Overview: The document describes the advantages and technical specifications of the CPS-B pump control system with a soft starter, designed for automatic control of one or two pumps, with a maximum capacity of 11 kW/25A. It highlights the system's compact design, high-quality equipment, and suitability for explosive areas (ATEX).
Specifications: The CPS-B system features a compact housing (400x390x170mm), a main circuit breaker, manual motor starter, and a QVGA color touch screen for monitoring pump operations. It includes a soft starter for three-phase systems, allowing stepless acceleration of motors, reducing maintenance costs, and extending pump life.
Technical Details: The system operates at 400V/230V AC with a control voltage of 230V AC/24V DC. It supports a temperature range of 0 to +50°C and includes potential-free alarm contacts. The housing is made of ABS plastic with protection class IP54.
Features: Key features include adjustable control parameters, alarm relay, ATEX mode, phase sequence monitoring, integrated buzzer, and a time switch for compressor function. It also offers graphical displays for level and operating states, motor current indication, and RS232 connection for software updates.
Options and Accessories: The system can be equipped with additional accessories such as zener barriers, panel heaters, flashing lights, and small compressors. It supports multiple languages and includes password protection and maintenance displays.
Compliance: The system complies with DIN EN 60079 standards for safe operation in explosive areas, with specific installation requirements for safe areas.
See more

Catalog excerpts

Pump Control CPS-B With Soft Start - New Generation-1

Pump control CPS-B with soft starter Pump control CPS-B with soft starter ... gentle on material! Compact pump control CPS-B1 and -B2 with soft starter of the latest generation, are designed for the automatic control of one or two pumps (max. 11 kW/25A) With high quality basic equipment in standard execution (main circuit breaker, manual motor starter, Manual-0-Auto, new QVGA color touch screen for operating conditions of the pumps, soft start, ...) optionally equipped with additional accessories. This pump control can be among other things for the operation of pumps and sensors in explosive areas (ATEX). ** pump control CPS-B2 - soft starter - new generation Advantages  compact housing (w400xh390xd170mm)  high quality basic equipment in standard execution (main circuit breaker, manual motor starter, soft start, Manual-0-Auto, QVGA color touch sreen for operating conditions of the pumps, external serial PC-interface, display illuminated, extensive functionality and adjustability - see detailed description)  Soft starter (three phase systems) - the soft starter controls the voltage steps from a selectable initial value to one hundred percent this allows a stepless acceleration of under load motors from standstill  Soft start - this cuts maintenance costs and extends the pump‘s lifetime  suitable for the operation of pumps (EEx d) in explosive areas (ATEX) **  installation areas e.g. for two zener barriers (operation of measuring and control technology as safe electrical circuits)*

 Open the catalog to page 1
Pump Control CPS-B With Soft Start - New Generation-2

Adjustable control parameter ■ alarm relay, programmable function ■ ATEX-Mode ■ date / time ■ phase sequence monitoring and phase drop monitoring via soft start ■ turn-on-delay ■ on / off switch levels of the pumps ■ reading errors ■ integrated buzzer (can be turned on/off) ■ integrated time switch for compressor function ■ short pump start against locking ■ load changeover time for pumps ■ max. pump operating time ■ follow-up time ■ password protection ■ pump power monitoring (electronic) ■ soft start - adjustable parameters (start / stop ramp, kick start, starting voltage, current monitoring,...