Portable BASrouter SHEET Portable BASrouter — BACnet® Multi-Network Router The Portable BASrouter provides stand-alone routing between BACnet networks such as BACnet/IP, BACnet Ethernet, and BACnet MS/TP — thereby allowing the system integrator to mix BACnet network technologies within a single BACnet internetwork. There are two physical communication ports on the Portable BASrouter. One is a 10/100 Mbps Ethernet port and the other is an isolated MS/TP port. Configuration is accomplished via a web page. Versatile Routing Between … • BACnet/IP and BACnet MS/TP • BACnet Ethernet and BACnet MS/TP • BACnet/IP and BACnet Ethernet • BACnet/IP and BACnet Ethernet and BACnet MS/TP IP Network Support • Web server for commissioning and troubleshooting • Communication diagnostic web page Flexible Communications • 10/100 Mbps Ethernet with auto-negotiation and Auto-MDIX • Optically isolated MS/TP port • MS/TP baud rates range from 9.6–76.8 kbps Convenient Installation • Powered via a USB port in a laptop • Compact plastic case can be easily stored

 Open the catalog to page 1
BACnet Multi-Network Router-2

Data Sheet — Portable BASrouter Portable BASrouter — BACnet® Multi-Network Router The Portable BASrouter is housed in a plastic case that is powered from a USB port on a laptop computer. There is one MS/TP port and one 10/100 Mbps Ethernet port. The MS/TP port offers an optically-isolated transceiver. It has a removable 3-pin terminal block for the EIA-485 connection. Logically, 255 devices can be addressed. Physically, the number of devices depends upon device loading. Up to 31 full-load EIA-485 devices can share the same MS/TP bus segment as the Portable BASrouter. For half-load devices, there...

 Open the catalog to page 2
BACnet Multi-Network Router-3

Data Sheet — Portable BASrouter BASRPT-B Configuration MAC Address 00-50-DB-00-C5-46 Firmware Revision 2.7.2 This screen displays a log of events that facilitate troubleshooting. Use this information when discussing any of your routing issues with Contemporary Controls technical support staff.

 Open the catalog to page 3
BACnet Multi-Network Router-4

Data Sheet — Portable BASrouter Portable BASrouter Parameter Settings Device Parameters Default Value Description Device Name BASRT-Bxxxxxx The unique default value ends with the last 6 characters of the unit’s Ethernet MAC address. You can edit it to be up to 20 characters. Device Instance 0 The router device instance is a 22-bit decimal value (0–4,194,303). Each BACnet device has a unique device instance. Device Location The default value can be edited to be up to 20 characters. BACnet Ethernet Parameter Default Value Description BACnet Ethernet Network 0 BACnet/IP Parameters 16-bit decimal...

 Open the catalog to page 4
BACnet Multi-Network Router-5

Data Sheet — Portable BASrouter BACnet Protocol Implementation Conformance (PIC) Statement Portable BAS Router Portable BACnet Commissioning Tool BACnet Protocol Implementation Conformance Statement (Annex A) Date: 5 September 2014 Vendor Name: Contemporary Controls Product Name: Portable BAS Router Product Model Number: BASRTP-B Applications Software Version: Firmware Revision: 2.0 BACnet Protocol Revision: 2 Product Description: Device to route between BACnet/IP, ISO 8802-3 and MS/TP networks. BACnet Standardized Device Profile (Annex L): BACnet Operator Workstation (B-OWS) BACnet...

 Open the catalog to page 5
BACnet Multi-Network Router-6

Wiring Diagrams The Portable BASrouter features a USB 2.0 Full Speed Device Port that accepts the Type B plug of the USB cable that is included in the box. It takes 5 VDC from a host computer, while typically drawing 400 mA of current. It can operate from a USB hub, if desired, and no driver installation is needed. The device incorporates a 3-wire optically-isolated EIA-485 interface for the MS/TP connection — allowing better circuit protection and noise immunity. To connect 2-wire MS/TP Bus Wiring to other 3-wire devices, simply make a one-to-one connection to the other devices. But when connecting to...

 Open the catalog to page 6
BACnet Multi-Network Router-7

Data Sheet — Portable BASrouter Typical Installation Connector Pin Assignments 3-pin (MS/TP) (All other pins are unused.) (All other pins are unused.)

 Open the catalog to page 7
BACnet Multi-Network Router-8

Data Sheet — Portable BASrouter Specifications Power Requirements Operating Temperature Storage Temperature Relative Humidity Protection Ethernet Communications MS/TP Communications USB power: 5 VDC ±10%, 400 mA, 2 W 0°C to 60°C -40°C to 85°C 10-95%, non-condensing IP30 IEEE 802.3 10/100 Mbps data rate 10BASE-T, 100BASE-TX physical layer 100 m (max) CAT5 cable length ANSI/ASHRAE 135 (ISO 16484-5) 9600, 19200, 38400, 76800 bps data rate EIA-485 physical layer 1200 m (max) cable length Power Green = power OK Ethernet Green = 100 Mbps Yellow = 10 Mbps Flash = activity Flashing green = receive...

 Open the catalog to page 8

All Contemporary Controls GmbH catalogs and technical brochures

  1. BASgatewayLX

    12  Pages

  2. BAS Remote

    9  Pages

  3. BAS Router

    8  Pages

  4. EISX Series

    6  Pages

  5. EICP Series

    4  Pages

  6. EIPE

    4  Pages

  7. EIMK

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.