1. Catalogs
  2. Contemporary Controls GmbH
  3. BAS Router BACnet ® Multi-Network Router

BAS Router BACnet ® Multi-Network Router
1 /8Pages

BAS Router   BACnet ®  Multi-Network Router

BAS Router BACnet ® Multi-Network Router
1 /8Pages

Catalog excerpts

BAS Router   BACnet ®  Multi-Network Router-1

SHEET BAS Router — BACnet® Multi-Network Router The BAS Router provides stand-alone routing between BACnet networks such as BACnet/IP, BACnet Ethernet, and BACnet MS/TP — thereby allowing the system integrator to mix BACnet network technologies within a single BACnet internetwork. The BAS Router has two physical communication ports. One is a 10/100 Mbps Ethernet port and the other is an optically isolated MS/TP port. Router configuration is accomplished via a web page. Versatile Routing Between … • BACnet/IP and BACnet MS/TP • BACnet Ethernet and BACnet MS/TP • BACnet/IP and BACnet Ethernet • BACnet/IP and BACnet Ethernet and BACnet MS/TP • Two BACnet/IP networks IP Network Support • Web server for commissioning and troubleshooting • Communication diagnostic web page • BACnet/IP Broadcast Management Device (BBMD) • Foreign Device Registration (FDR) Flexible Communications • 10/100 Mbps Ethernet with auto-negotiation and Auto-MDIX • Optically isolated MS/TP port • MS/TP baud rates range from 9.6–76.8 kbps • Jumper-selectable MS/TP bias and termination Convenient Installation • 24 VAC/VDC (± 10%), 47–63 Hz input voltage • Din-rail mounted BASautomation CONTROLS

 Open the catalog to page 1
BAS Router   BACnet ®  Multi-Network Router-2

Data Sheet — BAS Router BAS Router — BACnet® Multi-Network Router The BAS Router is housed in a metal case that mounts on 35-mm DIN-rail and is powered from a 24 VAC/VDC (± 10%) source. There is one MS/TP port and one 10/100 Mbps Ethernet port. The MS/TP port offers an optically-isolated transceiver. It has a removable 3-pin terminal block for the EIA-485 connection. Logically, 255 devices can be addressed, but physically, the number of devices depends upon device loading. Up to 31 full-load EIA-485 devices can share the same MS/TP bus segment as the BAS Router. For half-load devices, there can...

 Open the catalog to page 2
BAS Router   BACnet ®  Multi-Network Router-3

Data Sheet — BAS Router BACnet/IP UDP Port 1 BACO MS/TP Tolerance O Strict Lenient Save Changes Secondary BACnet/IP UDP Port 0000 Secondary BACnet/IP Network 0 Save Changes

 Open the catalog to page 3
BAS Router   BACnet ®  Multi-Network Router-4

Data Sheet — BAS Router BAS Router Parameters Main Settings Device Parameters Default Value Description Device Name BASRT-Bxxxxxx The unique default value ends with the last 6 characters of the unit’s Ethernet MAC address. You can edit it to be up to 20 characters. Device Instance 0 The router device instance is a 22-bit decimal value (0–4,194,303). Each BACnet device has a unique device instance. BACnet Ethernet Parameter Default Value Description BACnet Ethernet Network 0 BACnet/IP Parameters 16-bit decimal value (1–65534). Each BACnet network, regardless of technology, must have a unique network...

 Open the catalog to page 4
BAS Router   BACnet ®  Multi-Network Router-5

Data Sheet — BAS Router BAS Router Parameters Advanced Settings — BBMD BBMD Parameters Default Value Description BBMD Enable Check to enable BACnet/IP Broadcast Management Device (BBMD). BBMD UDP Port Primary Normally the primary port is selected. The secondary port is used in very special applications. Accept FDR Checked Secondary BACnet/IP UDP Port 0000 Uncheck to disable foreign devices from registering with this router. Enter secondary UDP port as a 16-bit hex value (0-FFFF) when operating with two BACnet/IP BACnet networks. In this case use BAC1 if it is available. Secondary BACnet/IP Net...

 Open the catalog to page 5
BAS Router   BACnet ®  Multi-Network Router-6

Data Sheet — BAS Router BACnet Protocol Implementation Conformance (PIC) Statement BACnet Multi-network Router BACnet Protocol Implementation Conformance Statement (Annex A) Vendor Name: Contemporary Controls Product Name: BAS Router Product Model Number: BASRT-B Applications Software Version: Firmware Revision: 2.6 BACnet Protocol Revision: 2 Product Description: Device to route between BACnet/IP, ISO 8802-3 and MS/TP networks. BACnet Standardized Device Profile (Annex L): □ BACnet Operator Workstation (B-OWS) □ BACnet Application Specific Controller (B-ASC) □ BACnet Building Controller (B-BC)...

 Open the catalog to page 6
BAS Router   BACnet ®  Multi-Network Router-7

Data Sheet — BAS Router Wiring Diagrams Since the BAS Router incorporates a half-wave rectifier circuit, it can share the same 24 VAC power with other half-wave rectified devices. It can also be powered from a 24 VDC source. A redundant power connection exists for back-up power schemes. The BAS Router incorporates a 3-wire optically-isolated EIA-485 interface for the MS/TP connection, allowing better circuit protection and noise immunity. To connect to other 3-wire devices simply make a one-to-one connection to the other devices. But when connecting to 2-wire non-isolated devices, the signal...

 Open the catalog to page 7
BAS Router   BACnet ®  Multi-Network Router-8

Data Sheet — BAS Router Specifications Power Requirements Operating Temperature Storage Temperature Relative Humidity Ethernet Communications IEEE 802.3 10/100 Mbps data rate 10BASE-T, 100BASE-TX physical layer 100 m (max) CAT5 cable length MS/TP Communications ANSI/ASHRAE 135 (ISO 16484-5) 9600, 19200, 38400, 76800 bps data rate EIA-485 physical layer 1200 m (max) cable length Green = 100 Mbps Yellow = 10 Mbps Flash = activity Flashing Green = receive activity Regulatory Compliance CE Mark; CFR 47, Part 15 Class A; RoHS UL 508, C22.2 No. 142-M1987 Ordering Information Model BAS Router BACnet...

 Open the catalog to page 8

All Contemporary Controls GmbH catalogs and technical brochures

  1. BASgatewayLX

    12  Pages

  2. BAS Remote

    9  Pages

  3. BAS Router

    8  Pages

  4. EISX Series

    6  Pages

  5. EICP Series

    4  Pages

  6. EIPE

    4  Pages

  7. EIMK

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.