UNI EN 12845 FIRE-FIGHTING SETS
16Pages

{{requestButtons}}

Catalog excerpts

UNI EN 12845 FIRE-FIGHTING SETS - 3

With over 2 million items produced every year, DAB electric pumps are synonym of technology and reliability. Established in 1975, DAB PUMPS is today an international point of reference in the water movement sector. The careful selection of materials and the approval procedures applied to each line before production release, ensure both product resistance and maximum performance levels. During the last years DAB has invested resources, passion and energy, acquiring companies with different specific skills, from electronics to motors. All this has allowed us to present ourselves as a solid...

Open the catalog to page 3
UNI EN 12845 FIRE-FIGHTING SETS - 4

UNI EN 12845 FIRE-FIGHTING SETS WITH STANDARDISED CENTRIFUGAL PUMPS Diesel and electric motor fire-fighting sets, ideal for automatic sprinkler systems and/or hydrants of commercial buildings. Designed to be coupled with each other, in order to obtain all the versions and meet all the requirements of the EN 12845 and UNI 10779 standards. By means of a elastic spacer coupling, the pump is coupled to an electric (efficiency level IE3) or Diesel motor capable of providing the power absorbed by the pump at any pump load condition, from no-load, to a load corresponding to NPSH16m (as requested...

Open the catalog to page 4
UNI EN 12845 FIRE-FIGHTING SETS - 5

FRAME Compact steel frame painted RAL 3000 red to support the pump, with anti-vibration devices to dampen the vibrations transmitted to the system. BATTERIES MAINTENANCE COLLECTION RESERVOIR Batteries and sensitive components are in front of the fire-fighting set, making their maintenance simpler. Reservoir for the collection of any fuel leaking out of the diesel tank, included up to 11kW, pursuant to UNI 11292. TANK All the engine-drive pumps have a fuel pump sized to ensure 6 hours of operation, as required for the highest hazard classes pursuant to standard EN12845 - 10.9.6. ALARM REMOTE...

Open the catalog to page 5
UNI EN 12845 FIRE-FIGHTING SETS - 6

DAB can offer the widest range of fire-fighting sets available on the market. With flow rates up to 650 m3/h and heads up to 130 m. EXTENSIVE RANGE PERFORMANCE OF THE 1KDN H m 150 120 OVERSIZE KDN RANGE FLOW: UP TO 650 m3/h HEAD: UP TO 130 m. RANGE OF STANDARD VERSIONS OF THE KDN FLOW: UP TO 400 m3/h HEAD: UP TO 120 m.

Open the catalog to page 6
UNI EN 12845 FIRE-FIGHTING SETS - 8

EXAMPLES OF INSTALLATION WITH 1KVT FLOODED SUCTION INSTALLATION Standard EN12845 recommends the use of vertical turbine pumps when flooded suction installation with endsuction horizontal pumps is not possible. Vertical turbine pumps offer the great advantage, in fact, of flooded suction installation even with an underground tank. Thanks to the submersible pump body and the motor assembly control above the surface, they eliminate any self-priming issues, in addition to making the job of the maintenance technician much easier

Open the catalog to page 8
UNI EN 12845 FIRE-FIGHTING SETS - 9

TANK Each diesel engine driven pump has a diesel tank that guarantees 6 hours of operation. For engine powers up to 26 kW, a collection tank is also included (in compliance with UNI 11292), for the containment of any fuel spillages. VERTICAL TURBINE PUMP DIESEL MODULE COUPLING KIT In order to obtain all the versions contemplated by the standard (2-3 pump sets), DAB supplies as accessory a coupling kit, to be fitted between the delivery manifolds of the individual sets. ELECTRIC MODULE Vertical turbine pumps offer the great advantage of flooded suction installation even with an underground...

Open the catalog to page 9
UNI EN 12845 FIRE-FIGHTING SETS - 10

DAB can offer the widest range of fire-fighting sets available on the market. With flow rates up to 300 m3/h and heads up to 150 m. EXTENSIVE RANGE PERFORMANCE OF THE 1KVT 0 H kPa 1KVT RANGE FLOW: UP TO 300 m3/h HEAD: UP TO 150 m.

Open the catalog to page 10
UNI EN 12845 FIRE-FIGHTING SETS - 11

oo NOT WOKK UNMH I Mr TAM * NOT MCCMANKAII y fllOCKI "•rEHl! 501 r° °UW,A » NC*f 8>0CCAIAMECCAhKAWN

Open the catalog to page 11
UNI EN 12845 FIRE-FIGHTING SETS - 12

By selecting DAB Pumps as your partner, you will have the confidence of obtaining fire-fighting systems that meet the highest quality standards. Our sets meet the requirements of the UNI EN 12845 standard and are capable of ensuring high reliability and safety. As a further guarantee, in 2014 we asked an External Certifying Body, Istituto Giordano, renowned for its knowledge of the fire-fighting sector, to carry out a "technical assessment of conformity to the specifications of the UNI EN 12845 standard", which enables us to obtain the Certification, and the certainty of offering to our...

Open the catalog to page 12
UNI EN 12845 FIRE-FIGHTING SETS - 13

DAB guarantees quick and safe deliveries of its sets. Handling at the place of installation is managed with the same level of accuracy and efficiency, to ensure an installation process without risks for the operators. The care of each detail also makes the installation very simple: the DAB sets are in fact Ready-to-install, as they are already complete with all the necessary components to ensure the best installation experience. DAB holds a full spare parts warehouse, capable of promptly meeting the requests of its customers. Thanks to full availability of spare parts and accessories,...

Open the catalog to page 13
UNI EN 12845 FIRE-FIGHTING SETS - 14

PUMPING SYSTEMS FOR THE OBI – BURGER KING BUSINESS PARK THE REQUEST: The new "business park" covers about 7,000 square metres in the province of Milan and consists of an OBI store and a Burger King restaurant. DAB supplied pumping sets, including: - 450 m3/h sprinkler fire-fighting system with a set consisting of two diesel pumps and one electric pump. FIRE-FIGHTING SET FOR GRASSI HOSPITAL IN OSTIA THE APPLICATION: Following the renovation of Ostia Hospital, the fire-fighting set was replaced with a DAB set consisting of an electric pump, a jockey pump and a diesel engine-driven pump,...

Open the catalog to page 14
UNI EN 12845 FIRE-FIGHTING SETS - 15

A FIRE-FIGHTING SET FOR THE NEW PREMISES OF ABIDJAN BANQUE IN COTE D'IVOIRE THE APPLICATION: BDA is a subsidiary of Société Ivoirienne des Finances (SIF), created by the Post Office of Cote d'Ivoire and the BDK Group. BDA currently provides services for businesses, large companies and high end customers. A fire-fighting set, consisting of a KDN diesel pump, a KDN electric supply pump and a jockey pump, was installed at the new premises of DBA. TWO FIRE-FIGHTING SETS FOR BRICOMAN IN FERRARA, ITALY THE APPLICATION: Bricoman opened its first store in France in 1999 and can now be found in 4...

Open the catalog to page 15

All DAB catalogs and technical brochures

  1. AC 65-80-110

    2 Pages

  2. MCE/C

    5 Pages

  3. MCE/P

    5 Pages

  4. ADAC

    4 Pages

  5. E-BOX

    1 Pages

  6. SMART PRESS

    1 Pages