FT90 Bid Submittal

FT90 Bid Submittal
1 / 13 PagesView full catalog

FT90 Bid Submittal

Product catalog summary
Product Overview
The Eaton EPCT Fire is a touchscreen-based electric fire pump controller that integrates fire pump controller (FPC) and automatic transfer switch (ATS) functionalities into a single 7-inch color display. It is designed to expedite commissioning and simplify troubleshooting with on-screen history filtering and diagnostic monitoring. The controllers support various starting methods, including full-voltage and reduced voltage options.
Key Features
  • Touchscreen Display: A 7-inch touchscreen facilitates easy programming, viewing of critical system information, and troubleshooting.
  • Automatic Transfer Switch Integration: Combines FPC and ATS into one display for streamlined management.
  • Commissioning Simplified: Features a Startup tab for quick setup and testing tasks.
  • UL Type Rating: The display is UL type 4X rated.
Programming Menu
  • Startup Tab: Guides users through commissioning tasks.
  • Panel Setup Tab: Manages panel variables like language and voltage.
  • Help Tab: Provides service contact information and a QR code for manual download.
  • Pressure Settings Tab: Allows programming of pressure-related settings.
  • Timer Values Tab: Contains programming points for fire pump controller timers.
  • ATS Settings Tab: Enabled for units with an ATS, for transfer switch operation.
  • Alarm Setpoints Tab: Includes seven programmable alarm points.
  • Inputs/Outputs Tab: Supports custom inputs and outputs for various conditions.
  • History/Statistics/Diagnostics Tab: Provides access to historical data and diagnostics.
I/O Board
  • Power Supply: Accepts voltage inputs between 200-600VAC three-phase or 240VAC single-phase.
  • Customer Input Connections: Terminals for external connections programmable via the touchscreen.
  • Output Relays: Features relays for common alarms and power/phase failures.
  • Optional Boards: Supports additional boards for expanded functionality.
Additional Components
  • Drain Valve Solenoid: Used for motor tests.
  • External USB Port: Allows data download to USB devices.
  • Enclosures: Standard with UL type 2 enclosures, with optional types available.
  • Emergency Start Operator: Mechanically activates motor contactors independently.
Standards & Certifications
The controllers meet or exceed standards from UL, FM, CSA, and others, and comply with NFPA 20 standards.
Specifications Overview
  • Approvals: Complies with NFPA 20 and other standards.
  • Starting Type: Supports multiple starting methods.
  • Ratings: Withstand rating of 100,000 RMS symmetrical amperes.
  • Construction: Includes motor-rated combination isolating switch and circuit breaker.
  • Enclosure: Available in various types, including watertight and dust-tight options.
  • Microprocessor Control: Features a 7-inch touchscreen with various system displays and statistics.
Specifications and Features
  • The document outlines the specifications for a fire pump controller manufactured by Eaton Corporation. It includes various voltage and frequency parameters for S1 and S2 systems, such as minimum and maximum voltages and frequencies.
  • Controller diagnostics include serial numbers, firmware versions, supply voltage, and communication capabilities. It also provides details on secondary amperage and transducer inputs/outputs.
  • The controller features a microprocessor logic board with a USB port for data transfer and firmware updates. It includes alarms for fail-to-start and locked rotor protection, with display indications for voltage, current, and trip conditions.
  • Standard features include a sequential start timer, weekly test timer, and a restart time delay to manage motor voltage decay. Overvoltage and undervoltage sensing and alarming are also standard.
  • Interlock and shutdown circuits are included, with LED indicators for interlock conditions. Low suction pressure shutdowns are managed without additional panels, with automatic or manual reset options.
Programming and Customization
  • The programming menu supports password protection and is available in nine languages. It is organized into ten tabs, including Home, Startup, Panel Setup, and more.
  • A solid-state 4-20mA pressure sensor is provided, with adjustable start and stop points in 1 PSI increments.
  • The controller includes ten programmable inputs and four programmed outputs, with options to add more outputs via relay boards. Inputs and outputs are customizable based on user-selected messages, alarms, and timers.
Alarm and Relay Systems
  • All relays are soldered on the PCB, with LED indicators for energized states. Relay contacts are rated at 8A, 277VAC/30VDC, with Form-C contacts for common alarms and power/phase failures.
  • An audible alarm buzzer is included for fail-to-start, hardware malfunctions, or common alarm conditions.
Manufacturer Information
  • The controller is identified as the EPCT Fire type, manufactured by Eaton Corporation, with contact details provided for Canadian operations.
See more

