ELNet PQ Tech Catalog

ELNet PQ Tech Catalog

ELNet PQ Tech Catalog

Product catalog summary
Overview: The ELNet-PQ multimeter is a multifunctional, three-phase power quality analyzer designed for detailed power analysis in electrical networks. It complies with the EN50160 standard and records waveform events with high sampling resolution.
Specifications:
  • Power Requirements: 90 ~ 250 VAC, 110 ~ 280 VDC, 60/50 Hz, 8VA.
  • Dimensions: 144 x 144 x 100 mm, Weight: 1.00 Kg.
  • Environmental: Operating and storage temperature range of -20 ~ +70 ºC, Humidity: 0 ~ 95% RH non-condensing.
  • Protection: IP64 front panel, 4GB memory size.
  • Communication: Supports BACnet and Modbus protocols over RS485 or Ethernet TCP/IP.
Input & Output Ratings:
  • Voltage: Line-Line 0 ~ 950 VAC RMS, Line-Neutral 0 ~ 550 VAC RMS, Maximum 1000V RMS.
  • Current: Rated 0-1 A or 0-5 A, Overload 50 A RMS Continuous, Withstand 100 A for 1 minute.
  • Accuracy: Active and Reactive energy 0.2%, Voltage and Current 0.2%, Power 0.4%, Frequency 0.05%, Power Factor 0.5%.
Display: High-resolution color LCD display with 320x234 pixels.
Measurement & Display Values:
  • Current and Neutral Current: 0.001 – 6A.
  • Voltage L-N: 0.000 – 550 V, Voltage L-L: 0.000 – 650 V.
  • Frequency: 45.001-65.001 Hz.
  • Power: Active, Reactive, and Apparent power measured up to 99999MW/MVAR/MVA.
  • Energy: Active, Reactive, and Apparent energy measured up to 99999999MWH/MVARH/MVAH.
  • Harmonic THD and Partial Harmonic: 0.000 – 100%.
Standards: Complies with various IEC and EN standards including IEC 62053-22, IEC 61000-4 series, and EN 55022.
Additional Features: The device includes history data logging, supports standard communication protocols, and integrates easily into Building Management Systems.
See more

Catalog excerpts

ELNet PQ Tech Catalog-1

electrical multimeter & power quality analyzer ELNet-PQ multimeter is a highly accurate multifunctional, three-phase power quality analyzer, the unit is especially designed to meet the stringent needs of power analyzing in any electrical network. ELNet PQ allows producing a detailed report according to EN50160 standard as well providing records of the wave forms during the power quality events (such as Sag, Swell etc with sampling resolution of 160 bit per cycle). The PQ model allows analyzing and receiving Profile recording and Event recording such as minimum and maximum RMS value over 10 min of voltage, current, harmonics, power and power factor. Voltage Unbalanced (positive and negative as well as Zero Sequence). PST and PLT. ELNet-PQ includes history data logging and supports standard communication protocols BACnet and Modbus with simple integration into Building Management Systems over RS485 or Ethernet TCP. In addition to power quality monitoring the PQ stores the daily based energy, showing the Power Factor, Max and Min demand, Voltage, Current, THD, TDD, K Factor, up to 64th Harmonics, phasor diagram and much more. Input & Output Rating Technical Data Power Requirements: Dimensions (HxWxD): Shipping Weight: Environmental: Operation. Storage. Humidity Front Panel Protection: Memory size: Communication RS485 port: Ethernet (TCP/IP): Up to 115200 bauds Modbus RTU, BACnet MSTP (Modbus and BACnet IP + Web browser capability Accuracy: Voltage: Line-Line Line-Neutral Maximum Burden Active energy 0.2% Reactive energy 0.2% 0 ~ 950 VAC RMS 0 ~ 550 VAC RMS 1000V RMS Continuous < 0.06VA Current: Rated Overload Withstand Burden High resolution color LCD display 320x234 pixels Maximum Input Voltage: Maximum Input Current: Digital inputs: Digital output: 6A 4, 230VAC (ON) 3, dry contact maximum load 250mA

 Open the catalog to page 1
ELNet PQ Tech Catalog-2

electrical multimeter & power quality analyzer Measurement & Display Values Display Range in direct connection (scaling factor 1) Measuring in direct connection (scaling factor 1) Neutral Current Measurement Parameter Display Range IEC 62053-23 IEC 62052-11 EN 55022, Class A, Amendments A1; A2 EN 55024, Amendments A1; A2 EN 61000-3-2, Class A Active power total\phase Reactive power total\phase Apparent power total\phase Power Factor (cap.\ind.) Active Energy total\phase Reactive Energy total\phase Apparent Energy total\phase Harmonic THD V\I Partial Harmonic V\I Operating hour meter NOTEMechanical...

 Open the catalog to page 2
ELNet PQ Tech Catalog-3

electrical multimeter & power quality analyzer External Power Supply Ethernet Prot TCP\IP ETHERNET (Shielded & Grounded) Supervision & control system Tel: +972-3-6474998 F»s:+972J-647J598 24a Haharzcl St. Tel-Aviv. 69710, Israel

 Open the catalog to page 3
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.