FD70 WYE DELTA (STAR-DELTA) OPEN

FD70 WYE DELTA (STAR-DELTA) OPEN

FD70 WYE DELTA (STAR-DELTA) OPEN

Product catalog summary
Product Description
The LMR Plus Electric Fire Pump Controllers, specifically the FD70 model, utilize a Wye-Delta (Star-Delta) open transition method to reduce motor starting current. This method ensures 100% starting torque efficiency and can be set for automatic or semi-automatic operation. The controllers feature embedded web pages for diagnostics and history retrieval, USB and Ethernet ports for data transfer, enhancing troubleshooting and maintenance.

Product Features
The controllers include a membrane keypad with NEMA ratings (2, 3R, 4, 4X, 12) and 20 LED indicators for alarms and status. Communication options include Ethernet, RS485, and USB ports. The power I/O board supports voltage inputs from 100 to 600V and includes five standard output relays, with optional expansion for additional relays. A drain valve solenoid is included for testing, and a silence button is available for alarm management.

Standards & Certification
The controllers comply with standards from Underwriters Laboratories, Factory Mutual, Canadian Standards Association, and meet NFPA 20 standards. They are also approved for seismic qualifications and New York City building codes.

System Configuration & Programming
The system configuration menu is password-protected, allowing settings for voltage, frequency, and more. The main display shows system pressure, voltage, and alarms. Users can program set points, view statistics, and access diagnostics. The embedded web page provides access to current status, readings, and history.

Custom Messages & Firmware
Custom messages can be programmed to trigger at specific points and displayed on the LCD. Firmware updates are managed via USB, retaining previous settings in case of failure.

Programming Menu
The programming menu includes sub-menus for language, regional settings, pressure, timers, alarm set points, and custom inputs/outputs. Users can program various pressure settings, timers, and alarm points, with options for custom input/output configurations.
See more

Catalog excerpts

FD70 WYE DELTA (STAR-DELTA) OPEN-1

LMR PLUS Electric Fire Pump Controllers Powering Business Worldwide FD70 Reduced Voltage - Wye Delta (Star-Delta) Open Transition Product Description The FD70 LMR Plus Controllers use a method of connecting the pump motor windings into wye configuration to start, then switching to a This reduces the starting current of the motor Wye-Delta starting is the only method that has a starting torque efficiency of 100%. The FD70 can be programmed for either fully automatic or semi-automatic operations. retrieving diagnostics and history reports, along with USB and Ethernet communication ports for downloading data, make the LMR Plus Series of controllers easy to troubleshoot and maintain. As well, critical information can be easily accessed and used for report generation and analysis, which aids in providing effective, reliable fire protection. Product Features Logic Controller Board The controller can be ordered with the option to display and output current values and status, on command, from various software protocols through the appropriate port(s). The web page is a multifunction tool that allows the user to view the controller's current status, data values, programmed set points and history. It is accessed using the optional ethernet port. Ethernet Port An optional Ethernet port can be used for direct connection to a computer for data transfer. An optional RS485 serial port can be provided for communication to various external software The logic controller board is equipped with a USB port that can be used to transfer data to and from a portable USB Drive device (memory A buzzer is mounted on the logic board which will operate if Fail to Start, Hardware Malfunction or any Common Alarm condition Incoming line voltage is run directly to the I/O board from the incoming lines. The I/O board will accept voltage inputs between 100 and Customer Connection Terminals Connection terminals for external customer connections, are located at the top of the Power Output Relays Five, 8 Amp, 2 Form - C (DPDT) output relays are provided standard on each power I/O board. They are designated for: Common Alarm, Phase Failure, Phase Reversal, Pump Run and Future #1. Each socket has an LED mounted on the I/O board which indicates each relay's coil Optional Output Relay Boards There is provision to add up to eight additional relay outputs, via optional relay output boards. Each board contains a maximum of 2 additional relays. The Power I/O Board will accept a maximum of 4 optional boards which mount in a snap-on configuration. Each board provides an area for the user to label the terminal number and relay name. Drain Valve Solenoid All LMR Plus electric controllers are equipped with a drain valve solenoid used for weekly test When using an external USB Drive, the drive should conform to the following specifications: All LMR controllers come standard with NEMA 2 enclosures unless otherwise ordered. Available Emergency Start Operator emergency start handle switch input. Membrane Keypad Door Mount The membrane keypad is accessible from the front door of the controller. NEMA Rating The standard membrane keypad is rated for Alarm & Status LED's A total of 20,(10 Status -10 Alarm ) LED's provide indication on the membrane keypad. Status LED's Pump Running Local Start Remote Start Deluge Valve Emergency Start Auto Shutdown Enabled Alarm LED's Phase Reversal Phase Failure Locked Rotor Trip Silence Button A silence pushbutton on the membrane can be used to silence the buzzer. When an alarm condition exists, the alarm buzzer will sound. If the Silence Alarm button is pressed, the alarm buzzer will turn off. If a subsequent alarm condition occurs after the silence button is pressed, the buzzer will re-sound. Pressing the Silence Alarm button again, will silence the Motor Test Button The motor test button on the membrane can be used to simulate an automatic start. Automatic Shutdown Enabled When the Automatic Shutdown function is enabled, a Green LED will indicate on the controller membrane. Standards & Certification The LMR Plus Electric Fire Pump Controllers meet or exceed the requirements of Underwriters Laboratories, Underwriters Laboratories Canada, Factory Mutual, the Canadian Standards Association, New York City building code, CE mark and U.B.C / C.B.C. Seismic requirements, and are built to NFPA20 For more information visit: www.chfire.com

 Open the catalog to page 1
FD70 WYE DELTA (STAR-DELTA) OPEN-2

LMR PLUS Electric Fire Pump Controllers Powering Business Worldwide FD70 Reduced Voltage - Wye Delta (Star-Delta) Open Transition Product Features Main Display The main display will show the current system pressure, time and date, voltage and amps reading for all three phases, the system frequency and any custom messages, alarms Programmed Set-Point The set-point display will show programmed pressure start point, pressure stop point and weekly test timer setting. The statistics display will allow the user to scroll through all of the measured statistics stored in memory. Refer to LMR Plus operation...

 Open the catalog to page 2

All Cutler-Hammer catalogs and technical brochures

  1. Fuses

    291  Pages

  2. OEM Product

    334  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.