Product catalog summary
Product Overview: Eaton's Cutler-Hammer custom Pump Controllers are designed for industrial, commercial, and municipal applications, including simplex, duplex, and triplex operations, as well as wastewater and sewage treatment. They range from relay-based Simplex controllers to PLC-based Quadraplex controllers with pressure transducer input. A Variable Frequency Drive Booster Controller, model BPV, is also available.
Key Features: The controllers offer various pressure switches for functions like low suction pressure and low system pressure, with options including diaphragm pressure switches and seawater-rated stainless steel Mercoid switches. PLC-based units can use a pressure transducer input instead of a standard pressure switch. Alarm indication is provided by a rotating warning light. All controllers use Eaton Cutler-Hammer components, including NEMA rated starters and pushbuttons.
Enclosures: Eaton Cutler-Hammer manufactures a variety of enclosures, including custom designs, with ratings such as NEMA 1, 2, 3R, 4, 4X, and 12.
Control Transformer: Control power is supplied by a transformer protected by two fuses, with secondary power at 120VAC - 50/60Hz.
Indicators and Timers: Standard on Duplex, Triplex, and Quadraplex controllers, power ON and pump run lights indicate power supply and pump operation. Timer options include Sequential Start Timer, Run Period Timer, and Elapsed Time Meter, with modifiable values in PLC-based controllers.
Additional Features: Options include space heaters with thermostats or humidistats, common alarm indication, auxiliary indication lights, manual alternation selector switch, weekly test function, elapsed time meter, and auxiliary/remote contacts for pump run and power failure indications.
Approvals and Catalog Information: The controllers are N.Y.C. approved. The catalog provides detailed options and pricing for various configurations, including voltage and horsepower specifications.
Catalog Overview: The document provides a comprehensive catalog of Eaton Cutler-Hammer pump controllers, detailing various models, specifications, and pricing. It includes sections on Booster Pump Controllers (BPC) and Fire Pump Controllers (FD series).
Booster Pump Controllers (BPC): The BPC series includes models for different voltage and horsepower requirements, with prices ranging from $2,916 to $16,650 depending on specifications.
Fire Pump Controllers (FD Series): The FD series includes various types of fire pump controllers such as Limited Service Controller (FD20), Across-the-Line (FD30), and Soft Start (FD90), with additional models like Transfer Switches (FT SERIES) and Diesel Engine Controllers.
Manufacturing and Support: Eaton Cutler-Hammer offers flexible production capabilities for custom and large volume orders. All controllers are tested in-house before shipping, with standard delivery of 2-3 weeks and options for expedited delivery.
Local and Technical Support: Local support is available through factory-trained agents, providing sales and technical assistance, including on-site start-up support. Spare parts are readily accessible for emergencies. Direct factory contact is recommended for areas without local agents.
Design and Application Support: Standard and custom controller models are designed in-house, with custom solutions developed based on specific customer requirements.
Contact Information: Customers can contact Eaton Cutler-Hammer via email or phone, with contact details provided for the Calgary, Canada location.
See more

Catalog excerpts

Booster Pump Controllers-1

Approvals (Ur) NYC- (Gift VjfL/ APPROVED WLW Eaton Cutler-Hammer Components All Pump Controllers are manufactured using Eaton Cutler-Hammer components such as NEMA rated starters, oil and dust tight 10250T Series NEMA pushbuttons and Cutler-Hammer breakers. Eaton Cutler-Hammer manufactures a wide variety of enclosures. As well as many standard designs, custom enclosures can be produced to your specifications. Ratings include NEMA 1, 2, 3R, 4, 4X and 12. The control power is supplied by a control power transformer (TR) which is protected by two fuses on the primary lines. Secondary power is 120vac - 50/60Hz. A 120V Power ON and Pump Run light is supplied standard on Duplex, Triplex and Quadraplex controllers and can be added as an option to all simplex controllers. The Power ON light indicates when power is supplied to the internal components and indicating devices. The Pump Run light is operated from an auxiliary contact from the pump motor starter. The two lights are provided standard in PLC controlled units. Auxiliary indication lights can be provided for indication of various conditions. Quantity and nameplate information must be specified at time of order. A common alarm indicating light can be provided which will activate when any alarm condition exists. Manual Alternation Selector Switch An optional selector switch can be installed which allows the user to manually select lead and lag pumps. An auxiliary set of contacts can be installed to provide a signal for indication of Pump Run and / or AC Power Failure. Extra remote contacts ( 1 set - Form-C ) are also available. The quantity required must be specified at time of order. Several space heater options are available. A 120V / 220V, 300W heater can be provided by itself, with Thermostat for controlling temperature or with a Humidistat for control of internal moisture. As well, a low room temperature switch and high temperature cutout input (PLC models) are available as options. Strobe Light A compact, rotating warning light can be provided in place of an alarm bell for alarm indication purposes. It features a parabolic reflector which rotates around an incandescent lamp, providing 60 flashes per minute in all directions. Timer options include SST - Sequential Start Timer, RPT - Run Period Timer and ETM - Elapsed Time Meter. In the PLC based controller, timer values can be field modified. Descriptions of each timer function can be found in the Pump Controller Instruction Manual - IM05805007K. The weekly clock function can be provided by either a separate component or as part of the PLC program / function. This allows the user to set automatic time intevals for performing system tests. A six digit LCD, solid state, non-resettable elapsed time meter can be installed which will record the amount of time the pump motor has been running. It receives the elapsed time signal from the auxiliary contact of the motor starter. This ensures that elapsed time is recorded in both the HAND and AUTO position of the H.O.A. Control selector switch. In a PLC operated controller, the elapsed time meter is integral to the PLC. Various pressure switches are available for functions such as low suction pressure, low suction shutdown and low system (tank) pressure. Options include a Standard diaphragm pressure switch, a Mercoid 10-300 or 25-600psi seawater rated stainless steel Mercoid switch. On PLC based controller units, a pressure transducer input can be substituted in place of a standard pressure switch. The transducer provides a 0.5 - 5.5v input to the PLC. For more information visit: www.chfire.com BR05805025K/B

