1. Catalogs
  2. Control Applications Ltd
  3. ELNet PFC Tech Catalog

ELNet PFC Tech Catalog

ELNet PFC Tech Catalog

ELNet PFC Tech Catalog

Product catalog summary
Overview: The ELNet PFC is a Power Factor Controller designed to measure and correct power factor using up to six On/Off switching controls for capacitor banks. It features automatic identification of capacitor sizes and various connection methods. The device includes a color LCD screen for easy access to electrical values and settings, and incorporates harmonic protections, capacitor life extension, and energy-saving algorithms.
Technical Specifications:
  • Power Requirements: 90 ~ 250 VAC, 110 ~ 280 VDC, 60/50 Hz, 8VA
  • Dimensions: 96 x 96 x 80 mm (HxWxD)
  • Weight: 0.65 Kg
  • Environmental Conditions: Operating and storage temperature: -20 ~ +70 ºC, Humidity: 0 ~ 95% RH non-condensing
  • Protection: IP64 Front Panel
Standards Compliance: The device complies with various IEC and EN standards, including IEC 61000-4 series and EN 55022, ensuring electromagnetic compatibility and safety.
Input & Output Ratings:
  • Voltage: Line-Line: 0 ~ 950 VAC RMS, Line-Neutral: 0 ~ 650 VAC RMS, Maximum: 1000V RMS Continuous, Burden: < 0.06VA
  • Current: Rated: 0-5 A, Overload: 50 A RMS Continuous, Withstand: 100 A for 1 minute, Burden: < 0.05 VA
  • Display: High-resolution color LCD, 320x240 pixels
  • Digital Output: 6 dry contacts, maximum load 3A
Measurement & Display Values:
  • Current: 0.001 – 6A
  • Voltage L-N: 0.000 – 650 V
  • Voltage L-L: 0.000 – 650 V
  • Frequency: 45.001-65.001 Hz
  • Power Factor: -1.000 ÷ 1.000
  • Harmonic THD V/I: 0.001 – 100%
Mechanical Mounting: The device has a height and width of 90 mm each.
See more

Catalog excerpts

ELNet PFC Tech Catalog-1

Power Factor Controller ELNet PFC - Power Factor Controller enables measurement of power factor and power factor correction by using up to 6 On/Off switching control of capacitor bank. ELNet PFC enables automatic identification of capacitors' size and its connection in various methods. The advanced color LCD screen allows easily accessing basic electrical values screens such as voltage, current etc as well as all the information and the setting screens. Harmonic protections, capacitor life prolonging and energy saving algorithms make the PFC to be a most effective solution for power factor correction. Input & Output Rating Technical Data Power Requirements: Dimensions (HxWxD): Shipping Weight: Front Panel Protection Standards IEC 60051-5 EN 55022, Class A, Amendments A1; A2 0.5% in nominal range 0 ~ 950 VAC RMS 0 ~ 650 VAC RMS 1000V RMS Continuous < 0.06VA Current: Rated Overload Withstand Burden High resolution color LCD display 320x240 pixels Maximum Input Voltage: Maximum Input Current: Digital output: Environmental: Operation. Storage. Humidity Accuracy: Voltage: Line-Line Line-Neutral Maximum Burden 6A 6, dry contact maximum load 3A

 Open the catalog to page 1
ELNet PFC Tech Catalog-2

Power Factor Controller Measurement & Display Values Display Range in direct connection (scaling factor 1) Measuring in direct connection (scaling factor 1) Measurement Parameter Power Factor (cap.\ind.) Harmonic THD V\I Display Range Wiring Diagram Example

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.