Catalog excerpts

FT90 Bid Submittal-1

Touchscreen based electric fire pump controllers Powering Business Worldwide

 Open the catalog to page 1
FT90 Bid Submittal-2

Product Description The EPCT Fire features an advanced, 7" color touchscreen that incorporates both the fire pump controller (FPC) and automatic transfer switch (ATS) functionality into one, intuitive display. Designed solely with the consumer in mind, the EPCT Fire enables technicians to commission the fire pump controller faster; troubleshooting is made easier and is more effective through the use on-screen history filtering and diagnostic monitoring. All full-service fire pump controllers can be offered in either full-voltage or reduced voltages starting methods: • FD/FT20 - Limited service...

 Open the catalog to page 2
FT90 Bid Submittal-3

Other Components Emergency Start Operator Drain Valve Solenoid A mechanically operated emergency start handle (ESH) will mechanically activate the motor contactor(s) independently from any electrical control circuits. All full-service EPCT Fire controllers are equipped with a drain valve solenoid used for manual or automatic motor tests. External USB Port Standards & Certifications The USB port allows the user to download historical messages, statistics, diagnostic information, startup file, and current controller configuration to any USB device with FAT16 or FAT 32 formatting. All EPCT Fire...

 Open the catalog to page 3
FT90 Bid Submittal-4

Withstand Ratings Starting Method Starting Limited Service Part Winding Primary Resistor WYE-Delta (Star-Delta) Open Transition WYE-Delta (Star-Delta) Closed Transition Soft Start Starting Staring Motor Voltage HP Short Circuit Current Torque Connections Withstand Rating F;T*I\I Powering Business Worldwide Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Electrical Sector Canadian Operations 5050 Mainway Burlington, ON L7L 5Z1 Canada EatonCanada.ca CHFire.com © 2018 Eaton All Rights Reserved Printed in Canada Publication No. BR124053EN / 001 January 2018 Eaton is a registered...

 Open the catalog to page 4
FT90 Bid Submittal-5

EPCT FIRE - FT90 SMALL HP DIMENSIONAL DRAWING - TYPE 2, 3, 3R, 4, 4X, 12 1 - EPCT TOUCHSCREEN 2 - EXTERNAL USB PORT 3 - SOURCE 1 POWER SWITCH 4 - SOURCE 2 POWER SWITCH 5 - START PUSHBUTTON 6 - STOP PUSHBUTTON 7 - MSH (EMERGENCY START HANDLE) 8 - RECOMMENDED CABLE ACCESS (BOTTOM ONLY) NOTES: 1 - DIMENSIONS: in [mm] 2 - ALL ENCLOSURES FINISHED IN RED 3 - STANDARD ENCLOSURE: TYPE (NEMA) 2 PIPING ENTRANCE 1/2" NPT - FEMALE THE INFORMATION ON THIS DOCUMENT IS CREATED BY EATON. IT IS DISCLOSED IN CONFIDENCE AND IS ONLY TO BE USED FOR THE PURPOSE IN WHICH IT IS SUPPLIED. LES RENSEIGNEMENTS CI-DESSUS...

 Open the catalog to page 5
FT90 Bid Submittal-6

EPCT FIRE - FT90 LARGE HP DIMENSIONAL DRAWING - TYPE 2, 3, 3R, 4, 4X, 12 1 - EPCT TOUCHSCREEN 2 - EXTERNAL USB PORT 3 - SOURCE 1MAIN POWER SWITCH 4 - SOURCE 2 MAIN POWER SWITCH 5 - START PUSHBUTTON 6 - STOP PUSHBUTTON 7 - MSH (EMERGENCY START HANDLE) 8 - RECOMMENDED CABLE ACCESS (BOTTOM ONLY) PIPING ENTRANCE 1/2" NPT - FEMALE PIPING ENTRANCE 1/2" NPT - FEMALE NOTES: 1 - DIMENSIONS: in [mm] 2 - ALL ENCLOSURES FINISHED IN RED 3 - STANDARD ENCLOSURE: TYPE (NEMA) 2 THE INFORMATION ON THIS DOCUMENT IS CREATED BY EATON. IT IS DISCLOSED IN CONFIDENCE AND IS ONLY TO BE USED FOR THE PURPOSE IN WHICH IT...