 Open the catalog to page 1
Booster Pump Controllers-2

12 Pump Controllers Industrial / Commercial / Municipal Dimensions Standard Enclosure - Type NEMA 2, 3R, 4, 4X, 12 Approximate Dimensions in Inches (mm) Box C. NEMA 1 Box C. NEMA 12 Operating Handle l_ 14,62 _ Qwatinq 'Handle Ffeset ELtlons -Knockouts for Flange Control Conduit 2 on Each Side Reset Buttons Box C. NEMA 3R Removable Top Cove r Provides Usage of Safety Switch Hubs per Table Below _14.52 \ 1368.8) \ ~ M w 8.60 y (218.4) -wL m-2M Fteset Biilons Reset Buttons 5 Holes & Slots for 1/4" Mtg. Screws 5 Holes & Slots for 1/4*' Mtg. Screws 2" Conduit Hub Top 8 Bottom Sire 3 2-1/2" Conduit...

 Open the catalog to page 2
Booster Pump Controllers-3

For more information visit: www.chfire.com BR05805025K/B

 Open the catalog to page 3
Booster Pump Controllers-4

Pump Controllers Industrial / Commercial / Municipal Typical Electrical Wiring Schematic Booster Pump Controller - PLC Based For more information visit: www.chfire.com

 Open the catalog to page 4
Booster Pump Controllers-5

Pump Controllers Industrial / Commercial / Municipal Catalog Number Selection Booster Pump Controller Catalog Numbering System Simplex Duplex Triplex Quadraplex 120V Control Voltage Filter Audible Alarm Audible Alarm with Silence Pushbutton Common Alarm Indication Light Remote Contacts "Pump Run" Extra Contacts "AC Power Failure" Extra Remote Contacts (1 Set - Form C) - price each * Current Sensing Relay Phase Failure / Reversal Relay ( DSP1-L ) NEMA 3R - Raintight Enclosure NEMA 4 - Watertight Enclosure NEMA 12 - Industrial Dust Tight Enclosure NEMA 4X - Stainless Steel Enclosure Tropicalization...

 Open the catalog to page 5
Booster Pump Controllers-6

Designation Description Price * Specify quantity and nameplate required BR05805025K/B For more information visit: www.chfire.com

 Open the catalog to page 6
Booster Pump Controllers-7

Catalog Number Selection Chart - Pump Controllers Catalog Number Selection Chart - Pump Controllers Catalog Number Catalog Number For more information visit: www.chfire.com BR05805025K/B

 Open the catalog to page 7
Booster Pump Controllers-8

Catalog Number Selection Chart - Pump Controllers Catalog Number Selection Chart - Pump Controllers Catalog Number Catalog Number BR05805025K/B For more information visit: www.chfire.com

 Open the catalog to page 8
Booster Pump Controllers-9

Pump Controllers Industrial / Commercial / Municipal Pump Controller Catalog Numbering System Booster Pump Controller - BPC31 - Triplex Catalog Number Selection Chart - Pump Controllers Catalog Number Selection Chart - Pump Controllers Catalog Number Catalog Number For more information visit: www.chfire.com BR05805025K/B

 Open the catalog to page 9
Booster Pump Controllers-10

Pump Controllers Industrial / Commercial / Municipal Pump Controller Catalog Numbering System Booster Pump Controller - BPC41 - Quadraplex Catalog Number Selection Chart - Pump Controllers Catalog Number Selection Chart - Pump Controllers Catalog Number Catalog Number BR05805025K/B For more information visit: www.chfire.com

 Open the catalog to page 10

All Cutler-Hammer catalogs and technical brochures

  1. Fuses

    291  Pages

  2. OEM Product

    334  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.