1. Catalogs
  2. Cutler-Hammer
  3. Eaton EPCT Fire
video corpo

Eaton EPCT Fire

Eaton EPCT Fire

Eaton EPCT Fire

Product catalog summary
Product Description
The Eaton EPCT Fire is a touchscreen-based electric fire pump controller that integrates both fire pump controller (FPC) and automatic transfer switch (ATS) functionalities into a single 7-inch color display. It is designed to simplify commissioning and troubleshooting with features like on-screen history filtering and diagnostic monitoring. The controllers are available in various starting methods, including full-voltage and reduced voltage options.
Product Features
  • Touchscreen Display: The 7-inch touchscreen allows for easy programming and troubleshooting with an intuitive menu structure.
  • Automatic Transfer Switch Integration: Combines FPC and ATS into one display for streamlined management.
  • Commissioning Simplified: Features a Startup tab for quick setup and testing tasks.
  • UL Type Rating: The display is UL tested and rated type 4X.
Programming Menu
  • Startup Tab: Guides users through commissioning tasks.
  • Panel Setup Tab: Contains settings for language, date, time, and voltage.
  • Help Tab: Provides service contact information and a QR code for manual download.
  • Pressure Settings Tab: Allows programming of pressure-related settings.
  • Timer Values Tab: Contains settings for various timers related to the fire pump controller.
  • ATS Settings Tab: Enabled for units with an ATS, for transfer switch operation settings.
  • Alarm Setpoints Tab: Includes seven programmable alarm points.
  • Inputs/Outputs Tab: Supports custom inputs and outputs for various conditions.
  • History/Statistics/Diagnostics Tab: Provides access to historical data and diagnostics.
I/O Board
  • Power Supply: Accepts voltage inputs between 200-600VAC three-phase or 240VAC single-phase.
  • Customer Input Connections: Terminals for external connections programmable via the touchscreen.
  • Output Relays: Includes four relays for alarms and status indications.
  • Optional Boards: Supports additional boards for expanded functionality.
Other Components
  • Drain Valve Solenoid: Used for motor tests.
  • External USB Port: Allows data download to USB devices.
  • Enclosures: Standard UL type 2 enclosures with optional types available.
  • Emergency Start Operator: Mechanically activates motor contactors independently of electrical circuits.
Standards & Certifications
The EPCT Fire controllers meet or exceed various standards, including UL, Factory Mutual, Canadian Standards Association, and NFPA 20. They are suitable for use as service entrance equipment but do not meet CEC requirements for Canada.
Quick Specification Overview
The document provides detailed specifications for various starting methods, including voltage, current, torque, and short circuit withstand ratings for different motor connections and voltages.
See more

Catalog excerpts

Eaton EPCT Fire-1

Touchscreen based electric fire pump controllers Powering Business Worldwide

 Open the catalog to page 1
Eaton EPCT Fire-2

Product Description The EPCT Fire features an advanced, 7" color touchscreen that incorporates both the fire pump controller (FPC) and automatic transfer switch (ATS) functionality into one, intuitive display. Designed solely with the consumer in mind, the EPCT Fire enables technicians to commission the fire pump controller faster; troubleshooting is made easier and is more effective through the use on-screen history filtering and diagnostic monitoring. All full-service fire pump controllers can be offered in either full-voltage or reduced voltages starting methods: • FD/FT20 - Limited service...

 Open the catalog to page 2
Eaton EPCT Fire-3

Other Components Emergency Start Operator Drain Valve Solenoid A mechanically operated emergency start handle (ESH) will mechanically activate the motor contactor(s) independently from any electrical control circuits. All full-service EPCT Fire controllers are equipped with a drain valve solenoid used for manual or automatic motor tests. External USB Port Standards & Certifications The USB port allows the user to download historical messages, statistics, diagnostic information, startup file, and current controller configuration to any USB device with FAT16 or FAT 32 formatting. All EPCT Fire...

 Open the catalog to page 3
Eaton EPCT Fire-4

Withstand Ratings Starting Method Starting Limited Service Part Winding Primary Resistor WYE-Delta (Star-Delta) Open Transition WYE-Delta (Star-Delta) Closed Transition Soft Start Starting Staring Motor Voltage HP Short Circuit Current Torque Connections Withstand Rating F;T*I\I Powering Business Worldwide Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Electrical Sector Canadian Operations 5050 Mainway Burlington, ON L7L 5Z1 Canada EatonCanada.ca CHFire.com © 2018 Eaton All Rights Reserved Printed in Canada Publication No. BR124053EN / 001 January 2018 Eaton is a registered...

 Open the catalog to page 4

All Cutler-Hammer catalogs and technical brochures

  1. Fuses

    291  Pages

  2. OEM Product

    334  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.