General Presentation
Load banks are devices used to apply electrical loads to equipment for testing purposes. They range from simple resistor assemblies to complex systems for applications like battery discharge testing and aerospace generator testing. Load selection can be manual, remote, or electronic, with features for data recording and device interfacing.
Main Features
The document emphasizes the design and reliability of load banks, focusing on their power, current, and voltage handling capabilities. Specific alloys are used for resistance wires to ensure durability. Both standard models and custom designs are available to meet customer needs.
Standard Series
Coudoint offers several series of load banks, including:
  • 6 kW hand-transportable battery discharge testers (DVIM, DMIM, DNIM series)
  • 12 kW hand-transportable battery discharge testers (DVTM, DMTM, DNTM series)
  • 16 kW automatic hand-transportable load banks (DXVA series)
  • 45 kW automatic load banks (DXLA series)
  • 150 kW automatic load banks (DCLA series)
These models can be customized to meet specific requirements.
6 kW Hand-Transportable Battery Discharge Testers
The DVIM, DMIM, and DNIM series are designed for manual load step selection and are hand-transportable. They feature forced-air cooling and are available for 12, 28, and 48 volts, with specific mechanical and electrical features, safety features, and customization options.
12 kW Hand-Transportable Battery Discharge Testers
The DVTM and DMTM series use woven and wirewound resistors respectively, with forced-air cooling, designed for higher power applications, offering similar customization options as the 6 kW series.
Overview of Load Bank Series
The document provides detailed specifications and features of various load bank series, characterized by cooling methods, portability, and power dissipation capabilities.
1. DVTM Series:
  • Manual load step selection, portable (~28 kg), dissipates up to 12 kW.
  • Forced-air cooling with built-in fans, noise level ~54 dB(A).
  • Models: DVTM-48 (48V/250A), DVTM-128 (128V/100A).
  • Features include reverse-voltage detection, cooling air flow failure detection, and various connection options.
2. DMTM Series:
  • Similar to DVTM but slightly heavier (~30 kg).
  • Models: DMTM-48 (48V/250A), DMTM-128 (128V/100A).
  • Constructed with Coudoint resistors, includes safety features like reverse-voltage detection.
3. DNTM Series:
  • Natural-air cooling, portable (~30-34 kg), dissipates up to 12 kW.
  • Models: DNTM-48 (48V/225A), DNTM-128 (128V/80A).
  • Features include manual load step selection and standard options for customization.
4. DXVA Series:
  • Electronically controlled, portable (~35 kg), dissipates up to 16 kW.
  • Forced-air cooling, models include DXVA-48, DXVA-128, DXVA-240.
  • Features include automatic load regulation and safety protections.
5. DXLA Series:
  • Electronically controlled, compact, dissipates up to 45 kW.
  • Models: DXLA-60, DXLA-96, DXLA-240.
  • Includes features like automatic load detection and regulation.
6. DCLA Series:
  • Electronically controlled, portable, dissipates up to 150 kW.
  • Models: DCLA-230, DCLA-240.
  • Features include built-in digital controller and safety protections.
7. Custom Designs:
  • Various custom load banks are available to meet specific needs, showcasing the diversity of solutions offered.
Specialized Load Banks
Several models are detailed, each with unique features and specifications, such as capacitive, resistive, inductive, and PLC-controlled load banks. These models vary in cooling methods, control interfaces, and protection levels, catering to specific testing requirements.
See more

Catalog excerpts

Load Banks Load Banks Test Benches Battery Discharge Testers-1

Load Banks Load Banks Test Benches Battery Discharge Testers Hardware Reference Document 1101031 - Edition October 2016

 Open the catalog to page 1
Load Banks Load Banks Test Benches Battery Discharge Testers-2

Hardware Reference Email : [email protected] Website : www.coudoint.com Address : 19, Avenue de la gare Document 1101031 – Edition October 2016 Information and products subjects to change without prior notice

 Open the catalog to page 2
Load Banks Load Banks Test Benches Battery Discharge Testers-3

Hardware Reference 1 Introduction This documentation aims at showing the evolutions in the last years of the load banks we propose. The products shown in the former bench documentation can always be produced, but we enhanced our product range by numerous models from the small hand-transportable products to the sophisticated custom products, with improvements under every aspect : mechanical structure for an easy maintenance, water-cooling if required, electronic control while using PLC's types according to our customer choice, ... . The documentation presents our standard products as well as some...

 Open the catalog to page 3
Load Banks Load Banks Test Benches Battery Discharge Testers-4

COt/OD/Nr Hardware Reference 3 Standard load banks Coudoint propose 8 standard load banks seiries : ♦> 3 series (9 models) of 6 kW hand-transportable load banks : DVIM, DMIM, DNIM ♦> 3 series (6 models) of 12 kW hand-transportable load banks : DVTM, DMTM, DNTM ♦> a series (3 models) of 16 kW automatic hand-transportable load banks : DXVA ♦> a series (3 models) of 45 kW automatic load banks : DXLA ♦> a series (3 models) of 150 kW automatic load banks : DCLA These standard load banks may be fitted for matching specific needs on request. 3.1 6 kW hand-transportable...

