General Overview
The M 20 RC Chlorination System is engineered for dosing gas chlorine and can be adapted for other gases. It operates on an indirect vacuum principle, ensuring safety and reliability. The system includes a vacuum regulator with a rate valve and an M 300 C ejector. Dosing is manually adjustable and synchronized with the ejector pump's operation.

Installation
Installation of vacuum regulators is straightforward but must be performed by qualified professionals adhering to international standards for safety and efficiency. An annual system overhaul by authorized service personnel is mandatory.

Operation Principle
The system comprises a chlorine cylinder, vacuum regulator, ejector, and booster pump. The typical installation involves a sequence from the chlorine cylinder to the ejector, including components like a pressure gauge, rate valve, booster pump, filth filter, and collector line.

Technical Specifications
The system supports a capacity of up to 15 kg/h and features a full vacuum system for enhanced safety. Chlorine-wetted parts are constructed from high-quality materials for reliability. Connection sizes vary based on vacuum requirements, with specific dimensions provided for different dosing capacities.

Order Codes and Options
Various options are available, including alarms, regulators, gas types (Cl2, CO2, SO2, NH3), dosing ranges, and ejector types. The system can be customized with pressure gauges and yokes for specific applications. Connection to the cylinder complies with DIN 477 standards.

Additional Information
The ejector connection details are available in the product information for M 300 ejectors. The system's accuracy is within 4% of flow, with an operating range of 20:1. The net weight is 4.7 kg, and the gross weight is 7.4 kg, with packaging dimensions of 600 x 400 x 400 mm.
See more

Catalog excerpts

M 20 RC-1

1 Dosing equipment for aggressive gases Full vacuum system for maximum safety Chlorine wetted parts made of high quality materials for maximum reliability The M 20 RC Chlorination System is designed for dosing gas chlorine and with minor alterations also for other gases, working on the indirect vacuum principle. The M 20 RC System consists of: M 20 C vacuum regulator with rate valve  M 300 C ejector  It is very simple to mount vacuum regulators. However, installation of the devices must be done by qualified experts taking in consideration all required international standards in order to ensure safe and faultless operation. An authorized service must overhaul the system once a year. Dosing can be set manually with the rate valve on the regulator. It starts or stops when the ejector pump switches on or off. Typical Vacuum Installation from The Chlorine Cylinder to the Ejector 1. Chlorine cylinder 2. Vacuum regulator 3. Ejector 4. Booster pump 1. Chlorine cylinder 2. Gas Chlorine Regulator 3. Outlet 4. Vacuum line 5. Ejector 6. Pressure Gauge 7. Rate Valve 8. Booster Pump 9. Filth filter 10. Collector Line for use

 Open the catalog to page 1
M 20 RC-2

1 Dosing equipment for aggressive gases ORDER CODES Model El. Alarm Signal (Full/Empty ) Regulator Gas type Dosing range Ejector Pressure Gauge(y/n) Block connection Yoke OPTIONS: - Alarm: yes “A”, without alarm the letter is not written in the code - Regulator: “R”, means system with all general parts - Gas type: “C” - Cl2, “CO2” - CO2, “S” - SO2, “N” - NH3 - Dosing range (g/h): 1 up to 12 2 up to 25 3 up to 100 4 up to 200 5 up to 500 6 up to 1000 7 up to 2000 8 up to 4000 9 up to 10000 15 up to 15000 - Ejector: “B” - D.P.T. : Ejector with PVC valves designed for pool engineering, (pressure...

 Open the catalog to page 2

All Controlmatik catalogs and technical brochures

  1. MR 50 RC

    2  Pages

  2. MR 40 RC

    2  Pages

  3. MR 21 RC

    2  Pages

  4. MR 20 RC

    2  Pages

  5. M 30 RC

    2  Pages

  6. M 470 C PVC

    2  Pages

  7. M 3800

    2  Pages

  8. M 2103 C

    2  Pages

  9. M 4510 C

    2  Pages

  10. M 5265 C

    2  Pages

  11. automation

    1  Page

  12. M 5700 C

    2  Pages

  13. M 1322

    2  Pages

  14. M 1122

    2  Pages

  15. M 1056 C

    2  Pages

  16. M 1036 C

    2  Pages

  17. M 1035 C

    2  Pages

  18. M 3610 C

    2  Pages

  19. M 3480 C

    2  Pages

  20. M 3100 C

    2  Pages

  21. M 3319 C

    2  Pages

  22. M 3531 C

    2  Pages

  23. M 300 C

    2  Pages

  24. M 200 C

    2  Pages

  25. M 20 C

    2  Pages

  26. M 40 C

    2  Pages

  27. M 50 C

    2  Pages

  28. M 5262 C

    2  Pages

  29. M 5600 C

    2  Pages

  30. M 3521 C

    2  Pages

  31. M 40 C

    2  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.