1. Catalogs
  2. Comde-Derenda GmbH
  3. Densistat D100 / D100i0

Densistat D100 / D100i0

Densistat D100 / D100i0

Densistat D100 / D100i0

Product catalog summary
Overview: The Densistat Model 100 by Comde-Derenda GmbH is a device designed for monitoring the density of SF6 gas in high-voltage circuit breakers. It is suitable for both indoor and outdoor use and features a manometer for relative pressure measurement, referenced to 20°C.
Specifications:
  • Pressure Range: 0 to 10 bar relative (0 to 145 psi relative).
  • Large pressure gauge with a diameter of 100 mm.
  • Pressure connection can be concentric or angled in four directions.
  • High long-term stability and precise switching accuracy.
  • Rugged construction with protection rating IEC 60529: IP 65.
  • Up to four micro switches can be installed.
Functionality: The device uses a reference chamber filled with the same gas to detect density changes. A pressure differential causes deformation of a metal bellows, which actuates micro switches for signaling. The switching thresholds are adjustable via lockable screws.
Technical Data:
  • Hysteresis: Less than 0.1 bar (1.5 psi).
  • Switching Accuracy: ±0.08 bar (1.2 psi).
  • Threshold: ±0.05 bar (0.7 psi).
  • Leakage: Less than 0.005 bar/year.
  • Operating Temperature: -40 to +70°C (-40 to +158°F).
  • Storage Temperature: -50 to +80°C (-58 to +176°F).
  • Vibration Resistance: Greater than 4 g (20 to 80 Hz).
  • Electrical Rating: AC 250 V, 10 (2) A; various DC ratings.
  • Material: Anodized AlSi1MgMn, powder-coated AlSi12, stainless steel 1.4541/1.4301, acrylic glass window.
  • Weight: 790 g.
Design and Construction: The device includes a color-coded analog pressure indicator and a GORE-TEX® membrane vent to prevent condensation. The junction box and cable gland are designed for easy installation and removal.
Additional Information: Comde-Derenda GmbH reserves the right to change specifications, design, or materials without notice, adhering to engineering principles and quality practices.
See more

Catalog excerpts

Densistat D100 / D100i0-1

Gas Density and Pressure Monitoring Densistat 100 for SF6 and other Gases Type: D100 for indoor and outdoor use The Densistat Model 100 is designed specially to monitor the density of the SF6 gas used to blanket highvoltage circuit breakers. It incorporates a manometer for relative pressure, referenced to 20 °C. Large pressure gauge (Ø 100 mm) Pressure connection concentric or angled in any of four directions High long term stability Precise switching accuracy Up to four micro switches The Densistat 100 uses a chamber filled with an identical gas as a reference. When the reference chamber and the switching enclosure are at the same temperature, a change in density in the latter will induce a pressure differential. The switching enclosure and the reference chamber are separated one from another by a metal bellows. A differential in pressure will cause a deformation of the bellows. This deflection motion is transferred via a switching rod with a switching plate to actuate the micro switch required for signaling purposes. The switching thresholds can be adjusted by way of lockable screws at the switching cam. The pressure connection can be installed at the factory either concentric to the housing at the rear or angled in any of the four directions. Up to four micro switches with double-throw contacts can be installed in the Model 100. The contact outputs for the micro switches terminate in an appropriate multi pole socket inside the junction box. The corresponding connector cable passes to the outside world through a suitable cable gland. The junction box cover, the cable gland, the connector cable and the plug-type connector form a unit that can easily be mounted and removed with just a screwdriver. The arrangement of the measurement mechanism and the use of vibration-resistant micro switches eliminate any shock-induced chattering at the switching contacts. The analog pressure indicator with color-coded scale (Ø 100 mm) shows the relative pressure of the SF6 gas, referenced to 20°C in the switching enclosure. If the density of the gas drops as a result of a leak, the change will be indicated by the pointer as it moves along the color-coded scale. The colors and the transition points along the scale can be specified by the customer. The micro switch response points are then calibrated to the specified values. The unit is equipped with a GORE-TEX® membrane vent to prevent condensation. Comde-Derenda GmbH Kieler Strasse 9, 14532 Stahnsdorf / Germany

 Open the catalog to page 1
Densistat D100 / D100i0-2

Gas Density and Pressure Monitoring Technical Data Densistat 100 Range: Hysteresis: Switching accuracy: Threshold: Leakage of reference chamber: Operating temperature: Storage temperature: Indicator diameter: Tolerance of indication: Vibration (min. difference 0.05 bar from changeover point): Protection: Connector: Standard 3 micro switches: Electrical Rating: Switch contacts load, charge resistive (inductive): Electric strength: Surge: Cable gland: Material Pressure connection: Housing: Reference system: Window, resistant to UV, Ozone: Typeplate, resistant to UV, Ozone, climate, chemicals and...

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.