Description: Crouzet Solid State Relays (SSRs) are versatile, robust, and designed for long life, suitable for various applications. The GN4 Series features a 4-channel solid-state relay in a compact package, offering easy installation and use.
Specifications:
  • Rated Load Current: 25 A
  • Output Voltage: 12-280 Va
  • Control Voltage: 4-32 Vc
  • Special Zero Cross for resistive, inductive, and capacitive loads
  • Certifications: cRUus, CE, UKCA
Product Features:
  • 4 channels in one package
  • Fast-on terminals
  • Zero Cross switching type
Output Characteristics:
  • Operating Voltage: 24-280 Vrms
  • Maximum Load Current: 4 x 25 Arms
  • Transient Overvoltage: 600 Vpk
  • Maximum Surge Current: 250-260 Apk
  • Thermal Resistance Junction to Case: 1.7 °C/W
Input Characteristics:
  • Control Voltage Range: 4-32 Vc
  • Minimum Turn-On Voltage: 4 Vc
  • Maximum Input Current: 12 mA
General Characteristics:
  • Dielectric Strength (Input-Output): 4000 Vrms
  • Ambient Operating Temperature Range: -40 to 80 °C
  • Housing Material: UL94 V-0
  • Humidity: 85% non-condensing
Accessories:
  • Heatsinks with various thermal resistances
  • Thermal Pads (Pre-cut and Self-Adhesive)
  • Screw Mounting Kit and Thermal Grease
  • DIN Rail Adapter
Standards & Compliance:
  • Designed according to IEC 62314
  • Shock and Vibration Resistance: IEC 60068-2-27 and IEC 60068-2-6
  • Electromagnetic Compatibility: IEC 61000-4 series
  • UL508 compliance
Warnings: Product information is for reference only and does not constitute a warranty. Crouzet reserves the right to modify products without notice. Users must ensure product suitability for specific applications.
See more

Catalog excerpts

GN4 Series-1

4 Channel Solid State Relays Panel Mount – 4 Channel › 5 A in a classic Hockey Puck package 2 › channels in one package 4 › Fast-on terminals › pecial Zero Cross (Resistive, Inductive and Capacitive loads) S › RUus, CE and UKCA Recognized c Product Selection - Special Zero Cross (Resistive, Inductive and Capacitive loads) Rated Load Current Output Voltage Part number system GN4 PART NUMBERING SYSTEM Phases/Channels 8415: 4-Channel Switching Type 0: Zero Cross RÉFÉRENCEMENT Do you need an adapted or customized solution? commutationon www.crouzet.com Phases/Canaux Type de Contact us Tension de commande 8415: 4-Channel Crouzet Solid State Relays are designed to be used in almost any application, offering very long life expectancy and are easy to install, easy to use, For more information about Crouzet’s Solid State relays, please visit www.crouzet.com. Cache 4: Sans cache

 Open the catalog to page 1
GN4 Series-3

General Characteristics General Notes (1) All parameters at 25 °C unless otherwise (2)Heatsink required, see derating curves Diagrams Wiring It's recommended to use external overvoltage protection (Varistor / TVS Diode) and short-circuit protection (fuse / circuit breaker), if they are not already integrated

 Open the catalog to page 3
GN4 Series-4

Diagrams Equivalent Circuit Block GN4 Series 4-32 Vc control Triac - 12-280 Va - Zero Cross - Input current vs Input Voltage Standard Regulated DC inputs 1 Current Limiter +DC Common Diagrams Dimensions (mm) GN4 Series

 Open the catalog to page 4
GN4 Series-5

Curves Surge Current Information GN4 - 25 A 300 Itsm (Apeak) No Repetitive Surge Current / Tj initial = 25 °C Repetitive Surge Current / Tj initial = 121 °C Curves Thermal Derating Curves GN4 - 25 A - 25 Amps per channel 120 Total Load Current (Amps) Accessories Heatsink 0.9 °C/W Thermal Resistance - 26532752N

 Open the catalog to page 5
GN4 Series-6

Accessories Thermal Pad Pre-cut - 26532720N Accessories Others Screw Mounting Kit - 26532001 Thermal Grease for Heatsink mounting 26532003 Standards & Electromagnetic Compatibility Specfification Designed in accordance with the requirements of IEC 62314 IEC 60068-2-27: Shock Resistance 15 g /11 ms IEC 60068-2-6: Vibration 0.33 mm / Amplitude over 10-55 Hz IEC 61000-4-2: Electrostatic Discharge Discharge 8kV air discharge Criterion A – Level 3 IEC 61000-4-4: Electrically Surge Output 1 kV Line to Line Criterion B – Level 3 IEC 61000-4-5: Surge Output 1 kV Line to Line Criterion B – Level 3 Standards...

 Open the catalog to page 6
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.