 Open the catalog to page 4
Load Banks Load Banks Test Benches Battery Discharge Testers-5

3.1.1 DVIM Series COt/OD/Nr Hardware Reference Load banks of the DVIM series are : - with manual load step selection - hand transportable (~ 13 kg, small size) - dissipating a power up to 6 kW - forced-air cooled (built-in fan) Standard models are : • DVIM-12 : 12 V / 250 A max. *> Mechanical features • overall dimensions (W)313 x (D)508 x (H)356 mm • aluminum lightweight case - ingress protection IP20 • weight : approximately 13 kg depending on the model • one carrying handle • forced-air cooling (built-in fan) • maximum noise level approximately 54 dB(A) Standard DVIM housing *>...

 Open the catalog to page 5
Load Banks Load Banks Test Benches Battery Discharge Testers-6

3.1.2 DMIM Series COt/OD/Nr Hardware Reference Load banks in the DVIM series: - have manual load step selection - are hand transportable (~ 14 kg, small size) - dissipate up to 6 kW - are forced-air cooled (built-in fan) Standard models are : • DMIM-12 : 12 V / 250 Amps max. • DMIM-28 : 28 V / 200 Amps max. • DMIM-48 : 48 V / 120 Amps max. *> Mechanical features • overall dimensions (W)313 x (D)508 x (H)356 mm • lightweight aluminum case - ingress protection IP20 • weight : approximately 14 kg depending on the model • one carrying handle • forced-air cooling (built-in fan) • maximum noise level...

 Open the catalog to page 6
Load Banks Load Banks Test Benches Battery Discharge Testers-7

3.1.3 DNIM Series COt/OD/Nr Hardware Reference Load banks in the DNIM series: - have manual load step selection - are hand transportable (~ 14 kg) - dissipate up to 6 kW - natural-air cooling Standard models are : • DNIM-12 : 12 V / 250 Amps max. • DNIM-28 : 28 V / 200 Amps max. • DNIM-48 : 48 V / 110 Amps max. *> Mechanical features • overall dimensions (W)304 x (D)623 x (H)320 mm • Aluminum and plated-zinc steel case - ingress protection IP20 • weight : approximately 14 kg depending on the model • One carrying handles • natural-air cooling ♦> Temperature range • ambient temperature - 30°C to...

 Open the catalog to page 7
Load Banks Load Banks Test Benches Battery Discharge Testers-8

Hardware Reference 3.2 Hand-transportable 12 kW battery discharge testers Coudoint propose three 12 kW hand-transportable battery discharge testers Series : ♦> the DVTM Series use woven resistors and forced-air cooling (2 fans). The woven resistors allow a weight reduction and bring a good resistance to mechanical shocks to the product. Forced-air cooling allows a compact housing and a limited temperature rise of the housing during the test. ♦> the DMTM Series use wirewound resistors and forced-air cooling (2 fans). Forced-air cooling allows a compact housing and a limited temperature rise of...

 Open the catalog to page 8
Load Banks Load Banks Test Benches Battery Discharge Testers-9

COt/OD/Nr Hardware Reference 3.2.1 DVTM Series ♦> Mechanical features • overall dimensions (W)403 x (D)500 x (H)753 mm • aluminum lightweight case - ingress protection IP20 • weight : approximately 28 kg • one carrying handle • 2 cooling fans • maximum noise level approximately 54 dB(A) *> Temperature range • ambient temperature - 10°C to + 40°C *> Electrical features • resistive load constructed of Coudoint woven resistances in low temperature coefficient alloy • 2 test sockets on the front panel for current measurement by an external voltmeter (1mV for 1,5A) • 2 x 25 mm2/ 3,5 m connecting cables...

 Open the catalog to page 9
Load Banks Load Banks Test Benches Battery Discharge Testers-10

Load banks in the DMTM series: - have manual load step selection - are hand transportable (~ 30 kg, small size) - dissipate up to 12 kW - are forced-air cooled (built-in fan) Standard models are : • DMTM-48 : 48 V / 250 Amps max. • DMTM-128 : 128 V / 100 Amps max. *> Mechanical features • overall dimensions (W)317 x (D)495 x (H)543 mm • lightweight aluminum case - ingress protection IP20 • weight : approximately 30 kg depending on the model • one carrying handle • forced-air cooling (built-in fan) • maximum noise level approximately 54 dB(A) *> Temperature range • ambient temperature - 10°C to...

 Open the catalog to page 10
Load Banks Load Banks Test Benches Battery Discharge Testers-11

COt/OD/Nr Hardware Reference 3.2.3 DNTM Series Load banks in the DNTM series: - have manual load step selection - are hand transportable (~ 30 to 34 kg) - dissipate up to 12 kW - natural-air cooling Standard models are : • DNTM-48 : 48 V / 225 Amps max. *> Mechanical features • overall dimensions (W)352 x (D)849 x (H)353 mm • aluminum and plated-zinc steel case - ingress protection IP20 • weight : approximately 30-34 kg depending on the model • two carrying handles and 4 rubber feet • natural-air cooling *> Temperature range • ambient temperature - 10°C to + 50°C *> Electrical features • resistive...

 Open the catalog to page 11