Data sheet Servo-operated 2/2-way solenoid valves Type EV220B 65 - EV220B 100 EV220B 65 - EV220B 100 is a 2/2-way solenoid valve program for use in robust industrial applications, demanding high flow rates. The valve is designed with cast iron valve body and flanged connection. Water-hammer damped design and built-in pilot filter ensures a reliable operation. y For water and similar neutral media y Flow range for water KV: 50 - 130 m³/h y Water hammer damped y Built-in filter for protection of pilot system y Seal material: EPDM and NBR y Viscosity: Up to 50 cSt y Coil enclosure: Up to IP67

Open the catalog to page 1
Servo-operated 2/2-way solenoid valves Type EV220B 65 - EV220B 100 - 2

Data sheet | Solenoid valves, type EV220B 65 - EV220B 100 EV220B 65-100 Valve body with flange connection Seal material Orifice kv - value size [m³/ h] [mm] Code number ) It is recommended to use filter in front of the valve. Recommended filter 50 mesh (297 microns). ) n water applications, exercise the valves at least once every 24 hours, meaning change the state of the valve. The valve exercise I will minimize the risk of the valve sticking due to calcium carbonate, zinc or iron oxide build-up. 3 ) To minimize scaling, and corrosion attack it is recommended that the water passing the...

Open the catalog to page 2
Servo-operated 2/2-way solenoid valves Type EV220B 65 - EV220B 100 - 3

Data sheet | Solenoid valves, type EV220B 65 - EV220B 100 Function 1. Armature 2. Closing spring in pilot system 3. Valve plate 4. Pilot orifice 5. Servo piston 6. Main orifice 7. Coil 8. Equalizing orifice Coil voltage disconnected (closed): When the voltage is disconnected, the valve plate (3) is pressed down against the pilot orifice (4) by the pilot system’s closing spring (2). The pressure across the servo piston (5) is built up via the equalizing orifice (8). The servo piston closes the main orifice (6) as soon as the pressure across the piston is equivalent to the inlet pressure. The...

Open the catalog to page 3
Servo-operated 2/2-way solenoid valves Type EV220B 65 - EV220B 100 - 4

Data sheet | Solenoid valves, type EV220B 65 - EV220B 100 Below coils can be used with EV220B Coil Power consumption IP00 with spade connector IP20 with protective cap, IP65 with cable plug Accessories: Cable plug Application GDM 2011 (grey) cable plug according to DIN 43650-A PG11 Code number 2 1/2 weld type 11 according to DIN EN 1092-1 4 weld type 11 according to DIN EN 1092-1 Manuel override kit, hand operated 3 weld type 11 according to DIN EN 1092-1 Seal material EPDM Code number Manuel override kit. used for manuel overrride in event of power failure.] Note: Valve height is increased...

Open the catalog to page 4
Servo-operated 2/2-way solenoid valves Type EV220B 65 - EV220B 100 - 5

Data sheet | Solenoid valves, type EV220B 65 - EV220B 100 Dimensions and weight L [mm] Weight without coil [kg] Required min. inside tube diameter d** (mm) *Avoid closing problems caused by turbulent flow it is required to have a straight tube on both sides of the valve. ** Required to keep same tube size for entire application, same or bigger inside diameter as valve orifice 65 / 80 / 100 mm Mounting angle

Open the catalog to page 5
Servo-operated 2/2-way solenoid valves Type EV220B 65 - EV220B 100 - 6

Data sheet | Solenoid valves, type EV220B 65 - EV220B 100 Application diagram Water supply Part Filter Ball valve, Water supply Ball valve, Test reservior Ball valve, Application Test reservoir Capacity diagram for EV220B 65 - 100 Example, water: Capacity for EV220B 65 at differential pressure of 4 bar: Approx. 100 m³/h Recommended operating range: Grey area 1-6 bar differential pressure.

Open the catalog to page 6
Servo-operated 2/2-way solenoid valves Type EV220B 65 - EV220B 100 - 7

Data sheet | Solenoid valves, type EV220B 65 - EV220B 100 Periodic maintenance/inspection Maintenance/Inspection every 6 to 12 months recommended. Before starting maintenance/inspection be sure: - Coil is not energized when removed from the armature tube. - System/solenoid valve is not pressurerised. Eventually close ball valves on each side of the valve. – Be sure any pumps one the upstream (inlet supply) will not be energized or a pressure sensor or switch will not start the pump. - After cleaning and service, eventually with Danfoss spare part kit, it is recommended to lubricate piston...

Open the catalog to page 7
Servo-operated 2/2-way solenoid valves Type EV220B 65 - EV220B 100 - 8

Spare part kit EPDM 016D0078 016D0079 016D0080 1. Armature +Spring 2. 2x O-ring 3. O-ring 4. Piston 5. O-ring 1. Steam gasket 2. 2x Sealing 3. Sealing 4. O-ring 5. Rubber gasket 6. O-ring 7. O-ring 8. 2x Steam gasket 9. O-ring 10. O-ring 11. Filter holder 12. Orifice 13. Filter 14. Drain plug For detailed guidance see installation guides for EV220B 65-100 valve, spare part kit and seal kit