Overview: The ELNet VIP Electrical Powermeter is a compact, multifunctional, three-phase meter designed for precise power measurement in electrical installations.
Technical Specifications:
  • Power Requirements: 90 ~ 250 VAC, 110 ~ 280 VDC, 60/50 Hz, 9VA
  • Dimensions: 96 x 96 x 80 mm (HxWxD)
  • Weight: 0.45 Kg
  • Environmental Conditions: Operating and storage temperature range of -20 ~ +70 ºC, humidity 0 ~ 95% RH non-condensing
  • Protection: IP64 Front Panel
Input & Output Ratings:
  • Accuracy: Active and reactive energy 0.5% FS
  • Voltage: Line-Line 0 ~ 950 VAC RMS, Line-Neutral 0 ~ 650 VAC RMS, Maximum 1000V RMS Continuous, Burden < 0.06VA
  • Current: Rated 0-5 A, Overload 50 A RMS Continuous, Withstand 100 A for 1 minute, Burden < 0.05 VA
Display: High-resolution backlight display with a maximum input voltage of 1000V and current of 6A.
Measurement & Display Values:
  • Current: 0.01 – 6A
  • Voltage L-N: 0.00 – 550 V
  • Voltage L-L: 0.00 – 950 V
  • Frequency: 45.1-65.1 Hz
  • Active Power: 0.00W – 999MW
  • Reactive Power: 0.00VAR -999MVAR
  • Apparent Power: 0.00VA -999MVA
  • Power Factor: -1.00 ÷ 1.00
Standards Compliance: The device complies with several standards including IEC 60051-03, EN 55022, EN 55024, EN 61000-3-2, EN 61000-3-3, and various IEC 61000-4 series standards.
Additional Information: Includes a wiring diagram example for installation guidance.
See more

Catalog excerpts

ELNet VIP Tech Catalog-1

Energy meter & Electrical Powermeter ELNet VIP Electrical powermeter is a compact, multi functional, three-phase meter, especially designed to meet the stringent needs of power measurement in any electrical installation. Input & Output Rating Technical Data Power Requirements: Shipping Weight: Environmental: Operation. Storage. Humidity Front Panel Protection Mechanical mounting Current: Rated Overload Withstand Burden High resolution backlight display 1000V Maximum Input Current: Voltage: Line-Line Line-Neutral Maximum Burden Active energy 0.5% FS Reactive energy 0.5% FS 0 ~ 950 VAC RMS 0 ~ 650 VAC RMS 1000V RMS Continuous < 0.06VA Maximum Input Voltage: Dimensions (HxWxD):

 Open the catalog to page 1
ELNet VIP Tech Catalog-2

Energy meter & Electrical Powermeter Measurement & Display Values Display Range in direct connection (scaling factor 1) Measuring in direct connection (scaling factor 1) Measurement Parameter Display Range EN 55022, Class A, Amendments A1; A2 EN 55024, Amendments A1; A2 Active power total\phase Reactive power total\phase Apparent power total\phase Power Factor (cap.\ind.) Wiring Diagram Example

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.