Catalog excerpts
SHEET BASremote — Versatile BACnet/IP Controller/Gateway The BASremote series provide the system integrator a flexible building block when integrating diverse building automation protocols or when expanding the number of points in a building automation system. By supporting open system protocols such as BACnet®, Modbus and Sedona Framework™ SOX, the BASremote series is easily adaptable. For small systems, it can operate stand-alone. For larger systems, it can communicate to supervisory controllers over Ethernet. Depending upon the model, the BASremote has the flexibility to provide the following: Versatile Control Device — remote I/O, router, gateway and controller • • • • • • • • • • Web-page configuration BACnet/IP remote I/O Modbus TCP remote I/O Modbus Serial to Modbus TCP router Modbus Serial or TCP to BACnet/IP gateway Modbus Master to Modbus TCP or serial slaves Certified Sedona Framework Controller® Power over Ethernet (PoE) Customisable webpages Web Services Flexible Input/Output — expandable with the addition of expansion I/O modules • • • • • • Six universal input/output points web-page configurable Two relay outputs Thermistor, voltage, current, contact closure and pulse inputs Voltage, current and relay outputs 2-wire Modbus Serial expansion bus Expansion port for up to three expansion I/O modules
Open the catalog to page 1Data Sheet — BASremote BASremote Master – Versatile BACnet/IP Controller/Gateway The BASremote Master provides the ultimate in flexibility. It can be used for expansion I/O at remote locations where an Ethernet connection exists. Its built-in router and gateway capabilities address unique integration needs where more than one communications protocol is involved. It can operate as a function block programmable controller with its resident Sedona Framework 1.2 virtual machine. Powered by a Linux engine, the BASremote Master can operate as BACnet/IP and Modbus TCP remote I/O, Sedona Framework...
Open the catalog to page 2Data Sheet — BASremote Some Common Components Used In Function Block Programming The HVAC Group operations that facilitate control The Scheduling Group scheduling operations based upon time of day convenient functions for developing control schemes LSeq ReheatSeq Reset Tstat Linear Sequencer — bar graph representation of input value Reheat sequence — linear sequence up to four outputs Reset — output scales an input range between two limits Thermostat — on/off temperature controller DailySc Daily Schedule Boolean — two-period Boolean scheduler DailyS1 Daily Schedule Float — two-period float...
Open the catalog to page 3Data Sheet — BASremote juatn Unltl[EHpamion untt 1 j| Expansion Unit Z |[¥iipjn&ian Unil 3. Help I Vfcit our Website fidS Remote help section. Main Unit fModtHi* Utility] [Sat Time] Current Setting* Unii Mamf : hlaroi Unlit BltOtl Prvir In^nt- 243L LED SUIIE Typical I/O Point Configuration Screen
Open the catalog to page 4Data Sheet — BASremote Powered by Sedona Framework for Implementing Control The BASremote Master incorporates Sedona Virtual Machine (SVM) technology developed by Tridium and compatible with their Niagara Framework™. Using established Tridium tools such as Niagara Workbench or Sedona Workbench, a system integrator can develop a control application using Workbench's powerful drag-and-drop visual programming methodology. Once developed, the program remains stored in the BASremote Master and executes by way of the SVM. The application can run standalone in the BASremote Master or interact with...
Open the catalog to page 5Data Sheet — BASremote BACnet Protocol Implementation Conformance (PIC) Statement Versatile BACnet/IP Controller/Gateway BACnet Protocol Implementation Conformance Statement (Annex A) Date: Vendor Name: Contemporary Controls Product Name: Product Model Number: Applications Software Version: BACnet Protocol Revision: 2 Product Description: BACnet/IP compliant 8-point Sedona Framework controller with Modbus Gateway. BACnet Standardized Device Profile (Annex L): BACnet Operator Workstation (B-OWS) BACnet Advanced Operator Workstation (B-AWS) BACnet Operator Display (B-OD) BACnet Building...
Open the catalog to page 6Data Sheet — BASremote Wiring Diagram loop supply pulse input Pulse Generator When configured control devices that use can share common control transformer if properly sized BAS Remote I/O expansion units located in the same control cabinet power supply as the master Isolated BA-485 Modbus devices. Optional tabs for surface-mounting (2 pieces) millimeters (inches)
Open the catalog to page 7Data Sheet — BASremote Specifications Universal Inputs/Outputs (Channels 1–6) Configured As Characteristics Analog input Temperature input Contact closure input Pulse input Analog output 0–10 VDC or 0–20 mA scalable by user. 10-bit resolution. Input impedance 100 kΩ on voltage and 250 Ω on current. Type II or type III thermistors +40°F to +110°F (+4.4°C to +44°C) Excitation current 2 mA. Open circuit voltage 24 VDC. Sensing threshold 0.3 VDC. Response time 20 ms. 0–10 VDC scalable by user. User adjustable threshold. 40 Hz maximum input frequency with 50% duty cycle. 0–10 VDC or 0–20 mA...
Open the catalog to page 8Data Sheet — BASremote Specifications (continued) RJ-45 Pin Assignments Signal Common Other pins Expansion Port (DN/UP) Pin Assignments Terminal Electromagnetic Compatibility Standard Test Method Test Levels EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-6 EN 61000-4-11 CISPR 22 CISPR 22 ANSI C63-4 Electrostatic Discharge Radiated Immunity Fast Transient Burst Voltage Surge Conducted Immunity Voltage Dips & Interruptions Radiated Emissions Conducted Emissions Radiated Emissions 6 kV contact & 8 kV air 10 V/m, 80 MHz to 1 GHz 1 kV clamp & 2 kV direct 2 kV L-L & 2 kV L-Earth...
Open the catalog to page 9All Contemporary Controls GmbH catalogs and technical brochures
-
BASgatewayLX
12 Pages
-
BAS Remote
9 Pages
-
BACnet Multi-Network Router
8 Pages
-
Portable BASrouter
9 Pages
-
BAS Router
8 Pages
-
EIRX28M-100T/4GT
5 Pages
-
EISX Series
6 Pages
-
EIDX MP Series
8 Pages
-
EICP Series
4 Pages
-
EIPE
4 Pages
-
EIMK
4 Pages
-
AI-SRVR server
6 Pages