Group: Condair Group
Catalog excerpts
CONDAIR ESCO Live steam humidifier With 100% steam tight rotary valve Humidification & Evaporative Cooling
Open the catalog to page 1Condensation-Free Live Steam Humidification Patented precision nozzles enable condensate-free steam Inner nozzles draw steam from the middle of the distribution pipe where it is at its hottest and driest. This guarantees that droplets aren’t released into the air handling system. The nozzles are made of robust stainless steel. They are reliable and durable with no fear of leaks. Standard connection Standardised flange connections enable simple and safe connection to a steam network. Rotary disk valve is completely leak proof once closed The ceramic rotary valve is completely steam tight...
Open the catalog to page 2Steam Distribution System Condair ESCO steam distribution systems with ready fitted connections are built in a modular fashion. With no need for thread sealants on site they are easy to install and leak-free. Condair ESCO Model: GGG40 Steam connection unit in tried and tested cast iron GGG40 material. Condair ESCO Model: AISI304 Steam connection unit in stainless steel AISI304 for special requirements on the steam circuit. Condair ESCO humidifiers set the standard for live steam humidification. Innovative technology and quality construction provide unrivalled performance. The system can...
Open the catalog to page 3The Condair ESCO ceramic rotary disk valve in open position The Condair ESCO ceramic rotary disk valve in closed position
Open the catalog to page 4Rotary Disk Valve is Completely Steam Tight When Closed and Oers 0-100% Modulation The Condair ESCO’s ceramic rotary disc valve provides 0-100% modulation and does away with the problems associated with vertical stroke valves. Due to the design, the valve is capable of accurately delivering a linear output throughout the entire regulating range. When closed the valve is absolutely steam tight and prevents any steam from penetrating into the steam lance when the unit is switched o. This avoids unwanted condensation from occurring after steam leakage. Minimal torque and optimum reliability...
Open the catalog to page 5Dry Steam Distribution with Short Evaporation Distance Short evaporation distances are crucial for reliable and hygienic steam humidification. The steam must never come into contact with components within the air handling unit. This would result in wetting, corrosion and hygiene risks. Condensate-free steam with patented humidification nozzles Dry steam delivery is guaranteed by the tiny nozzles that are located inside the Condair Esco’s steam lance. The steam is taken only from the centre of the lance, where it is at its hottest and driest. This provides a very short evaporation distance...
Open the catalog to page 7System overview Series DL40 with single pipe distribution Series DL40 with double pipe distribution Series DL40 with triple pipe distribution Series DR73 with vertical pipe distribution Technical Data Series Steam capacity Steam pressure Evaporation distances are for guidance only. For exact evaporation distances please contact us. Condair AG Member of the Walter Meier Group Verkauf Schweiz, Talstrasse 35-37, 8088 Pfäkon SZ Tel: +41 55 416 6111 - info@condair.com - www.condair.com
Open the catalog to page 8All Condair Group AG catalogs and technical brochures
-
Food industry
10 Pages
-
Condair Group Corporate Brochure
24 Pages
-
Automotive brochure
4 Pages
-
Condair MLP RO
6 Pages
-
Condair RO-A
6 Pages
-
Condair DP
16 Pages
-
Draabe TurboFog
8 Pages
-
Condair HP
2 Pages
-
Condair DL
11 Pages
-
Condair CP3mini
6 Pages
-
Defensor PH15 and PH28
12 Pages
-
Condair ME
5 Pages
-
Condair OptiSorp
4 Pages
-
Condair GS
8 Pages
-
Condair EL
5 Pages
-
Condair RS
5 Pages
-
Condair JetSpray
8 Pages
-
Draabe NanoFog Evolution
8 Pages
-
Condair SE
4 Pages
-
Condair PureFlo
4 Pages
-
e-LINKS
4 Pages
-
Condair Atomisers
4 Pages
Archived catalogs
-
ABS3
4 Pages
-
Defensor Mk5
6 Pages
-
Condair Dual2
6 Pages