Product catalog summary
Fire Pump Controllers Overview

1. Approvals and Specifications
The Fire Pump Controller is approved by Factory Mutual Research (FM) and listed by Underwriters, Canadian Standards Association, and New York Department of Buildings for fire pump service. It operates on a 12 or 24-volt negative ground system compatible with diesel engines.

2. Construction Features
All components are front-mounted for easy inspection. The controller includes an LCD display for battery voltage, amperes, and system pressure. It features twin battery chargers with reverse polarity protection and auto voltage detection.

3. Pressure Sensor
A solid-state 4-20mA pressure sensor is included, with adjustable start and stop points. A low-pressure pre-alarm is indicated by a flashing green LED.

4. Output Relays
The controller provides two sets of alarm contacts for remote indication of engine run, low fuel, auto mode, and common alarm. Additional relays are programmable for future site requirements.

5. Enclosure Options
The controller is housed in a NEMA Type 2 enclosure, with optional enclosures available for various environmental conditions, including watertight and dust-tight options.

6. Microprocessor Control
Programmable parameters include start/stop PSI points, pressure alarms, and timers. Visual and audible alarms cover a range of conditions such as fail to start, low oil pressure, and high engine temperature.

7. Programming Menu
The menu supports password protection and multiple languages. It is organized into seven main headings, including regional settings and system configuration.

8. Custom Inputs/Outputs
The controller includes nine custom inputs and programmable LED indicators. Users can program future inputs/outputs and optional relays through the main menu.

9. Manufacturer
The controller is manufactured by Eaton Industries (Canada) Co.

For more information, visit: www.chfire.com
See more

Catalog excerpts

Diesel Plus Fire Pump Controllers-1

F^T'N Powering Business Worldwide April 2015 Fire Pump Controllers FeaturesDiesel Plus Fire Pump ControllersTypical Specifications1. Approvals A. The Fire Pump Controller shall meet Factory Mutual Research (FM) 1321/1323. It shall be listed by [Underwriters Laboratories (UL)], [Canadian Standards Association (CSA)j, [New York Department of Buildings (NySb)] for fire pump service. B. The controller shall be [12 volt / 24 volt] negative ground, for use with Diesel Engine, Model manufactured by. A. All internal components shall be front mounted and wired for ease of inspection and maintenance. All relays shall have visual indication to show that the relays are energized. The controller shall include an LCD display to indicate battery voltage and amperes as well as system pressure, in PSI or Bars. B. The controller shall have twin battery chargers meeting Factory Mutual Research (Fm) requirements. The battery chargers shall have reverse polarity protection/ indication and be capable of recharging a completely discharged battery within 24 hours. The chargers shall auto detect the input voltage of 100VAC to 240VAC and shall be able to be programmed for either 12VDC or 24VDC output. C. The controller shall come standard with a breaker disconnect on the AC line and for both battery connections. 3. Pressure Sensor A. A solid-state 4-20mA pressure sensor shall be provided. The pressure Start and Stop points shall be adjustable in increments of one (1) PSI. A low pressure pre-alarm, indicated with a flashing green LED, shall denote a potential pump starting condition and will remain lit once the pump has started to indicate the starting cause. 4. Output Relays A. Two (2) sets of alarm contacts (Form-C) rated at 8A, 250VAC/30VDC, shall be provided for remote indication of: 4. COMMON ALARM B. Two (2) 'FUTURE' relays, each containing two sets of alarm contacts (Form-C) shall be provided. Relays can be factory set to indicate a specific alarm and shall be field programmable / adjustable to meet future site requirements: C. The Common Alarm relay shall be energized under normal conditions. 5. Enclosure A. The controller shall be housed in a NEMA Type 2 (IEC IP11) drip-proof, powder baked finish, freestanding enclosure. B. Optional Enclosures: 1. NEMA 3R (IEC IP24) rain-tight enclosure. 2. NEMA 4 (IEC IP66) watertight enclosure. 3. NEMA 4X (IEC IP66) watertight 304 stainless steel enclosure. 4. NEMA 4X (IEC IP66) watertight 316 stainless steel enclosure. 5. NEMA 4X (IEC IP66) watertight corrosion resistant enclosure. 6. NEMA 12 (IEC IP54) dust-tight enclosure. 6. Microprocessor Control A. The following parameters shall be programmable and included as standard: 1. START and STOP PSI points 2. High and Low Pressure Alarm Setpoints 3. STOP MODE: Manual or Auto 5. AC POWER FAILURE: Enable or Disable 6. SEQUENTIAL START TIMER: 0-300 sec. 7. WEEKLY TEST TIMER 9. LANGUAGE: English/French/Spanish/Other B. The following visual and audible alarms shall be provided: FAIL TO START LOW OIL PRESSURE ENGINE OVERSPEED BATTERY #1 FAILURE BATTERY #2 FAILURE REMOTE START LOW PRESSURE SPEED SWITCH FAULT ECM SELECTOR IN ALT POSITION FUEL INJECTOR MALFUNCTION STARTER #1 FAILURE STARTER #2 FAILURE TRANSDUCER FAILURE DATA CABLE DISCONNECT DC FAIL HIGH ENGINE TEMP. ENGINE RUN LOW FUEL CHARGER #1 FAILURE CHARGER #2 FAILURE DELUGE VALVE INTERLOCK ON LOW SUCTION ECM WARNING ECM FAILURE HIGH RAW WATER TEMPERATURE LOW ENGINE TEMPERATURE LOW RAW WATER FLOW FUEL SPILL For more information visit: www.chfire.com PS081002EN

 Open the catalog to page 1
Diesel Plus Fire Pump Controllers-2

Fire Pump Controllers Features April 2015 Diesel Plus Fire Pump Controllers The controller shall have a 4 line by 40 character LCD display mounted on a panel opening in the front door. The LCD display shall indicate the following: 1. Main screen displaying system pressure, Battery #1/#2 voltage and amperage, operation mode, shutdown mode, custom messages, alarms, timers, date, and time. 2. Set point review screen displaying the programmed pressure start and stop points, and weekly test time. 3. Controller statistics screen, including: a. Powered Time b. Engine Run Time c. Number of Cranks d....

 Open the catalog to page 2
Diesel Plus Fire Pump Controllers-3

Fire Pump Controllers Features April 2015 Diesel Plus Fire Pump Controllers Where shutdown of the pump(s) due to low suction pressure is required, it shall be accomplished without the addition of a separate panel or enclosure. The LCD display shall indicate low suction shutdown. Resetting of the condition shall be automatic or manual as selected by the user. Means shall be provided to test the operation of all LED’s to ensure their functionality. The programming menu shall have the ability to enable an entry password. B. The programming menu shall be limited to two (2) levels of password protection....

 Open the catalog to page 3