 Pages
8 Pages
7 Pages
14 Pages
12 Pages
22 Pages
40 Pages
48 Pages
22 Pages
60 Pages
28 Pages
12 Pages
4 Pages
2 Pages
4 Pages
68 Pages
2 Pages
2 Pages
44 Pages
10 Pages
12 Pages
12 Pages
12 Pages
2 Pages
2 Pages
5 Pages
46 Pages
171 Pages