FDF/FTF20 Bid Submittal (Foam) - 1

Powering Business Worldwide

Open the catalog to page 1
FDF/FTF20 Bid Submittal (Foam) - 2

Product Description The EPCT Fire features an advanced, 7" color touchscreen that incorporates both the fire pump controller (FPC) and automatic transfer switch (ATS) functionality into one, intuitive display. Designed solely with the consumer in mind, the EPCT Fire enables technicians to commission the fire pump controller faster; troubleshooting is made easier and is more effective through the use on-screen history filtering and diagnostic monitoring. All full-service fire pump controllers can be offered in either full-voltage or reduced voltages starting methods: • FD/FT20 - Limited...

Open the catalog to page 2
FDF/FTF20 Bid Submittal (Foam) - 3

Other Components Emergency Start Operator Drain Valve Solenoid A mechanically operated emergency start handle (ESH) will mechanically activate the motor contactor(s) independently from any electrical control circuits. All full-service EPCT Fire controllers are equipped with a drain valve solenoid used for manual or automatic motor tests. External USB Port Standards & Certifications The USB port allows the user to download historical messages, statistics, diagnostic information, startup file, and current controller configuration to any USB device with FAT16 or FAT 32 formatting. All EPCT...

Open the catalog to page 3
FDF/FTF20 Bid Submittal (Foam) - 4

Withstand Ratings Starting Method Starting Limited Service Part Winding Primary Resistor WYE-Delta (Star-Delta) Open Transition WYE-Delta (Star-Delta) Closed Transition Soft Start Starting Staring Motor Voltage HP Short Circuit Current Torque Connections Withstand Rating F;T*I\I Powering Business Worldwide Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Electrical Sector Canadian Operations 5050 Mainway Burlington, ON L7L 5Z1 Canada EatonCanada.ca CHFire.com © 2018 Eaton All Rights Reserved Printed in Canada Publication No. BR124053EN / 001 January 2018 Eaton is a...

Open the catalog to page 4
FDF/FTF20 Bid Submittal (Foam) - 5

1 - EPCT TOUCHSCREEN 2 - EXTERNAL USB PORT 3 - MAIN POWER SWITCH 4 - START PUSHBUTTON 5 - STOP PUSHBUTTON 6 - MSH (EMERGENCY START HANDLE) 7 - RECOMMENDED CABLE ACCESS (BOTTOM ONLY) NOTES: 1 - DIMENSIONS: in [mm] 2 - ALL ENCLOSURES FINISHED IN RED 3 - STANDARD ENCLOSURE: TYPE (NEMA) 2 PIPING ENTRANCE 1/4" NPT FEMALE THE INFORMATION ON THIS DOCUMENT IS CREATED BY EATON. IT IS DISCLOSED IN CONFIDENCE AND IS ONLY TO BE USED FOR THE PURPOSE IN WHICH IT IS SUPPLIED. LES RENSEIGNEMENTS CI-DESSUS ONT ÉTÉ ÉLABORÉS PAR EATON. ILS VOUS SONT DIVULGUÉS EN TOUTE CONFIANCE ET LEUR UTILISATION SE LIMITE...

Open the catalog to page 5
FDF/FTF20 Bid Submittal (Foam) - 6

1 - EPCT TOUCHSCREEN 2 - EXTERNAL USB PORT 3 - SOURCE 1 POWER SWITCH 4 - SOURCE 2 POWER SWITCH 5 - START PUSHBUTTON 6 - STOP PUSHBUTTON 7 - MSH (EMERGENCY START HANDLE) 8 - RECOMMENDED CABLE ACCESS (BOTTOM ONLY) NOTES: 1 - DIMENSIONS: in [mm] 2 - ALL ENCLOSURES FINISHED IN RED 3 - STANDARD ENCLOSURE: TYPE (NEMA) 2 PIPING ENTRANCE 1/4" NPT - FEMALE THE INFORMATION ON THIS DOCUMENT IS CREATED BY EATON. IT IS DISCLOSED IN CONFIDENCE AND IS ONLY TO BE USED FOR THE PURPOSE IN WHICH IT IS SUPPLIED. LES RENSEIGNEMENTS CI-DESSUS ONT ÉTÉ ÉLABORÉS PAR EATON. ILS VOUS SONT DIVULGUÉS EN TOUTE CONFIANCE...

Open the catalog to page 6
FDF/FTF20 Bid Submittal (Foam) - 7

EPCT FIRE - FDF20 THREE PHASE WIRING SCHEMATIC - FOAM (ADDITIVE) VOLTAGE SURGE ARRESTER NDTESi 1. POWER/PHASE FAILURE AND COMMON ALARM RELAYS ARE ENERGIZED UNDER NORMAL CONDITIONS. 2. ALL RELAY CONTACTS ARE SHOWN IN NO POWER CONDITION, LEGENDi CB - CIRCUIT BREAKER CT - CURRENT TRANSFORMER M - RUN CONTACTOR MSH - MANUAL START HANDLE (EMERGENCY) MICRO SWITCH THE INFORMATION ON THIS DOCUMENT IS CREATED BY EATON. IT IS DISCLOSED IN CONFIDENCE AND IS ONLY TO BE USED FOR THE PURPOSE IN WHICH IT IS SUPPLIED. LES RENSEIGNEMENTS CI-DESSUS ONT EtE ELABORES PAR EATON. ILS VOUS SONT DIVULGUES EN TOUTE...