 Open the catalog to page 6
FT90 Bid Submittal-7

CUSTOMER INPUTS NDTESi 1. PDWER/PHASE FAILURE AND CDMMDN ALARM RELAYS ARE ENERGIZED UNDER NDRMAL CDNDITIDNS. 2. ALL RELAY CONTACTS ARE SHOWN IN NO POWER CONDITION, LEGENDi 9CR - BYPASS RELAY CB - CIRCUIT BREAKER CT - CURRENT TRANSFORMER M - RUN CONTACTOR MIS - MAIN ISOLATING SWITCH MSH - MANUAL START HANDLE (EMERGENCY) MICRO SWITCH STARTUP ACCELERATION COMMON ALARM (NORMALLY ENERGIZED) COMMON ALARM (NORMALLY ENERGIZED) POWER/PHASE FAILURE (NORMALLY ENERGIZED) POWER /PHASE FAILURE (NORMALLY ENERGIZED) PHASE REVERSAL PHASE REVERSAL PUMP RUN PUMP RUN 73 DISPLAY BOARD COMMS LOOPBACK COMMS FAULT CUBE...

 Open the catalog to page 7
FT90 Bid Submittal-8

TO M01 -FROM TERMINAL 53 -SOURCE 2 DISCONNECTED SOURCE 2 DISCONNECTED ENGINE START CONTACTS EA EB EC EMERGENCY SHUNT SOURCE 2 DISCONNECTED^ ATS NORMAL ATS EMERGENCY THE INFORMATION ON THIS DOCUMENT IS CREATED BY EATON. IT IS DISCLOSED IN CONFIDENCE AND IS ONLY TO BE USED FOR THE PURPOSE IN WHICH IT IS SUPPLIED. LES RENSEIGNEMENTS CI-DESSUS ONT ETE £LABORES PAR EATON. ILS VOUS SONT DIVULGUES EN TOUTE CONFIANCE ET LEUR UTILISATION SE LIMITE AUX SEULES FINS POUR LESQUELLES ILS VOUS SONT TRANSMIS.

 Open the catalog to page 8
FT90 Bid Submittal-9

EPCT FIRE - FD/FT90 THREE PHASE FIELD CONNECTIONS Line Terminals Connections Line Voltage Line Lugs Service Ground Lugs (QTY.) & Cable Size per 0 (QTY.) & Cable Size per 0 Load Terminals Connections Line Voltage 200-208 220-240 380-415 440-480 575-600 Single Run Cable Sizes Double Run Cable Sizes For ambient temperatures exceeding 30C (86F), the temperature rating of motor conductors is recommended to be a minimum of 90C (194F) For proper cable size, refer to the National Electric Code (NEC - NFPA70) CONTROLLER CONNECTIONS ALARM CONTACTS CUSTOMER INPUTS COMMON ALARM (NORMALLY ENERGIZED) COMMON...

 Open the catalog to page 9
FT90 Bid Submittal-10

Options B - Alarm Bell Cl - Extra. Contacts "Pump Run" (Two Form-C) C2 - Extra Contacts "AC Power Failure" (Two Form-C) C3 - Extra Contacts "Phase Rev" (Two Form-C) C4 - Remote Contacts (2 Form C) Low Reservoir C5 - Remote Contacts (2 Form C) High Reservoir El - NEMA 3R - Raintight Enclosure E2 - NEMA4-WatertightEnclosure E3 - NEMA 12-Industrial Dust Tight Enclosure E4 - NEMA 3-Watertight Enclosure E5 - NEMA 4X- 304 Stainless Steel Enclosure E8 - Tropicalization E9 - NEMA4X-Painted Steel EIO - NEMA4X-316 Stainless Steel Enclosure EX - Export Crating F2 - Floor Stand -2 Inch Height** H - High...

 Open the catalog to page 10
FT90 Bid Submittal-11

Fire pump controllers Features Effective February 2019 EPCT Fire electric fire pump controllers Typical specifications 1. Approvals A. The Fire Pump Controller shall meet the requirements of the latest edition of NFPA 20 and shall be listed by [Underwriters Laboratories (UL)] and approved by [Factory Mutual Research (FM)] [Canadian Standards Association (CSA)] [New York Department of Buildings (NYSB)] and carry the CE marking for fire pump service. 2. Starting type A. The controller shall be of the combined manual and automatic type designed for [Full Voltage Starting] [Part Winding Starting]...

 Open the catalog to page 11

All Cutler-Hammer catalogs and technical brochures

  1. Fuses

    291  Pages

  2. OEM Product

    334  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.