Catalog excerpts
with serial RS485/RS232 output ith CO 2 w e e and ressur lity, accurat heric p • ua tmosp high q midity idity, a r design • tive hu 17025 d rela e, hum interio O/IEC d eratur ure an f temp industry an nt temperat y with EN IS ors o sens uts • abilit mbie mable y outp from a e with trace ogram ts and rela computed t • pr tifica te inpu rs • values libration cer a wo-sta so t en ble c able s tracea
Open the catalog to page 1Applications Building management needs quality and reliable components. Our instruments which measure temperature, humidity, atmospheric pressure and CO2 are an integral part of these industry-leading solutions. Industry is distinguished by its capital demands. The competition across the market is still growing and creates additional pressure on the prices. Our company has a good understanding of this situation and thus provides very reliable and precise products for a very competitive price. Měřící a záznamový systém MS v různých provedeních Pharmaceuticals and laboratories Technological...
Open the catalog to page 2Sensors and regulators with serial output RS485/RS232 and with relay outputs Sensors and regulators of temperature, humidity, barometric pressure and CO2 concentration convert measured values to digital serial output the RS485 and RS232 link parameters. These devices support communication protocols Modbus RTU and protocol compatible with standard Advantech-ADAM. By means of this communictaion via serial line the measured values can be read and some settings changed. Parameters can be set from the regulator´s keypad or from a computer. Computerized design ensures maximum long term stability,...
Open the catalog to page 3Programmable industry regulators Choose the appropriate sensor model Regulators with relay and power relay output Programmable regulators with relay outputs are designed to measure temperature, relative humidity and CO2 concentration in chemical non-aggressive environment. Used for alarms signalization and control of external devices.The devices are available in wall and duct mounting models or with a cable probe. Programmable regulators with outputs to power relays are powered by AC 110V to 240V. The advantage is the possibility of direct control of external power circuits. Two output...
Open the catalog to page 4DIGITAL .SENSORS. Programmable industry regulators Regulators with two-state inputs, with relay output and serial output RS485/RS232 The regulators are designed for online monitoring of temperature in °C or °F, relative humidity of air without aggressive substances, atmospheric pressure, CO2 and three binary inputs for detection of two values. Measured temperature and relative humidity can be recalculated to other humidity interpretation like dew point, absolute humidity, specific humidity, mixing ratio and specific enthalpy. You can set the altitude correction (offset) and choose the...
Open the catalog to page 5Programmable industry regulators Choose the appropriate sensor model Regulators with relay and serial output RS485/RS232 MEASURED VALUES * Custom range 10 000 ppm for extra fee. Accuracy ± (100ppm+5% of measured value). tfComputed humidity values Specific humidity Accuracy: ±2,1g/kg at ambient temperature T < 35°C Range: 0 to 550 g/kg jninunjn) irri iTTl u Ti inuiMIjnL iTTl ITTl ITTl Dew point temperature Accuracy: ±1,5°C at ambient temperature T<25°C and relative humidity RH>30%, for more details see manual. Range: -60 to +80 °C (-76 to 176 °F) Absolute humidity Accuracy: ±1,5g/m3 at...
Open the catalog to page 6Industry design Programmable sensors with serial output without relay Programmable sensors with serial output RS485/RS232 limits may be changed by user. Electrical wiring of sensor with serial output RS232 Supply from communication port Terminal for power and signal RS485/RS232 – for more details please see electrical wiring of sensors page 13. External mounting holes - easy and fast mounting without the need to take off lid cover. Sensor version with watertight male connector TxxxxL For easy connection/disconnection of the output cable is used TxxxxL version with Lumberg connector (IP67)...
Open the catalog to page 7DIGITAL SENSORS■ Programmable sensors with serial output without relay Industry design Programmable sensors with serial output RS485/RS232 MEASURED VALUES Specific humidity Accuracy: ±2g/kg at ambient temperature T < 35°C Range: 0 to 550 g/kg Dew point temperature Accuracy: ±1,5°C at ambient temperature T<25°C and relative humidity RH>30%, for more details see manual. Range: -60 to +80 °C (-76 to 176 °F) Absolute humidity Accuracy: ±1,5g/m3 at ambient temperature T < 25°C for more details see manual. Range: 0 to 400 g/m3 Mixing ratio Accuracy: ±2g/kg at ambient temperature T < 35°C Range: 0...
Open the catalog to page 8Interior design Optional accessories for sensors and regulators Programmable sensors with serial output RS485 and RS232 Mounting accessories Programmable transmitters with RS232 or RS485 serial interface are designed to measure temperature, relative humidity, barometric pressure and concentration CO2 in especially in interiors, in building energy management and HVAC systems. They are made for easy installation in a standard way into a flush-mounted wiring box. These devices support communication protocols Modbus RTU and protocols compatible with standard Advantech-ADAM. PP90 - right-angled...
Open the catalog to page 9DIGITAL SENSORS , Comet Database - Monitoring of temperature, relative humidity, atmospheric pressure and CD. Comprehensive system multiple networks RS485 Sensors RS485 utility supports » COMET sensors with serial output RS485/RS232 » 3rd party devices communicating via Modbus RTU protocol » multiple networks (can connect multiple serial communication ports) » sending data to a remote server (Comet Database can be installed on another PC) » alarm setting SMs Sensor RS485/232 utility This utility provides communication between sensors with RS485/232 output and software system Comet Database....
Open the catalog to page 10All COMET SYSTEM catalogs and technical brochures
-
Cometeo - Meteo shields
5 Pages
-
Monitoring Systems
9 Pages
-
Multilogger
4 Pages
-
WebSensors with Ethernet output
13 Pages
-
Radiation Shield COMETEO
5 Pages
-
DATALOGGERS
11 Pages
-
Mobile DATALOGGERS
5 Pages
-
PROFESSIONAL MEASURING EQUIPMENT
11 Pages