Open the catalog to page 7
FDF/FTF20 Bid Submittal (Foam) - 8

EPCT FIRE - FDF20 SINGLE PHASE WIRING SCHEMATIC - FOAM (ADDITIVE) SEE LOCKED ROTOR TRIP FOR CT RATIO VOLTAGE SURGE ARRESTER NDTESi 1. POWER/PHASE FAILURE AND COMMON ALARM RELAYS ARE ENERGIZED UNDER NORMAL CONDITIONS. 2. ALL RELAY CONTACTS ARE SHOWN IN NO POWER CONDITION, LEGENDi CB - CIRCUIT BREAKER CT - CURRENT TRANSFORMER M - RUN CONTACTOR MSH - MANUAL START HANDLE (EMERGENCY) MICRO SWITCH THE INFORMATION ON THIS DOCUMENT IS CREATED BY EATON. IT IS DISCLOSED IN CONFIDENCE AND IS ONLY TO BE USED FOR THE PURPOSE IN WHICH IT IS SUPPLIED. LES RENSEIGNEMENTS CI-DESSUS ONT EtE ELABORES PAR...

Open the catalog to page 8
FDF/FTF20 Bid Submittal (Foam) - 9

EPCT FIRE - FTF20 THREE PHASE WIRING SCHEMATIC - FOAM (ADDITIVE) ALARM RELAYS ARE ENERGIZED UNDER NORMAL CONDITIONS. 2. ALL RELAY CONTACTS ARE SHOWN IN NO POWER CONDITION, THE INFORMATION ON THIS DOCUMENT IS CREATED BY EATON. IT IS DISCLOSED IN CONFIDENCE AND IS ONLY TO BE USED FOR THE PURPOSE IN WHICH IT IS SUPPLIED. LES RENSEIGNEMENTS CI-DESSUS ONT EtE ELABORES PAR EATON. ILS VOUS SONT DIVULGUES EN TOUTE CONFIANCE ET LEUR UTILISATION SE LIMITE AUX SEULES FINS POUR LESQUELLES ILS VOUS SONT TRANSMIS.

Open the catalog to page 9
FDF/FTF20 Bid Submittal (Foam) - 10

EPCT FIRE - FTF20 SINGLE PHASE WIRING SCHEMATIC - FOAM (ADDITIVE) - «. 3 3 3 a NDTESi 1. POWER/PHASE FAILURE AND CDMMDN ALARM RELAYS ARE ENERGIZED UNDER NDRMAL CDNDITIDNS. 2. ALL RELAY CONTACTS ARE SHOWN IN ND PDWER CDNDITIDN, LEGENDi CB - CIRCUIT BREAKER CT - CURRENT TRANSFORMER M - RUN CONTACTDR MSH - MANUAL START HANDLE (EMERGENCY) MICRO SWITCH STARTUP ACCELERATION COMMON ALARM (NORMALL Y ENERGIZED) COMMON ALARM (NORMALL Y ENERGIZED) POWER/PHASE FAILURE (NORMALL Y ENERGIZED) POWER/PHASE FAILURE (NORMALLY ENERGIZED) PHASE REVERSAL PHASE REVERSAL PUMP RUN PUMP RUN 73 DISPLAY BOARD CDMMS...

Open the catalog to page 10
FDF/FTF20 Bid Submittal (Foam) - 11

TO M01 -FROM TERMINAL 53 -SOURCE 2 DISCONNECTED SOURCE 2 DISCONNECTED ENGINE START CONTACTS EA EB EC EMERGENCY SHUNT SOURCE 2 DISCONNECTED^ ATS NORMAL ATS EMERGENCY THE INFORMATION ON THIS DOCUMENT IS CREATED BY EATON. IT IS DISCLOSED IN CONFIDENCE AND IS ONLY TO BE USED FOR THE PURPOSE IN WHICH IT IS SUPPLIED. LES RENSEIGNEMENTS CI-DESSUS ONT ETE £LABORES PAR EATON. ILS VOUS SONT DIVULGUES EN TOUTE CONFIANCE ET LEUR UTILISATION SE LIMITE AUX SEULES FINS POUR LESQUELLES ILS VOUS SONT TRANSMIS.

Open the catalog to page 11
FDF/FTF20 Bid Submittal (Foam) - 12

TO M01 -FROM TERMINAL 53 -SOURCE 2 DISCONNECTED SOURCE 2 DISCONNECTED ENGINE START CONTACTS EA EB EMERGENCY SHUNT SOURCE 2 DISCONNECTED^ ATS NORMAL ATS EMERGENCY THE INFORMATION ON THIS DOCUMENT IS CREATED BY EATON. IT IS DISCLOSED IN CONFIDENCE AND IS ONLY TO BE USED FOR THE PURPOSE IN WHICH IT IS SUPPLIED. LES RENSEIGNEMENTS CI-DESSUS ONT ETE £LABORES PAR EATON. ILS VOUS SONT DIVULGUES EN TOUTE CONFIANCE ET LEUR UTILISATION SE LIMITE AUX SEULES FINS POUR LESQUELLES ILS VOUS SONT TRANSMIS.